Outdoor unit

5.Purging Method:To use vacuum pump

Detach the service port's cap of 3-way valve, the

valve rod's cap for 2-way valve and 3-way's, connect

the service port into the projection of charge hose

(low) for gaugemanifold. Then connect the projection

of charge hose (center) for gaugemanifold into

vacuum pump.

Tube(for R410A)

Open the handle at low in gaugemanifold, operate

vacuum pump. If the scale-moves of gause (low)

reach vacuum condition in a moment, check         again.

Vacuumize for over 15min. And check the level gauge

which should read -0.1 MPa (-76 cm Hg) at low

pressure side. After the completion of vacuumizing,

close the handle 'Lo' in gaugemanifold and stop the

operation of the vacuum pump.

Check the condition of the scale and hold it for 1-2min.

If the scale-moves back in spite of tightening, make

flaring work again, the return to the beginning of        .

Open the valve rod for the 2-way valve to an angle of

anticlockwise 90 degrees.

After 6 seconds, close the 2-way valve and make

the inspection of gas leakage.

No gas leakage?

In case of gas leakage, tighten

parts of pipe connection. If

leakage stops, then proceed

steps.

Detach the charge hose from the service port, open

2-way valve and 3-way. Turn the valve rod anticlockwise

until hitting lightly.

To prevent the gas leakage, turn the service port's

cap, the valve rod's cap for 2-way valve and 3-way's

a little more than the point where the torque increases

suddenly.

After attaching the each caps, check the gas leakage

around the caps.

CAUTION:

1.If the refrigerant of the air conditioner leaks, it is necessary to

 discharge all the refrigerant. Vacuumize first, then charge the liquid

 refrigerant into air conditioner according to the amount marked on

 the name plate.

2.Please do not let other cooling medium, except specified one (R410A),

  or air enter into the cooling circulation system. Otherwise, there will be

 abnormal high pressure in the system to make it crack and lead to

  personal injuries.

If it does not stop gas leakage, discharge
whole refrigerants from the service port.
After flaring work again and vacuumize,
fill up prescribed refrigerant from the gas
cylinder

3-way valve

Gas Side

9.52mm(3/8")

6.35mm(1/4")

2-way valve

3-way valve

Service port cap

Gaugemanifold(for R410A)

Anti countercurrent joint

Vacuum pump(for R410A)

Open

Close

Liquid Side

2-way valve

Valve rod cap

Valve rod cap

2-way valve

9.52mm(3/8")

6.35mm(1/4")

3-way valve

12.7mm(1/2")

Gas Side

Liquid Side

12.7mm(1/4")

Gas Side

6.35mm(1/4")

Liquid Side

2-way valve

3-way valve

2-way valve

3-way valve

3-way valve

2-way valve

Service port

90

o

Open

90

o

for 6 sec.

HSU-09H03/R2(DB)

HSU-22H03/R2(DB)

HSU-12H03/R2(DB)
HSU-12HB03/R2(DB)
HSU-18H03/R2(DB)

12.7mm(1/2")

HSU-18HA103/R2(DB)

HSU-22HA103/R2(DB)

HSU-09HA103/R2(DB)
HSU-12HA103/R2(DB)

Summary of Contents for HSU-09HA103-R2

Page 1: ...iping Mark Parts name Non adhesive tape Adhesive tape Saddle L S with screws Connecting electric cable for indoor and outdoor Drain hose Heating insulating material Piping hole cover No Accessory part...

Page 2: ...lightened Place which is less affected by rain or direct sunlight and is sufficiently ventilated Place possible to bear the unit where vibration and noise are not increased Place where discharged win...

Page 3: ...al it off with putty after installation Section of wall hole Piping hole pipe Outdoor side Thickness of wall Indoor side Wall hole 60mm Indoor unit 1 Fitting of the Mounting Plate and Positioning of t...

Page 4: ...rain hose must be bound with refrigerant piping by protecting tape Cut away with a nipper the lid for piping according to the piping direction and then bend the pipe according to the position of wall...

Page 5: ...not correct proper operation can not be carried out and will cause defect 1 If the supply cord is damaged it must be replaced by the manufacturer or its service agent or a similar qualified person The...

Page 6: ...standard pipe length is 5m If it is over 5m the function of the unit will be affected If the pipe has to be lengthened the refrigerant should be charged according to 20 g m But the charge of refriger...

Page 7: ...akage turn the service port s cap the valve rod s cap for 2 way valve and 3 way s a little more than the point where the torque increases suddenly After attaching the each caps check the gas leakage a...

Page 8: ...arried out Please install the drain hose so as to be downward slope without fail Please don t do the drainage as shown below Please pour water in the drain pan of the indoor unit and confirm that drai...

Reviews: