20
PART 2. ELECTRICAL
(FIGURE 2-1) .2 FIELD WIRING CONNECTIONS
A. Terminals 1 & 2
External Sensor Connection (T6)
— System temperature sensor,
senses water temp in a heating
loop.
B. Terminals 3 & 4
Outdoor Sensor (T4) — Outdoor
air sensor, set point will adjust
based on outdoor air temperature
(not needed if 0-10 VDC output is
connected)
C. Terminals 5 & 6
0–10 VDC — Connect a
0–10 VDC output here to
vary set point temperature.
Requires a connection to each
appliance.
D. Terminals 7& 8
Fault Service — Alarm bell or light
may be connected here to indicate
that the appliance is a hard lockout.
E. Terminals 9 & 10
Additional Heat Demand —
dry contacts that will close a
thermostat on an extra appliance
if the appliance is at 100% of
capacity.
F. Terminals 11 & 12
Room Thermostat — Normally
jumped. A room thermostat may
be connected here to enable/
disable the appliance.
G. Terminal 13–17
Cascade Connection —
Communication cables get
connected here and “daisy
chained” to all appliances in a
cascade. This is polarity sensitive.
H. Terminals 18 & 19
Tank Sensor (T3) — Sensor
for indirect or direct DHW. An
aquastat may also be connected
here.
Terminals 20 & 21
Additional Safety Circuit. On .3
models, it contains the Water
Flow Switch; the burner door and
rear wall high limits in series.
I. Terminals 22 & 23
E-stop—Requires a parallel
wiring connection between
appliances back to E-stop switch
at rom wall.
B. INTERNAL WIRING CONNECTION (continued)
Summary of Contents for XL800
Page 6: ...6 PART 1 GENERAL INFORMATION As a Stand Alone Appliance HOT CONTROL MENU NAVIGATION ...
Page 7: ...7 PART 1 GENERAL INFORMATION Appliance as Part of a Cascade HOT CONTROL MENU NAVIGATION ...
Page 19: ...19 PART 2 ELECTRICAL B INTERNAL WIRING CONNECTION continued XL BCB LAYOUT ...
Page 21: ...21 PART 2 ELECTRICAL XL CASCADE BOX ...
Page 31: ...31 PART 4 VENTING Direct Vent Terminal Clearances ...
Page 33: ...33 PART 4 VENTING Other Than Direct Vent Terminal Clearances continued ...
Page 69: ...69 PART 10 PARTS BREAKDOWN 1A 1B PART 10 PARTS BREAKDOWN 2 ...
Page 70: ...70 PART 10 PARTS BREAKDOWN 3 4 5 6 7 8 9A 9B 9C 10 4 ...