Outdoor unit

1.Installation of Outdoor Unit

2.Connection of pipes

Install according to

To bend a pipe, give the roundness as large as possible not to crush the pipe ,and the bending radius
should be 30 to 40 mm or longer.
Connecting the pipe of gas side first makes working easier.
The connection pipe is specialized for R410A.

Drawing for the installation of indoor and outdoor units

Half union

Flare nut

Forced fastening without careful
centering may damage the
threads and cause a leakage of
 gas.

Pipe Diameter

Fastening torque

Spanner

Torque wrench

Liquid side 6.35mm(1/4")

18N.m

Gas side 9.52mm(3/8")

Gas side 12.7mm(1/2")

42N.m

55N.m

Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.
The standard pipe length is 5m. If it is over 5m, the function of the unit will be affected. If the pipe has
to be lengthened, the refrigerant should be charged, according to 20 g/m. But the charge of refrigerant
must be conducted by professional air conditioner engineer. Before adding additional refrigerant,
perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then charge
additional refrigerant.

3.Connection

Use the same method on indoor unit. Loosen
the screws on terminal block and insert the
plugs fully into terminal block, then tighten the
screws.
Insert the cable according to terminal number
in the same manner as the indoor unit.

If wiring is not correct, proper operation can
not be carried out and controller may be
damaged.
Fix the cable with a clamp.

4.Attaching Drain-Elbow

 If the drain-elbow is used, please attach it as
 figure.

 Note: Only for heat pump unit.

Drain hose

Drain elbow

Summary of Contents for HSU-09HA103-R2

Page 1: ...iping Mark Parts name Non adhesive tape Adhesive tape Saddle L S with screws Connecting electric cable for indoor and outdoor Drain hose Heating insulating material Piping hole cover No Accessory part...

Page 2: ...lightened Place which is less affected by rain or direct sunlight and is sufficiently ventilated Place possible to bear the unit where vibration and noise are not increased Place where discharged win...

Page 3: ...al it off with putty after installation Section of wall hole Piping hole pipe Outdoor side Thickness of wall Indoor side Wall hole 60mm Indoor unit 1 Fitting of the Mounting Plate and Positioning of t...

Page 4: ...rain hose must be bound with refrigerant piping by protecting tape Cut away with a nipper the lid for piping according to the piping direction and then bend the pipe according to the position of wall...

Page 5: ...not correct proper operation can not be carried out and will cause defect 1 If the supply cord is damaged it must be replaced by the manufacturer or its service agent or a similar qualified person The...

Page 6: ...standard pipe length is 5m If it is over 5m the function of the unit will be affected If the pipe has to be lengthened the refrigerant should be charged according to 20 g m But the charge of refriger...

Page 7: ...akage turn the service port s cap the valve rod s cap for 2 way valve and 3 way s a little more than the point where the torque increases suddenly After attaching the each caps check the gas leakage a...

Page 8: ...arried out Please install the drain hose so as to be downward slope without fail Please don t do the drainage as shown below Please pour water in the drain pan of the indoor unit and confirm that drai...

Reviews: