6
HRFEREEQ*C HRFEREEQ*2C HRFSEREEQ*C
97880C - 2/05
CHILLER SHELF
P/N 27638C
HOOK RODS (2)
P/N 101567443730
INSTALL (2) SCREWS
(P/N 101008343890) IN FRAME
BEFORE INSTALLING IN OPENING
5/16" SCREWS OR BOLTS
(10 REQ'D - NOT PROVIDED)
FRAME
SCREWS OR BOLTS
(NOT PROVIDED)
Figure 7 – HRFER-EE-Q Rough-In
Figure 8 – Rough-In Assembly
Single-Station Mounting Frame
Models
HRFER-EE-Q
1.
Cut a rectangular wall opening
18-3/4” (475 mm) W x
37-3/4” H (959 mm) and 4-1/2” (114 mm) above the floor line
(see Figure 8). The dimensions are required to obtain proper
rim and bubbler heights for compliance with ANSI standard
A117.1.
2.
Reinforce the wall opening
on all sides to adequately
support the water fountain. This reinforcement must support
up to 150 lbs. static load and provide a means for securing
the frame assembly in place.
NOTE:
Building construction must allow for adequate air flow
on both sides and top of remote chiller unit.
Minimum of 4” (102 mm) is required.
3.
Install plumbing and electrical rough-ins.
A junction box
for a (3) wire, 10 amp branch circuit is provided on the
inside of the chiller. (Standard 120 Volts, 60 Hz, and single
phase.)
4.
Remove frame and related hardware
from packaging.
Release the two shelf rods by cutting cable ties.