A.
General
The
Halogen Valve Systems
Terminator™
Actuator
and
Gemini™ Controller
are designed to
be used on standard 150 lb. cylinder and ton
container valves approved for chlorine service by
The Chlorine Institute
.
DO NOT USE ON OTHER
VALVE TYPES WITHOUT FIRST CONSULTING
FACTORY TO INSURE COMPATIBILITY
. The
Terminator Actuator is an automatic valve closer that
supplements the manual operation of these valves
by providing for powered valve closure in case of an
emergency. No modification of existing cylinder or
ton valve is required to install the system.
B.
Equipment
Standard
The Terminator/Gemini emergency shutoff system
consists of the following major components and
accessories:
Major Components
1. Gravity or clamp mount
Terminator Actuator
which
mounts directly to the valve
or yoke assembly.
2.
Gemini Controller
with
actuator power supply
designed to be mounted
adjacent to the cylinder or
ton container.
3.
Power cable assembly
to
provide a flexible two-wire
connection between the
controller and actuator.
Included Accessories
1. Storage bracket for each actuator to provide
temporary storage of the actuator during
cylinder or tank change, testing, and
maintenance.
2. One (1) remote mountable
Emergency Shutoff Switch
(
Normally Open, momentary
contact
). For additional
switches, order P/N 6430.00
and specify Normally Open or
Normally Closed contacts.
Additional Elements Required for Installation
1. 115 VAC or 230 VAC electrical source for
battery charging circuit (dedicated
disconnect).
2. Corrosion resistant conduit and fittings.
3. Suitable anchors for mounting controller,
storage brackets and emergency shutoff
switch.
Options
1.
Relay Interface Module (RIM)
P/N 4500.05
Dry contact output relay
with latching capability to
indicate when an
emergency close operation
has been performed. Rated
5A@115/230V (see pages 4, 14, 15).
2.
Relay Reset Button Assembly
P/N 4500.06-A
External manual relay reset button
on controller. Converts momentary
relay to latching.
C. Specifications
Emergency torque:
40 ft-lbs (55 Nm)
Motor speed:
1600 RPM
Charge current @ 115/230 VAC:
0.9 amp max
Charge current (solar) @ 12 VDC:
0.34 amp max
Battery Type:
12V, 8.0 amp-hr. High Rate
Battery backup power:
Up to 5 days
Standard cable length:
Gravity Mount: 7 ft.
Clamp Mount: 15 ft.
Valve:
C.I. ** DWG's 110,113
Yoke:
C.I.** DWG's 189,131
The C.I. (Chlorine Institute), Wash., DC torque
specified : Emergency Close 40-50 ft-lbs
**Compatible with C.I. and CGA (Compressed Gas
Association) No. 820, 820C Yokes.
l. Introduction
1/17
1.
For Clamp Mount
For Gravity Mount
Summary of Contents for Terminator
Page 16: ...For the Gemini Controller IX Typical Circuit Board Wiring 1 17 13 ...
Page 17: ...1 17 14 X Optional Relay Interface Module Circuit Board TB2 JS1 JS2 COM N O K2 K1 PIN 1 TB2 V ...
Page 19: ...1 17 16 XII Remote Input Circuit Wiring N O ...
Page 20: ...XIII Remote Input Circuit Wiring N C 1 17 17 ...
Page 21: ...1 17 18 XIV Actuator Cable Extension ...
Page 22: ...1 17 19 XV Emergency Shutoff Switch ...
Page 23: ...1 17 20 XVI Optional Auxiliary Valve Adapter ...
Page 28: ...7 17 Bulletin 800 06 ...