OUTDOOR TECHNICAL OVERVIEW
B-5
ENGLISH
Components
The 4 Way Valve is energized during heating mode operation.
The valve is energized with 230 volts via a connection plug on
the ECU. When energized, the valve directs the compressor
hot gas to the indoor coil.
During Cooling mode and Defrost mode operation, the valve
is de-energized. When de-energized, the valve will direct the
compressor hot gas to the outdoor coil.
The Outdoor Fan Motor is a variable speed motor. The motor
is energized via a connection plug on the ECU. The motor
is powered by line voltage from the ECU. The motor has a
PWM circuit that feeds back voltage to the ECU. The ECU will
control the speed of the motor by a DC voltage applied to the
yellow wire of the connection plug. The feedback PWM signal
from the fan motor is applied to the ECU via the blue wire on
the connection plug.
The system has a Low Pressure Switch that will shut down
system operation if abnormally low refrigeration circuit
pressure is detected. This switch is connected to the ECU via
an electrical plug. During normal operation this switch will be
closed.
If the switch were to open during a call for cooling or heating
mode operation, the system will shut off the compressor
and display an error code. If the pressure rises to re-close
the switch, the compressor will re-start and continue on with
normal operation. Multiple cycles of opening and closing the
switch will cause the system to lock out and display an Error
Code 43.
Causes of low refrigerant pressure include leaks,
undercharging, restrictions, EEV failure and cold room air
temperatures/dirty indoor coils/restricted airflow at indoor
unit.
The system has a High Pressure Switch that will shut down
system operation if abnormally high refrigeration circuit
pressure is detected. This switch is connected to the ECU via
an electrical plug. During normal operation this switch will be
closed.
If the switch were to open during a call for cooling or heating
mode operation, the system will shut off the compressor and
display an error code. If the pressure drops to re-close the
switch, the compressor will re-start and continue on with
normal operation. Multiple cycles of opening and closing the
switch will cause the system to lock out and display an Error
Code 42.
Causes of high refrigerant pressure include overcharging,
restrictions, EEV failure, and dirty outdoor coil.
Outdoor Fan Motor
Low Pressure Switch
4 Way Valve
High Pressure Switch
Summary of Contents for AW07EH2VHA
Page 2: ...Aug 2020 Manual release Revision History ...
Page 12: ... This page intentionally left blank ...
Page 30: ...OUTDOOR TECHNICAL OVERVIEW B 18 ENGLISH Wiring Diagrams 2U18MS2VHB ...
Page 31: ...OUTDOOR TECHNICAL OVERVIEW B 19 ENGLISH Wiring Diagrams 3U24MS2VHB ...
Page 32: ...OUTDOOR TECHNICAL OVERVIEW B 20 ENGLISH Wiring Diagrams 4U36MS2VHB ...
Page 36: ... This page intentionally left blank ...
Page 45: ...WALL MOUNT TECHNICAL OVERVIEW C 9 ENGLISH Topic Title Wiring Diagrams ...
Page 68: ... This page intentionally left blank ...
Page 78: ... This page intentionally left blank ...
Page 100: ...MEDIUM STATIC DUCTED PRO SERIES TECHNICAL OVERVIEW H8 ENGLISH Topic Title Wiring Diagram ...
Page 114: ... This page intentionally left blank ...
Page 122: ...TROUBLESHOOTING REFERENCES J 10 ENGLISH Refrigeration Diagrams 3U24MS2VHB Refrigerant Diagram ...