PSx3xxDP Instruction Manual
10
4.4
Setting the device address and terminating resistors
Removing the protective cap provides access to two rotary switches for setting the device
address and a DIP switch to set the terminating resistors.
The rotary switches indicate the tens and ones places of the address selected. A setting
of 01 is the delivery state; the PSx3xxDP identifies itself using address 1 at the bus.
To activate the terminating resistors both switches must be in position ON (If active,
remove the connection to a following device).
Switch configurations:
PSx30xDP,
PSx31xDP-8,
Psx32xDP,
PSx31xxDP
PSx31xDP-14,
PSx33xDP-14
PSx34xxDP
Important: Always replace the protective cap after setting the address. This will
prevent dust and contaminants from entering the housing.
4.5
LED status
The red LED indicates the operating status of the Profibus DP.
LED status
Meaning
LED remains lit
The Profibus DP is not connected or is inactive
LED flashes
The instrument has detected data transfer activity on the bus and
identified the transfer rate.
LED is not lit
Provided the power supply is switched on, an unlit LED indicates
that the instrument is involved in bus communication.
The green LED indicates the status of the power supply.
LED status
Meaning
LED remains lit
Power supply of control unit and motor is activ
LED flashes
Power supply of the motor is inactive.
LED is not lit
Power supply of the control unit is inactive. The status of the
motor supply could not be detected in this case.