TROUBLESHOOTING & REFERENCES
J-6
ENGLISH
Topic Title
Matching Tables
2U18MS2VHB / 2U20EH2VHA
Combinations
Total Capacity
Required
Adapter
Port B
Port A
1/4" x 3/8" 1/4" x 3/8"
Two
Zone
7
7
14K
-
9
7
16K
-
9
9
18K
-
12
7
19K
-
12
9
21K
-
12
12
24K
-
3U24MS2VHB / 3U24EH2VHA
Combinations
Total
Capacity
Required
Adapter
Port C
Port B
Port A
MS: 1/4" x 3/8"
EH: 1/4" x 1/2"
1/4" x 3/8" 1/4" x 3/8"
MS
EH
Two Zone
7
7
- - -
14K
-
E
9
7
- - -
16K
-
E
9
9
- - -
18K
-
E
12
7
- - -
19K
-
E
12
9
- - -
21K
-
E
12
12
- - -
24K
-
E
18
7
- - -
25K
D
-
18
9
- - -
27K
D
-
18
12
- - -
30K
D
-
Three
Zone
7
7
7
21K
-
E
9
7
7
23K
-
E
9
9
7
25K
-
E
12
7
7
26K
-
E
9
9
9
27K
-
E
12
9
7
28K
-
E
12
9
9
30K
-
E
12
12
7
31K*
-
E
18
7
7
32K*
D
-
12
12
9
33K*
-
E
4U36MS2VHB/ 4U36EH2VHA
Combinations
Total
Capacity
Required
Adapter
Port D
Port C
Port B
Port A
1/4" x 1/2" 1/4" x 3/8" 1/4" x 3/8" 1/4" x 3/8"
MS
EH
Two
Zone
18
9
- - -
- - -
27K
-
18
12
- - -
- - -
30K
-
24
7
- - -
- - -
31K
C
A
24
9
- - -
- - -
33K
C
A
24
12
- - -
- - -
36K
C
A
18
18
- - -
- - -
36K
D
18
24
- - -
- - -
42K
A
B
24
24
- - -
- - -
48K*
B
C
A (x2)
Three
Zone
9
9
9
- - -
27K
E
-
12
9
7
- - -
28K
E
-
12
9
9
- - -
30K
E
-
12
12
7
- - -
31K
E
-
18
7
7
- - -
32K
-
12
12
9
- - -
33K
E
-
18
9
7
- - -
34K
-
18
9
9
- - -
36K
-
12
12
12
- - -
36K
E
-
18
12
7
- - -
37K
-
24
7
7
- - -
38K
C
A
18
12
9
- - -
39K
-
24
9
7
- - -
40K
C
A
24
9
9
- - -
42K
C
A
18
12
12
- - -
42K
-
24
12
7
- - -
43K
C
A
24
12
9
- - -
45K
C
A
18
18
12
- - -
48K*
D
24
12
12
- - -
48K*
C
A
Four
Zone
7
7
7
7
28K
E
9
7
7
7
30K
E
9
9
7
7
32K
E
12
7
7
7
33K
E
9
9
9
7
34K
E
12
9
7
7
35K
E
9
9
9
9
36K
E
12
9
9
7
37K
E
12
12
7
7
38K
E
12
9
9
9
39K
E
18
7
7
7
39K
-
12
12
9
7
40K
E
18
9
7
7
41K
-
12
12
9
9
42K
E
12
12
12
7
43K
E
18
9
9
7
43K
-
18
12
7
7
44K
-
24
7
7
7
45K
C
A
12
12
12
9
45K
E
24
9
7
7
47K*
C
A
12
12
12
12
48K*
E
18
12
9
9
48K*
-
*ALL INDOOR UNITS MUST BE FLEXFIT.
*ALL INDOOR UNITS MUST BE FLEXFIT.
Adapters
GEA Part #
GEA Part #
A
1/4” to 3/8” (Liquid line for ports C & D)
WJ01X23925
B
3/8” to 5/8” (Vapor line for port C)
WJ01X23924
C
1/2” to 5/8” (Vapor line for port D)
WJ01X23932
D
3/8” to 1/2” (Vapor line for port C)
WJ01X26853
E
1/2” to 3/8” (Vapor line for port C OR D)
WJ01X26854
Summary of Contents for AW07EH2VHA
Page 2: ...Aug 2020 Manual release Revision History ...
Page 12: ... This page intentionally left blank ...
Page 30: ...OUTDOOR TECHNICAL OVERVIEW B 18 ENGLISH Wiring Diagrams 2U18MS2VHB ...
Page 31: ...OUTDOOR TECHNICAL OVERVIEW B 19 ENGLISH Wiring Diagrams 3U24MS2VHB ...
Page 32: ...OUTDOOR TECHNICAL OVERVIEW B 20 ENGLISH Wiring Diagrams 4U36MS2VHB ...
Page 36: ... This page intentionally left blank ...
Page 45: ...WALL MOUNT TECHNICAL OVERVIEW C 9 ENGLISH Topic Title Wiring Diagrams ...
Page 68: ... This page intentionally left blank ...
Page 78: ... This page intentionally left blank ...
Page 100: ...MEDIUM STATIC DUCTED PRO SERIES TECHNICAL OVERVIEW H8 ENGLISH Topic Title Wiring Diagram ...
Page 114: ... This page intentionally left blank ...
Page 122: ...TROUBLESHOOTING REFERENCES J 10 ENGLISH Refrigeration Diagrams 3U24MS2VHB Refrigerant Diagram ...