All of the following parameters are controlled by a storage tank temperature sensor:
• Setpoint
= Target Temperature (120°F) Low fire only above this point
• Offset
= Off Setpoint (3) = 123°F off
• Hysterese
= On Setpoint (8) (120 + 3 - 8 = 115°F)
• Proportional Band
= Modulation range (4) (120 - 4 = 116°F, modulation begins)
The appliance turns on at 115°F and when the temperature reaches 116°F the flame will begin to modulate down
(approximately 25% of the modulation range per degree F of increase in this example). At 120°F, it will be at low
fire and will remain there unless the temperature drops below 120°F and it will modulate back up. If it continues to
increase, it will shut down at 123°F.
WATER HEATER OPERATING SAMPLE
Modulation Range
Setpoint
Se Offset
Se Offset - Hysterese
Bandwidth
Burner On
Burner Off
115°
119°
120°
121°
122°
123°
124°
125°
126°
116°
118°
117°
Temperature
Low Fire
53