7.1.3
Dehumidifying
mode.
* temperature control range:
16---30
* temperature difference:
1
Control feature:
send the dehumidifying
signal to the outdoor system.
When Tr>Ts+2
, the compressor will be turned on, the indoor fan will operate at the set speed.
When Tr is between the Ts and Ts+2
, the outdoor system will operate at the high dehumidifying
frequency for 10 minutes and then at the low dehumidifying
mode for six minutes. The indoor fan will
operate at low speed.
When Tr< Ts, the outsystem will be stopped, the indoor fan will be stopped for 3 minutes and then
turned to the low speed option.
All the frequency converses have a
1
difference.
* Wind speed control: Automatic:
When Tr
≥
Ts+ 5
, high speed.
When Ts+3
Tr< Ts+5
, medium speed.
When Ts+2
Tr< Ts+3
, low speed.
When Tr<Ts+2
, light speed.
If the outdoor fan stopped, the indoor fan will be paused for 3 minutes.
If the outdoor fan stopped for more than 3 minutes and the outdoor system still operates, the system
will be changed into light speed mode.
When the airflow speed has no delay from the high to low switching, the speed should be delayed for
3 minutes (remain at high speed for 3 minutes.) before the next switch.
Manual: When the sensor is off or Tr< Ts+3
, the manual operation can not be made. (obligatory
automatic operation.)
*Airgate location control: the location for the airgate can be set according to your needs.
*Defrosting function: preventing the frosting on the indoor heat exchanger (when cooling or
dehumidifying ). When the compressor works continuously for 1/6 minutes (adaptable in EEPROM)
and the temperature of the indoor coils has been below zero centigrade for 10 seconds, the
compressor will be stopped and the malfunction will be recorded in the malfunction list. The indoor
system will continue to run. When the temperature of the indoor coil is raised to 7
, the compressor
will be restarted again (the requirement of 3 minutes’ delay should be satisfied.)
* coil protection (synchronic overheating protection) are installed for the four directions latch
malfunctions when dehumidifying .
* timing system on/off function.
* Dormant control functio
n.
7.1.4
Heating operation mode.
* temperature control range:
16---30
* temperature difference:
1
* control feature: the temperature compensation is automatically added and the system will send the
heating signals to the outdoor system.
If Tr Ts, the outdoor compressor is turned on, the indoor fan will be at the cold air proof mode.
If Tr>Ts+3 , the outdoor system is turned off, the indoor fan will be at the heat residue sending mode.
If Tr<Ts+3 , the outdoor system will be turned on again, the indoor fan will be at the cold air proof mode.
Functions and Control
Domestic air conditioner
181
Summary of Contents for Super Match Series
Page 1: ...Super Match SYJS 11 2015REV D Edition 2015 11 3U19FS2ERA 3U24GS2ERA 4U30HS2ERA 5U34HS2ERA...
Page 3: ...Super Match Part 1 General Information 1 Indoor Outdoor unit models 3 2 Features 4 2...
Page 7: ...Super Match Super Match Part 2 Indoor units 1 4 way cassette type 9 2 Duct indoor type 90 6...
Page 10: ...Super Match 2 Specification 9...
Page 11: ...Super Match Super Match 10...
Page 12: ...Super Match 11...
Page 13: ...Super Match Super Match 3 Dimension AB09CS2ERA AB12CS2ERA S AB18CS2ERA S AB24ES1ERA 12...
Page 24: ...Super Match 8 Installation 23...
Page 25: ...Super Match Super Match 24...
Page 26: ...Super Match 25...
Page 27: ...Super Match Super Match 26...
Page 28: ...Super Match 27...
Page 30: ...Super Match 1 Features AD09 12SS1ERA N P AD18 24SS1ERA N P AD12 18MS1ERA AD24MS2ERA 29...
Page 40: ...Super Match AD09SS1ERA N P AD09SS1ERA N P AD18SS1ERA N P AD24SS1ERA N P 39...
Page 53: ...Super Match Super Match 52...
Page 54: ...Super Match 53...
Page 55: ...Super Match Super Match 54...
Page 56: ...Super Match 55...
Page 57: ...Super Match Super Match 56...
Page 58: ...Super Match AD12MS1ERA AD18MS1ERA AD24MS2ERA 57...
Page 59: ...Super Match Super Match 58...
Page 60: ...Super Match 59...
Page 61: ...Super Match Super Match 60...
Page 62: ...Super Match 61...
Page 63: ...Super Match Super Match 62...
Page 90: ...Super Match 9 Maintenance WARNING CAUTION 89...
Page 91: ...Super Match Super Match 90...
Page 92: ...Super Match 91...
Page 93: ...Super Match Super Match 92...
Page 94: ...Super Match Items to Be Checked 93...
Page 95: ...Super Match Super Match 94...
Page 96: ...Super Match 95...
Page 99: ...Super Match Super Match 98...
Page 100: ...Super Match 99...
Page 101: ...Super Match F 100...
Page 102: ...Super Match 101...
Page 103: ...Super Match 102...
Page 106: ...Super Match 105...
Page 107: ...Super Match 106...
Page 110: ...Super Match PCB 0151800175 AD09 24SS1ERA N P AD12MS1ERA AD18MS1ERA AD24MS2ERA 109...
Page 119: ...Super Match Power module 0150400643A 3U24GS2ERA Power module 0150400643B 3U19FS2ERA 118...
Page 120: ...Super Match Filter board 0150400699 3U19FS1ERA 3U24GS2ERA 4U30HS1ERA 5U34HS1ERA 119...
Page 177: ...Piping diagrams Domestic air conditioner 5 Pinping diagrams 176...
Page 180: ...Connector Wiring diagrams Domestic air conditioner 179...
Page 232: ...Piping diagrams Domestic air conditioner 5 Pinping diagrams 231...
Page 235: ...Connector Wiring diagrams Domestic air conditioner 234...
Page 287: ...Piping diagrams Domestic air conditioner 5 Pinping diagrams 286...
Page 310: ...Seivice diagnosis Domestic air conditioner 9 Dimensional drawings 10 Center of gravity 309...
Page 339: ...Piping diagrams Domestic air conditioner 5 Pinping diagrams 338...
Page 391: ...Piping diagrams Domestic air conditioner 5 Pinping diagrams 390...
Page 443: ...Piping diagrams Domestic air conditioner 5 Pinping diagrams 442...