Page 14
31-5000724 Rev. 0
•
Initiate furnace ignition sequence and move to and hold
mid-fire rate by applying a jumper to R and W2.
•
Apply then remove the jumper from R to W1 and W2 to
change the firing rate from low fire to mid fire and high
fire.
•
A vent calibration sequence can be initiated even if a
thermostat signal is not present. Press and hold the push
button until a solid “C” is displayed. Release the button
and calibration will begin. The furnace will perform the
high-fire and low-fire pressure switch calibrations and
display “CAL”. After calibration, the LED will return to the
flashing “-” display.
During Field Test mode operation, all safety switches
are still in the circuit (they are not by-passed) and indoor
blower performance and timings will match DIP switch
selections. Current furnace firing rate, indoor blower CFM
and flame signal will be displayed. To exit the Field Test
mode, press and hold the button. The menu will resume
from the beginning. Also, cycle the main power to exit the
Field Test mode. The integrated control will automatically
exit the Field Test mode after 45 minutes of operation.
These options are displayed on the menu when the button is pressed during normal operation
Display
Action (when button is released)
No change (idle)
Remain in idle mode
Solid “E”
Enter diagnostic mode
Solid “-”
Enter field test mode
NOTE - No change implies the display will continue to show whatever is currently being displayed for normal operation
Table 10. Idle Menu Options
These options are displayed when the button is used in Field Test Mode
Display
Action (when button is released)
No change (blinking “-”)
Remain in field test mode
Solid “-”
Exit field test mode
Solid “c”
Start pressure switch calibration
Table 11. Field Test Menu Options
These options are displayed when the button is used in diagnostic recall mode
Display
Action (when button is released)
No change (displaying error history)
Remain in diagnostic recall mode
Solid (3 horizontal bars)
Exit diagnostic recall mode
Solid “c”
Clear error history
Once the button is released to clear the error history a blinking “c” will be shown on the display for up to 10 seconds. During this
time the user must press and release the button one additional time to confirm the action of deleting the error history. Once the error
history is deleted it cannot be recovered.
Table 12. Diagnostic Recall Menu Options