Page 16
31-5000724 Rev. 0
LED Diagnostic Codes
Code
Diagnostic Codes / Status of Equipment
Action Required to Clear and Recover
Idle mode (Decimal blinks at 1 Hertz - 0.5 seconds
ON, 0.5 seconds OFF).
A
Cubic feet per minute (cfm) setting for indoor blower
(1 second ON, 0.5 seconds OFF) / cfm setting for
current mode displayed.
C
Cooling stage (1 second ON, 0.5 seconds OFF) /
1 or 2 displayed / Pause / cfm setting displayed /
Pause / Repeat codes.
d
Dehumidification mode (1 second ON, 1 second
OFF) / cfm setting displayed / Pause / Repeat
codes.
h
Heat pump stage (1 second ON, 0.5 seconds OFF)
/ % of input rate displayed / Pause / cfm setting /
Pause / Repeat codes.
H
Gas Heat stage (1 second ON, 0.5 seconds OFF)
/ 1 or 2 displayed / Pause / cfm setting displayed /
Pause / Repeat codes. Blinking during ignition.
dF
Defrost mode.
E110
Low line voltage.
Line Voltage low (Voltage tower than nameplate rating).
Check power line voltage and correct. Alarm clears 5
seconds after fault recovered.
E113
High line voltage.
Line Voltage high (Voltage higher than nameplate
rating). Provide power voltage within proper range.
System resumes normal operation 5 seconds after fault
recovered.
E114
Line voltage frequency out-of-range.
No 60 Hertz power. Check voltage and line power
frequency. Correct voltage and frequency problems.
System resumes normal operation 5 seconds after fault
recovered.
E115
Low 24V - Control will restart if the error recovers.
24 Volt Power high (Range is 18 to 30 Volts). Check
and correct voltage. Check for additional power
robbing equipment connected to system. May require
installation of larger VA transformer to be installed in
furnace/air handler. Clears after fault recovered.
E125
Control failed self-check, internal error, failed
hardware. Will restart if error recovers, Integrated
control not communicating Covers hardware errors
(flame sense circuit faults, pin shorts, etc).
Hardware problem on the control. Cycle power on
control. Replace if problem prevents service and is
persistent. Cleared 300 seconds after fault recovered.
E126
Control internal communication problem.
Hardware problem on the control. Cycle power on
control. Replace if problem prevents service and is
persistent. Cleared 300 seconds after fault recovered.
E200
Hard Lock out - Rollout circuit open or previously
open
Correct cause of rollout trip or replace flame rollout
switch. Test furnace operation. Cleared after fault
recovered.
E201
Indoor blower/communication failure - Unable to
communicate with blower motor
Indoor blower communication failure including power
outage. Lost communication with indoor blower motor.
Possible causes: motor not powered, loose wiring.
Problem may be on control or motor side. Cleared after
fault recovered.