background image

Safety Precautions

The installation, maintenance, service and repair operations of this product shall be carried

out by professional personnel, who have been trainedand certified by national training

organizations that areaccredited to teach the relevant national competency standards

that may be set in legislation.

Improper installation may cause water leakage, electrical shock, fire, or explosion.

Install the air conditioner according to the instructions given in this manual.

Incomplete installation may cause water leakage, electrical shock, fire, or explosion.

Be sure to use the supplied or specified installation parts.

Use of other parts may cause the unit to cometo lose, water leakage, electrical shock, fire, or explosion.

Install the air conditioner on a solid base that can support the unit's weight.

An inadequate base or incomplete installation may cause injury in the event the unit falls off the base.

Electrical work should be carried out in accordance with the installation manual and the

national electrical wiring rules or code of practice.

Insufficient capacity or incomplete electrical work may cause electrical shock, fire, or explosion.

Be sure to use a dedicated power circuit. Never use a power supply shared by another

appliance.

For wiring, use a cable long enough to cover the entire distance with no connection.

Do not use an extension cord. Do not put other loads on the power supply, use a dedicated

power circuit.

(Failure to do so may cause abnormal heat, electrical shock,  fire, or explosion.)

Use the specified types of wires for electrical connections between the indoor and outdoor

units.

Firmly clamp the interconnectiong wires so their terminals receive no external stresses. Incomplete connections or clamping

may cause terminal overheating, fire, or explosion.

After connectiong interconnecting and supply wiring be sure to shape the cables so that

they do not put undue force on the electrical covers or panels.

Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, fire, or explosion.

If any refrigerant has leaked out during the installation work, ventilate the room.

(The refrigerant produces a toxic gas if exposed to flames, may cause explosion.)

After all installation is complete, check to make sure that no refrigerant is leaking out.

(The refrigerant produces a toxic gas if exposed to flames, may cause explosion.)

When installing or relocating the system, be sure to keep the refrigerant circuit free from

substancs other than the specified refrigerant(R32), such as air.

(Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture,

resulting in injury.)

During pump-down, stop the compressor before removing the refrigerant piping.

If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the compressor

is run, causing abnormal pressure in the freezer cycle which will lead to breakage and even injury.

Be sure to establish an earth. Do not earth the unit to a utility pipe, arrester, or telephone

earth.

Incomplete earth may cause electrical shock, fire, or explosion. A high surge current from lightning or other sources may cause

damage to the air conditioner.

The installation of pipe-work shall be kept to a minimum.

Pipe-work shall be protected from physical damage and shall not be installed in an unventilated space, if that space is

smaller than the Minimum Room Area specified in the table on the following pages.

Mechanical connections shall be accessible for maintenance purposes.

Information for handling, installation, cleaning, servicing and disposal of refrigerant.

Warning: Keep any required ventilation openings clear of obstruction.

Notice: Servicing shall be performed only as recommended by this manual instruction.

Be sure to install an earth leakage breaker.

Failure to install an earth leakage breaker may result in electric shocks, fire, or explosion.

WARNING

3

Summary of Contents for 3U55S2PR1FA

Page 1: ...TIONER 3U55S2PR1FA 4U71S2PR1FA 4U80S2PR1FA 5U125S2PN1FA 0150558811 Move and scrap the air conditioning Contents Safety Precautions Read Before Installation Accessories Procedure for Selecting the location Installation drawings of indoor and outdoor units Precautions on Installation Limitations on the installation Refrigerant piping work Pump Down Operation Wiring work Dred function Test running Tr...

Page 2: ...y refrigerant charge of the product see unit name plate C additional refrigerant amount charged in the field D total refrigerant charge E outdoor unit F refrigerant cylinder and manifold for charging Air conditioner working temperature cooling 10 46 degree heating 15 24 degree The single indoor unit will reduce in heating efficiency if the ambient temperature is under 0 degree WARNING IMPORTANT IN...

Page 3: ...ware that refrigerants may not contain an odour The appliance must be installed operated and stored in a room with a floor area larger than the Minimum Room Area specified in the table on the following pages The room should be well ventilated Comply with national gas regulations This appliance can be used by children aged 8 years and above and persons with reduced physical sensory or mental capabi...

Page 4: ... do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock fire or explosion If any refrigerant has leaked out during the installation work ventilate the room The refrigerant produces a toxic gas if exposed to flames may cause explosion After all installation is complete check to make sure t...

Page 5: ...all be used for maintenance and exposed transporting of refrigerant cylinders and the products to be maintained is not allowed 4 The rain cover or similar shielding material of transporting vehicles shall be provided with certain flame retardancy 5 Leakage warning device of flammable refrigerant shall be installed inside the closed type compartment 6 Anti static device shall be equipped inside the...

Page 6: ...hecked cannot be less than the area specified on the warning sign of the indoor unit 2 Inspection on the surrounding environment of place of installation the outdoor unit of flammable refrigerants air conditioner cannot be installed inside an enclosed room reserved 3 Power supply switches or other high temperature articles such as the fire source and oil heater shall be avoided below the indoor un...

Page 7: ...r of the indoor unit is connected to the connector pipe after welding nitrogen more than 4 0MPa shall be charged inside the evaporator and the piping connected to evaporator with a nitrogen cylinder adjusted by a reducing valve Afterwards the valve of the nitrogen cylinder shall be closed for leak detection with soapy water or leak detecting solution The pressure shall be maintained for more than ...

Page 8: ...with the conical surface of corresponding valve connector The nut of connecting pipes shall be installed at a proper position and then be tightened with a spanner Excessive tightening torque shall be avoided or otherwise the nut may be damaged A digital vacuum gauge shall be connected for vacuumizing The duration of vacuumizing shall be at least 15 minutes and the pressure of the vacuum gauge shal...

Page 9: ...dging of the refrigeration system requiring no disassembly of refrigeration elements and no welding In case replacement of gas liquid pipes is required during maintenance the joint of evaporator gas liquid pipes of the indoor unit shall be cut off with a cutting knife Connection is only allowed after re flaring the same to the outdoor unit Note in case relocation is required the joint of evaporato...

Page 10: ...e maintenance site shall be relatively fixed with standardized pipe routing Temporary wires and sockets at the maintenance site are not allowed The environment in which the refrigerant leakage is checked shall be free from potential ignition source Leak detection with halogen probes or any other detector with open fire shall be avoided For the system containing flammable refrigerant leak detection...

Page 11: ...ied out to ensure no leakage and reliable earthing In case the allowable voltage and current limit may be surpassed during the service of the air conditioner any inductance or capacitance cannot be added in the circuit Only the elements appointed by the air conditioner manufacturer can be used as the parts and components replaced or otherwise a fire or explosion may be triggered in case of refrige...

Page 12: ...linder and equipment must be evacuated rapidly and all the stop valves on the equipment must be closed 11 Before purification and tests the refrigerant recovered cannot be charged into another refrigeration system Note The air conditioner shall be marked with dates and signature after being scrapped and the refrigerant is discharged It shall be guaranteed that the sign on the air conditioner can r...

Page 13: ...k without circuit breaker Call the dealer to take measures to prevent the refrigerant from leaking If conditioner is installed in a small room be sure to take every measure in order to prevent suffocation and explosion accident even in case of refrigerant leakage When conditioner is installed or reinstalled the dealer should be responsible for them Incorrect installation may cause water leaking el...

Page 14: ... If installed improperly dust and or water may enter the unit and present a risk of electric shock smoke fire or explosion Only use refrigerant R32 as indicated on the unit when installing or relocating the unit The use of any other refrigerant or an introduction of air into the unit circuit may cause the unit to run an abnormal cycle and abnormal cycle and cause the unit to burst In the event of ...

Page 15: ...nections Use liquid refrigerant to charge the system Charge the unit with gas refrigerant will cause the refrigerant in the cylinder to change its composition and will lead to a drop in performance Do not use a charging cylinder The use of charging cylinder will change the composition of the refrigerant and lead to power loss Exercise special care when handling the tools An introduction of foreign...

Page 16: ...itioners in water Water on the unit presents a risk of electric shock Periodically check the platform on which is placed for damage to prevent the unit from falling If the unit is left on a damaged plarform it may topple over causing injury Things such as nails may be included in the package Dispose of them properly to prevent injury Plastic bags present a choking hazard to children Tear up the pl...

Page 17: ...rging Meter Refrigerant charging Vacuum Gauze Checking vacuum degree Tools Materials Use Notes Charging Cylinder Refrigerant Charging Must not be used with R32 type units CAUTION Items to Be Checked 1 Verify the type of refrigerant used by the unit to be serviced Refrigerant Type R32 2 Check the symptom exhibited by the unit to be serviced Look in this service handbook for symptoms relating to the...

Page 18: ...ack into the refrigerant circuit when the vacuum pump power is turned off power failure It is also possible to attach a check valve to the actual vacuum pump afterwards Standard degree of vacuum for the vacuum pump Use a pump which reaches 65Pa or below after 5 minutes of operation In addition be sure to use a vacuum pump that has been properly maintained and oiled using the specified oil If the v...

Page 19: ...ther places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moisture 10 On a flat surface that does not collect rain water 11 Away from strong wind 12 Away from direct exposure to rain or snow 13 Away from sea breeze 14 Away from inflammable mater...

Page 20: ...nity on the heat exchanger and applying a rust inhibitor more frequently than once a year ODU ODU ODU ODU Sea breeze Sea breeze Sea breeze Sea Sea Sea Protection walls ODU 7 Set the unit on mounting brackets or pad To avoid the adverse effects of snow ice and defrosting issues install the unit on heat pump risers to ensure a sufficient height from the ground In all cases refer to local code for co...

Page 21: ...pe with the finishing tape from bottom to top Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left in the insulation pipe s cut line more than 10cm more than 10cm more than 60cm more than 25cm 20 Installation figure please refers to the following Do not connected the embedded branch piping and the outdoor unit when only carrying out piping work...

Page 22: ...g and the maximum allowable height difference between the outdoor and indoor units are listed below The shorter the refrigerant piping the better the performance Connect so that the piping is as short as possible Shortest allowable length per room is 3m 1 Precautions on installation Check the strength and level of the installation ground so that unit will not cause any operating vibration or noise...

Page 23: ...eight under the outdoor unit s feet 3 In cold areas do not use a drain hose with the outdoor unit Otherwise drain water may freeze impairing heating performance Indoor Unit Outdoor Unit Level difference 15m max Level difference 7 5m max If the outdoor unit is positioned higher than all indoor units Outdoor Unit Indoor Unit Level difference 15m max Level difference 7 5m max If the outdoor unit is p...

Page 24: ...g all the connection and loosening then retightening thenuts reqeat steps 2 4 Remove covers from liquid stop valve and gas stop valve Turn the liquid stop valve s rod 90 degrees counterclockwise with a hexagonal wrench to open valve Close it after 5 seconds and check for gas leakage Using soapy water check for gas leakage from indoor unit s flare and outdoor unit s flare and valve rods After the c...

Page 25: ...ecommend 1 Before filling check whether the cylinder has a siphon attached or not It should have something like liquid filling siphon attached displayed on it recommend 2 Be sure to use the R32 tools to ensure pressure and to prevent foreign objects entering 1 This system must use refrigerant R32 2 Add refrigerant 20g per meter when the total piping length exceeds the standard value but make sure ...

Page 26: ... never install a drier to this R32 unit in order to guarantee its lifetime The drying material may dissolve and damage the system 5 Incompete flaring may cause refrigerant gas leakage Cut exactly at right angles Remove burrs Flare s inner surface must be flaw free The pipe end must be evenly flared in a perfect circle Make sure that the flare nut is fitted Check A Flare tooling die Pipe diameter S...

Page 27: ...nits for 5U outdoor and the rest outdoors follow the same logic Reinstall the clamp and cover of terminal box according to the Installation Manual after the connection above mentioned done 2 Wiring method Wiring Method for Ring Terminal Block Connect the wire with same diameter to the two sides of the terminal Do not connect the wire with same diameter to the same side Do not connect the wire with...

Page 28: ...e heat generation Do not connect the power line with different dimensions to the same grounding wire end Improper contact will affect protection Do not connect the power line to the connecting end of communication wire Incorrect connection will cause damage to the connected unit The wiring should ensure that the ground line is the last one to be broken off by force 4 Wiring method of indoor unit 5...

Page 29: ... bag b Separate DRED module to 3 parts as shown c Continue to separate the DRED module to 7 parts as shown 1 2 3 4 3 2 1 3 a Fix Pin 1 for contractor supplied line through nut 1 seal ring 2 tapered cup nut 3 insert to stud 4 b Repeat step 1 for fixed DRM line c Tighten the screw position on both sides a b c a b c 4 a Tighten the DRED module to right side plate b Tighten the screw Insert the DRED t...

Page 30: ...r example a flashing means No 15 failure that is indoor and outdoor communication error Wiring Error Check This product is capable of automatic checking of wiring error ON 4 3 2 1 CN2 CN3 CN1 CN4 SW1 4 3 2 1 5 During this operation the digital number will alternately show the compressor working frequency e g 50 stands for the current running frequency and letter CH means checking After this operat...

Page 31: ...unction of module temp sensor Momentary power failure detection 38 3A 5 8 Malfunction of condensing temp sensor 39 3B 5 9 Malfunction of liquid pipe temp sensor for indoor unit E 40 3C 6 0 System high pressure switch off 42 3E 6 2 System low pressure switch off 43 3F 6 3 44 40 6 4 45 41 6 5 Timer lamp flash time Running lamp flash time Communication failure between Module and ECU Module low or hig...

Page 32: ...Address Haier Industrial Park Qianwangang Road Eco Tech Development Zone Qingdao 266555 Shandong P R C Contacts TEL 86 532 88936943 FAX 86 532 8893 6999 Website www haier com ...

Reviews: