COMPACT CASSETTE TECHNICAL OVERVIEW
D-3
ENGLISH
Topic Title
Components
The Blower Assembly
The blower assembly consists of a plastic blower wheel that is connected to a PSC indoor blower motor. A set screw
holds the blower wheel to the blower motor.
The indoor blower motor is a Multi Speed Fan Motor that is connected to the indoor unit control board. The wiring from
the motor to indoor board consists of 4 wires connected to pins common, low , medium and high speeds.
During normal operation, the indoor control board will energize the indoor blower motor and request proper speed. The
motor has a run capacitor that is located in the Cassette unit’s control box. The run capacitor connects to the motor via
Louver Motors
The louver motors are stepper type motors that move the louvers up/down. The motors are controlled by pulsed voltage
that cannot be measured. If the louver does not move when it should, check for a bind in the louvers.
Piping Temperature Sensor
The Piping Temperature Sensor senses indoor coil temperature in the c
ooling mode and in the heating mode.
This sensor is
used for Anti Freezing and Anti Cold Blow cycles. The sensor also provides critical temperature information to the ECU that
may be used in frequency adjustments.
Ambient Temperature Sensor
The Ambient Temperature Sensor senses room temperature. This sensor provides room temperature information to the
ECU for calculation of inverter capacity and temperature control.
Control Board
The indoor unit circuit board controls the switching functions of the indoor unit. All control decisions are made by the
outdoor unit ECU. The indoor board has some limited diagnostic capability which will be covered in this manual.
Condensate Pump & Float Switch
4
5
6
7
8
9
1. If in COOL or DRY mode: Compressor running (Thermal ON), then condensate pump is energized
•When compressor stops (Thermal OFF), condensate pump runs for an additional 5 minutes
2. If in COOL or DRY modes and compressor is running (Thermal ON) and the float switch opens for 5 minutes
•Compressor will stop, the pump will continue to run
•If the float switch does not close, error code will display and pump continues to run
•If the float switch does close, the pump will continue to run for 5 additional minutes
3. During standby (Thermal OFF) in COOL/DRY modes or in HEAT and FAN modes and float switch opens for 2 seconds,
the condensate pump is energized.
•If the float switch closes, the pump will run an additional 5 minutes
•If the float does not close, the pump continues to run and error code is displayed
Summary of Contents for AW07EH2VHA
Page 2: ...Aug 2020 Manual release Revision History ...
Page 12: ... This page intentionally left blank ...
Page 30: ...OUTDOOR TECHNICAL OVERVIEW B 18 ENGLISH Wiring Diagrams 2U18MS2VHB ...
Page 31: ...OUTDOOR TECHNICAL OVERVIEW B 19 ENGLISH Wiring Diagrams 3U24MS2VHB ...
Page 32: ...OUTDOOR TECHNICAL OVERVIEW B 20 ENGLISH Wiring Diagrams 4U36MS2VHB ...
Page 36: ... This page intentionally left blank ...
Page 45: ...WALL MOUNT TECHNICAL OVERVIEW C 9 ENGLISH Topic Title Wiring Diagrams ...
Page 68: ... This page intentionally left blank ...
Page 78: ... This page intentionally left blank ...
Page 100: ...MEDIUM STATIC DUCTED PRO SERIES TECHNICAL OVERVIEW H8 ENGLISH Topic Title Wiring Diagram ...
Page 114: ... This page intentionally left blank ...
Page 122: ...TROUBLESHOOTING REFERENCES J 10 ENGLISH Refrigeration Diagrams 3U24MS2VHB Refrigerant Diagram ...