22
22
Single installation around the opening
Inlet
Outlet
Min200mm
Single installation around the closed
Inlet
Outlet
Min300mm
Min300mm
Min150mm
Min360mm
Outdoor installation
Installation location
■
Outdoor unit should be placed in well ventilated and dry place.
■
Outdoor noise and exhaust should not affect neighbors and around the ventilation.
■
Ensure the ground steadily reliable.
■
Do not install the outdoor unit on high oil, salt spray or harmful gases.
■
Don't being installed to electromagnetic wave can directly radiate an electricity box and keep
off electromagnetic
wave radiation possibly, at least more than 3 meters.
■
When ice snow overlay area installs outdoor unit, please add to defend snow cover.
■
Outdoor unit installed in the shade, avoiding direct sunlight or high temperature heat sources of radiation.
■
Do not install in dusty or polluted place to prevent outdoor unit heat exchanger jam.
■
The outdoor unit should install in the public unapproachable place.
Installation and maintenance space
As shown below, install the outdoor unit should allow sufficient space for handing and maintenance.
Case 1: Stumbling block on the inlet , also upside opens.
H
A
h
Single installation around the opening
Single installation around the closed