Dip Switch Setting
Note: communication protocol between indoor and outdoor units
The new communication protocol is faster than the old communication and its control content is more than the
old one.
The indoor PCB 151800113, 151800161, 0151800161B, 0151800227, 0151800244, 0010451751AF,
0151800141A, 0010451751AE and 151800141 are new communiction protocol.
The indoor PCB 151800086 and 0010451181A are old communiction protocol.
Old communication protocol indoor PCB can't connect with new communiction protocol outdoor, so if this
outdoor unit connect with old communication protocol indoor, need set the dip switch BM2-6 to ON position.
BM2 Introduction
BM2
Definition
Introduction
BM2_1
Cooling only or heat
pump selection
OFF
Heat pump (default)
ON
Cooling only
BM2_2
BM2_3
Outdoor capacity
selection
[2]
[3]
Outdoor capacity selection
OFF
OFF
8HP (AV08NMSETA)
ON
OFF
10HP (AV10NMSETA)
ON
ON
12HP (AV12NMSETA)
BM2_4
Heat reservation
module selection
OFF
Default ( no heat reservation module) note: forbid changing
BM2_5
Indoor and outdoor
high drop selection
OFF
No high drop (default)
ON
High drop
BM2_6
Communication
protocol selection
OFF
New communication protocol (default)
ON
Old communication protocol
BM2_7
BM2_8
Start mode selection
[7]
[8]
Start mode selection
OFF
OFF
First open priority
OFF
ON
After open priority
ON
OFF
Cooling priority, any one indoor unit runs in cooling
mode, the outdoor unit will run in cooling mode, the
indoor units running in heating mode will stop.
ON
ON
Heating priority, any one indoor unit runs in heating
mode, the outdoor unit will run in heating mode, the
indoor units running in cooling mode will stop.