MASSACHUSETTS REQUIREMENTS

The following must be observed when installing the Halcyon Gas Fireplace within the Commonwealth of Massachusetts:

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or 

in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent 

termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and 

porches, the following requirements shall be satisfied: 
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled 

equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and 

battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber 

or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each 

additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be 

the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired 

carbon monoxide detectors

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the 

hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the 

owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said 

thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above 

provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified. 
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum 

height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating 

appliance or equipment. The sign shall read, in print size no less than one-half (½) inch in size, "GAS VENT DIRECTLY BELOW. KEEP 

CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the 

installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with 

the provisions of 248 CMR 5.08(2)(a)1 through 4. 
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: 
 

1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 

54 as adopted by the Board; and 
 

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the 

dwelling, building or structure used in whole or in part for residential purposes. 
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product 

Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the 

equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
 

1. Detailed instructions for the installation of the venting system design or the venting system components; and

 

2. A complete parts list for the venting system design or venting system. 

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product 

Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies 

"special venting systems", the following requirements shall be satisfied by the manufacturer:
 

1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation 

instructions; and 
 

2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a 

parts list and detailed installation instructions. 
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting 

instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or 

equipment at the completion of the installation. 

Summary of Contents for H50-01-NG

Page 1: ...06 5 WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not try to light any appliance...

Page 2: ...FIREPLACE 38 COMPLETING the INSTALLATION 40 MAINTENANCE 43 TROUBLESHOOTING 45 INSTALLATION RECORD 47 Appendix A LP Gas Conversion 49 These symbols appear throughout this Manual This WARNING symbol ind...

Page 3: ...irement 8 The area around the Halcyon Gas Fireplace must be kept clear and free from combustible materials gasoline and other flammable vapors and liquids 9 The flow of combustion and ventilation air...

Page 4: ...height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than...

Page 5: ...157 8 C Glass Frame Height 145 16 D Viewable Height 123 4 E Bead to Floor 6 F Total Width 59 G Bead to Bead Width 513 4 H Glass Frame Width 501 2 I Viewable Width 483 4 J Cabinet Width Standoffs 561 4...

Page 6: ...9 16 M Depth With Standoffs 18 N Depth Minus Standoffs 17 O Rear of Cabinet to Center Line of Vent Collar 71 4 P Rear of Cabinet to Center Line of Gas Access 87 16 Q Bottom of Cabinet to Center Line o...

Page 7: ...replace is installed and operated OMNI Test Laboratories Inc has certified that the Halcyon Gas Fireplace meets the ANSI Z21 88 2007 CSA 2 33 2007 Vented Gas Fireplace Heaters and CAN CGA 2 17 M91 Gas...

Page 8: ...tion instructions Keep burner and control compartment clean See installation and operating instructions ac companying appliance WARNING Improper installation adjustment alteration service or maintenan...

Page 9: ...clearances 1 Rough Installation Build the rough frame and install the Fireplace 2 Electric Installation The electric supply connections and the control switches 3 Gas Installation The gas hook up 4 Ve...

Page 10: ...vent A number of installation styles are possible a corner an island a peninsula built into a wall or enclosed by walls For maximum performance you should choose a Fireplace location which minimizes t...

Page 11: ...re W and the minimum distance between a room ceiling and the bottom of the Halcyon V Figure 8 shows the relationship between a room ceiling V and an enclosure or chase ceiling W S U T Figure7 RoughOpe...

Page 12: ...talled in a simple bump in enclosure If your installation requires more duct it is available through your retailer or from European Home NOTE A grille for each duct box is NOT included and must be pro...

Page 13: ...e chart representing your run and the two numbers left and right columns of the chart representing your rise Mark the point at which the lines intersect If that point falls in a black area the configu...

Page 14: ...Note 3 3 ft 91 cm within a height of 15 ft 4 5 m above the meter regulator assembly I Clearance to a service regulator vent outlet See Note 3 3 ft 91 cm J Clearance to non mechanical air supply inlet...

Page 15: ...e proofed made fire resistant orare fire rated they are considered combustible The combustibility of a material can be tested per ASTM E136 StandardTestMethodforBehaviorofMaterialsinaVerticalTube Furn...

Page 16: ...16 Figure12 Mantel CeilingandEnclosureClear ances rightsideview MINIMUM CLEARANCES to COMBUSTIBLES Non combustible Wall Face Glass Panel Top Line of Glass Panel Frame 4 6 8 10 22 201 2 19 171 2 16 44...

Page 17: ...lcyon cabinet may be no closer to the room ceiling than 44 The minimum height of an enclosure is 571 2 Figure 13 shows the combustible facing limits for the Halcyon Gas Fireplace Combustible wall faci...

Page 18: ...01 LP Gas Conversion Kit is sold separately See Appendix A for complete conversion instructions Note Check the VENTING section now to determine if your installation requires the Horizontal Heat Shield...

Page 19: ...anges to the framing Do not enclose the Fireplace chase or begin the finish work until the Fireplace has been installed tested and approved by the local code inspection authority Note INSTALLATION Fig...

Page 20: ...ly circuit which provides electrical power solely to the Control Module and is used to power the control and safety systems The Control Circuit must not contain a dimmer but it may be switched The Con...

Page 21: ...he National Electrical Code d Using wire nuts connect the Lamp Circuit to the blue and purple wires and connect the Control Circuit to the white and black wires e Connect the green ground wire to an a...

Page 22: ...FLAME PV MV TH TR FLAME SENSOR SPARK IGNITOR N L1 G to 1 x 120 V AC SWITCHED CONTROL CIRCUIT TRANSFORMER Control Schematic Lamp Schematic Figure18 LampandControlElectricalSchematicDiagrams Table7 Wire...

Page 23: ...isolated from the gas supply system by closing the service valve during any pressure testing of the gas supply system at test pressures equal to or less than psi 3 5 kPa Verify the gas pressure using...

Page 24: ...ction 1 2 3 5 6 7 8 9 10 4 Figure20 HalcyonPanelNumbers 7 INSTALL THE MEDIA The contents of the bag of Burner Media should be spread to an even depth over the entire burner top a Cut one corner of the...

Page 25: ...When replacing the glass panel assembly use only European Home part number H50 SA GP 01 substitute parts are not permitted Replacement part numbers are listed in the MAINTENANCE section Replacement o...

Page 26: ...nd Latch 4 by swinging Latch 1 clockwise and Latch 4 counter clockwise until they swing free of their catches c Using two hands swing the bottom edge of the panel out and lift the top of the panel off...

Page 27: ...ct vent components from any of the manufacturers listed in Table 8 Approved terminations are also listed in Table 8 All measurements are taken from the center of the vent connector on the top of the H...

Page 28: ...90 45 equals 270 but a combination of two 90 elbows and three 45 elbows is not allowed the total equals 315 These elbows can be installed either horizontally or vertically The first 90 elbow must have...

Page 29: ...must remain open until the Fireplace has been tested and is operating properly Figure26 RestrictorAdjustmentQuadrants Setting the Restrictors The Restrictor Settings Charts pages 32 33 accommodate ven...

Page 30: ...that the intersection of 8 feet total rise and 9 feet total run falls within the section labeled B1 2 21 2 This means that the Air Intake Adjustment Quadrant is set to a position one half of the way...

Page 31: ...e C Using the dimensions shown in Figure 28 the intersection of the rise 16 and run 12 on either Chart is black Therefore this configuration is not allowed 3 6 Figure29 VentingExample 10 Example D The...

Page 32: ...32 32 31 31 30 30 29 29 28 28 27 27 26 26 25 25 24 24 23 23 22 22 21 21 20 20 19 19 18 18 17 17 16 16 15 15 14 14 13 13 12 12 11 11 10 10 9 9 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 1 2 3 4 5 6 7 8 9 10 11...

Page 33: ...1 20 20 19 19 18 18 17 17 16 16 15 15 14 14 13 13 12 12 11 11 10 10 9 9 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Horizontal Vent Run in feet Vertical Vent Rise in feet E 3...

Page 34: ...ort is ducted the resulting wall temperature will be higher than if two ports are ducted The Remote Heat Kit components can accommodate several different installation configurations but the following...

Page 35: ...pper cover Remove both covers See Figure 32 b Remove the insulation discs and lower covers c Leave the two gaskets in place on the cabinet top d Place two duct collars on the cabinet top one around ea...

Page 36: ...d insulation back to expose the metal core It is easier to pull the metal core onto both the duct box and duct collar than to push it i Working with one hand inside and one hand outside slowly work th...

Page 37: ...ound the Glass Panel Assembly When the Halcyon cools the movement of air stops NOTE Make sure that the Heat Kit can move air away from the fireplace otherwise the wall face above the fireplace will be...

Page 38: ...and sealants used when manufacturing the Fireplace We recommend that you open the nearby windows for extra ventilation and operate the Fireplace for at least four hours Upon lighting the Fireplace wh...

Page 39: ...nt C Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas contr...

Page 40: ...necessary it is dependent on the type of fuel that is being used When burning natural gas flames that are too short or too blue will be the most common observation When burning LP gas flames that are...

Page 41: ...crement is required and the flames are still too long and sooty then go to Step 3 below 3 Adjust the exhaust restrictor by a Loosening the exhaust quadrant locking wingnut b Adjust the exhaust quadran...

Page 42: ...he facing within the limits shown in Figure 13 however must be made of non combustible material The Halcyon was designed to be faced with approved 1 2 thick non combustible facing This non combustible...

Page 43: ...r proper combustion Carefully clean the Crushed Glass Burner Media with a brush 3 Check that the vent pipe and termination cap are free from obstructions such as nests leaves or debris Ensure that the...

Page 44: ...ing products including water on the media 4 When necessary the panels can be removed and cleaned as follows a The stone like panels should be brushed with a clean soft bristled brush Do not use any cl...

Page 45: ...ated again and flame sensor is not shorted to ground replace the control module A flashing light indicates the problem is most likely in the external components or wiring see Table 11 below Proceed as...

Page 46: ...internal fault with the pilot valve PV relay Check for short betweenTH and PV If no external cause then replace control module There is an internal fault with the main valve MV relay Check for short...

Page 47: ..._____ SoldBy __________________________________________________________________________________________________ Fuel Natural Gas Propane Inlet Pressure at Installation ________________________________...

Page 48: ...Halcyon Gas Fireplace EuropeanHome com 48 NOTES...

Page 49: ...e installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes and requirements of the authority having jurisdiction If the information in these...

Page 50: ...r assembly up about an inch and move it to the right enough to provide an opening through which you can reach the wiring tunnel See Figure A1 Take care to avoid damaging the gasket beneath the burner...

Page 51: ...es by unscrewing them from the Center Tee See Figure A3 8 Screw the left and right LP Burner Orifices into the tee and tighten securely 9 Re install the left and right Burners and secure them with the...

Page 52: ...g the conversion on the LP Conversion Label Peel the backing off the label and affix it to the bottom plate of the Burner Assembly next to the gas valve as shown in Figure B8 13 Re install the Burner...

Page 53: ...rifice Size 56 DMS OMNI Test Laboratories Inc has certified that the Halcyon Gas Fireplace meets the ANSI Z21 88 2007 CSA 2 33 2007 Vented Gas Fireplace Heaters and CAN CGA 2 17 M91 Gas Fired Applianc...

Page 54: ...lcyon Gas Fireplace EuropeanHome com 54 rev 110707u EUROPEAN HOME a division of Europa Ja Inc 376 Washington Street Suite 203 Malden MA 02148 1300 tel 781 324 8383 fax 781 324 8384 info europeanhome c...