Gemini™ Controller

Installation of the controller should be performed 
by a professional electrician in accordance with 
applicable electrical codes.

 Mount Controller 

The Gemini controller 
enclosure is gasket 
sealed and rated for 
installation in a 
corrosive chemical 
environment. The 
controller should be 
rigidly mounted to a 
wall or other 
permanent structure 
within the length of the 
electrical cable and 
convenient to the 
cylinder or ton valve 
and the actuator storage bracket. Installation of the 
controller should be performed by an electrician in 
accordance with applicable electrical codes. 

Maximum distance from actuator to controller must 
not exceed 17 ft (5.2m). 

See Actuator Cable 

Extension info on page 18.

 

The back of the 
Gemini enclosure is 
equipped with tapped 
screw holes for 
mounting tabs. The 
tabs and attach 
screws are taped to 
the inside of the 
enclosure door for 
shipping. Attach tabs 
to enclosure using 
screws and tapped holes. Fasten the controller to a 
wall or structure using the mounting tabs and  proper 
anchors for the material. The controller should be 
mounted in a location which allows its status lights to 
be easily viewed by operators when working on the 
ton container or cylinder.

It is recommended that 115 / 230 VAC power to the 

controller be supplied from a dedicated circuit with 
disconnect switch. Wiring should be through rigid 
PVC or liquid tight flexible PVC coated conduit. 
Connections and terminations should only be made 
in enclosures rated for the corrosive environment 
encountered in chlorine facilities (NEMA 4X). All 
controller entry fittings should be of the proper size 
and type to insure the gas-tight integrity of the 
enclosure is not broken at cable or conduit 
entrances. Molex Woodhead MAX-LOC® or similar 
fittings are preferred.

C. Actuator Storage Bracket

An actuator storage bracket is provided for each 
actuator. Install bracket on a wall or other structure in 
a location convenient to the cylinder or ton container 
and within reach of the actuator cable. The bracket 

helps prevent damage to the actuator and cable 
when not in use and during tank or cylinder change. 

D. Actuator Cable

The actuator is shipped 
with an electrical cable 
pre-wired to the actuator. 
This cable cannot be 
disconnected from the 
actuator in the field. If 
longer cable lengths are 
necessary, see 
acceptable method for 
cable extension on page 
18, and consult the factory.  

Connect actuator cable to the 
actuator terminal block inside the 
Gemini Controller (

see image and 

drawing on page 11 and 13). 

For 

proper polarity, the actuator wire 
color must match the color 
labeled on the terminal. 

Red = 

positive, black = negative

.

 

CAUTION  

Do not connect AC power to the controller or 

battery leads to battery terminals until instructed 

to do so. All other connections should be 

completed first. Connecting AC power to the 

improper terminal block will damage the 

controller.

 

Gravity  Mount  Actuator 

Storage Bracket

 

Gemini Controller

Mounting Tabs  

1/17 

 

 

 

 

 

 

3. 

Cable Entry Fittings

 

Clamp Mount  Actuator 

Storage Bracket 

Summary of Contents for Terminator

Page 1: ...Terminator Actuator with Gemini Controller Emergency Valve Shutoff System Installation Operation and Maintenance Manual Bulletin 800 06 1 17 For Chlorine Cylinders Ton Containers ...

Page 2: ... each item to prevent shipping damage Carefully inspect each item and report damages to the shipping agent Halogen Valve Systems or your local sales representative Inspect all packing materials before discarding to prevent loss of accessories mounting hardware or instructions Halogen Valve Systems or your local sales representative can provide technical consultation and personnel training on the i...

Page 3: ...8 B In Service Testing 8 C Corroded Valves 8 9 VII Maintenance 9 A Operational Testing 9 B Emergency Shutoff Testing 9 C Battery 1 Operating Characteristics 10 2 Storage 10 3 Replacement 10 D Microprocessor Circuit Board 11 VIII Troubleshooting 12 IX Typical Circuit Board Wiring 13 X Relay Interface Module Circuit Board 14 XI Relay Interface Module Wiring 15 XII Remote Input Circuit Wiring N O 16 ...

Page 4: ...ge testing and maintenance 2 One 1 remote mountable Emergency Shutoff Switch Normally Open momentary contact For additional switches order P N 6430 00 and specify Normally Open or Normally Closed contacts Additional Elements Required for Installation 1 115 VAC or 230 VAC electrical source for battery charging circuit dedicated disconnect 2 Corrosion resistant conduit and fittings 3 Suitable anchor...

Page 5: ...y falls to a critical level the controller will automatically initiate the valve closing sequence to protect against an unguarded system followed by an output relay signal alerting that a valve shutoff operation was performed The recommended installation includes a remote mountable emergency shutoff switch One switch is provided per controller as a standard accessory This switch should be located ...

Page 6: ...nduit Connections and terminations should only be made in enclosures rated for the corrosive environment encountered in chlorine facilities NEMA 4X All controller entry fittings should be of the proper size and type to insure the gas tight integrity of the enclosure is not broken at cable or conduit entrances Molex Woodhead MAX LOC or similar fittings are preferred C Actuator Storage Bracket An ac...

Page 7: ... connections are made connect wires for 115 230 VAC power Connect 115 230 VAC wires to the terminal block labeled 115 230VAC WHT L2 low side GRN G ground and BLK L1 high side See drawing on page 13 Conduit and fittings should be rated NEMA 4X to maintain a gas and liquid tight seal for the controller H Battery The battery is included but not pre installed in the Gemini controller Install battery i...

Page 8: ...r polarity and status indication This is done by test running each actuator BEFORE placing the actuator on a cylinder or tank valve TEST PROCEDURE 1 Place actuator in the storage rack or hold in a manner where drive bushing can be observed 2 Depending on actuator being observed press either TEST A or TEST B key on Gemini panel and observe rotation of bushing 3 Confirm that the actuator shaft and d...

Page 9: ...ushing should fully engage the wrench flats on the valve stem 7 The Terminator Actuator mounting rods are designed to straddle and loosely grasp the valve on either side of the outlet as shown in figure 2 The two rods on the actuator will fit inside the standard yoke and fit loosely on either side of the valve nozzle after the drive bushing is seated as shown in Figure 3 8 Confirm proper alignment...

Page 10: ...eates additional clearance between the vacuum regulator and the actuator Contact your local Halogen Valve Systems representative or factory for assistance with vacuum regulator compatibility C Ton Container Mounting Procedures 1 Make sure all piping connections are in accordance with The Chlorine Manual or local procedures The CGA 820 yoke and adapter assembly is the standard connection used to co...

Page 11: ...ing of it by the Terminator Gemini system Confirm that the Gemini controller panel lights are in the following normal conditions If an Armed Ready light is OFF but the actuator is connected to controller attempt to reset controller by pressing and holding the TEST B key until the BATTERY STATUS light turns OFF 6 seconds then release The system will reboot after which all status lights should indic...

Page 12: ...trusion of atmospheric moisture Your Halogen Valve Systems representative can provide information on devices engineered to dispense chlorine while precluding the introduction of contaminants A Operational Testing The system test sequence described in In Service Testing section B on page 8 should be performed each time a tank or cylinder change out is done For cylinders or ton containers kept in ex...

Page 13: ...es for cooling and recharging After a test cycle be sure that the BATTERY STATUS light is on and steady before proceeding with the next test Discharging below about 9 volts can damage the battery At that point the BATTERY STATUS light goes off and the battery cannot be recharged and must be replaced 2 Storage Spare batteries when not supplied a sustaining charge have a shelf life of approximately ...

Page 14: ... repair 1 Disconnect 115 230 VAC power at the source external to the control enclosure 2 Disconnect DC power supply input 3 Disconnect the battery leads from battery then from board 4 Disconnect the signal inputs and optional relay board if installed from the circuit board 5 Disconnect actuator cables from board 6 Remove the single screw holding the board to the center pin holder Gently pull the c...

Page 15: ...ncluded with instructions 2 Determine the cause of the blown fuse Most likely cause of blown fuse is a cross connect or short in the cable 1 Check cable terminations for proper polarity Check for damaged cable Check for secure connections at cable termination in control box Return actuator and cable to factory for service BATTERY STATUS light FLASHING or OFF A FLASHING Low battery B OFF Replace Re...

Page 16: ...For the Gemini Controller IX Typical Circuit Board Wiring 1 17 13 ...

Page 17: ...1 17 14 X Optional Relay Interface Module Circuit Board TB2 JS1 JS2 COM N O K2 K1 PIN 1 TB2 V ...

Page 18: ...For the Gemini Controller XI Optional Relay Interface Module Wiring 1 17 15 BLUE BROWN BLUE BRN BLUE ...

Page 19: ...1 17 16 XII Remote Input Circuit Wiring N O ...

Page 20: ...XIII Remote Input Circuit Wiring N C 1 17 17 ...

Page 21: ...1 17 18 XIV Actuator Cable Extension ...

Page 22: ...1 17 19 XV Emergency Shutoff Switch ...

Page 23: ...1 17 20 XVI Optional Auxiliary Valve Adapter ...

Page 24: ...local authorized Halogen Valve Systems Inc representative for additional details of this program Halogen Valve Systems Inc HVSI will not make an implied warranty of any other kind with respect to this product except as set forth herein Seller makes no warranty of merchantability or of fitness of the material or equipment for any particular purpose even if seller knows that purpose HVSI shall not b...

Page 25: ...liable for any incidental or consequential damages arising from the sale or use of the equipment Halogen s liability and customer s remedies are expressly limited to repayment of the purchase price repair or replacement at Halogen s election during the warranty period Items requiring repair must be returned to Halogen s factory or a designated repair station freight prepaid Halogen reserves the ri...

Page 26: ...______________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ __________________________...

Page 27: ...______________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ ________________________________________________ __________________________...

Page 28: ...7 17 Bulletin 800 06 ...

Reviews: