b) Shifting the positioning range upwards starting from the delivery state
In the following example, starting from the DS, the maximum possible positioning range is shifted
slightly
upwards
using the parameter “upper mapping end” (example for a PSD401/411,
PSD422/432 or PSD480/490):
Here, the upper mapping end was increased from the value 806,400 to 1,031,600. Consequently,
a higher proportion of the possible positioning range is in the positive range and a smaller
proportion in the negative range.
In the extreme case, the upper mapping end can be set so that the entire possible positioning
range is a
t values ≥ 0. With standard scaling (numerator = denominator = 400, i.e. 1 step = 0.9°)
and referencing value = 0, this special case results if the relevant value from the following table is
selected for the upper mapping end. The device then automatically adjusts the lower and upper
limits accordingly.
Device type
PSD
401/411,
422/432,
480/490
PSD
403/413,
481/491
PSD
424/434
PSD
426/436
PSD
428/438
Measurement range of the
absolute measuring system
4,032
rotations
992
rotations
1,944
rotations
1,280
rotations
983
rotations
Max. possible positioning
range
4,026
rotations
986
rotations
1,938
rotations
1,274
rotations
977
rotations
Upper mapping end
1,611,600
395,796
776,400
510,800
392,166
Lower limit
0
0
0
0
0
Upper limit
1,610,400
394,596
775,200
509,600
390,966
Positioning range starts at 0