Inspection on Maintenance Environment

Maintenance Site Requirements

Leak Detection Methods

Safety Principles

9

  

Before operation, the refrigerant leaked in the room is not allowed.

  

The area of the room in which maintenance is made shall be in line with this manual.

  

Continuous ventilation shall be maintained during maintenance.

  

Open fire or high-temperature heat source higher than 548 degree which can easily give birth to open fire is not allowed

inside the room within the maintenance area.

  

During maintenance, the phones and the radioactive electronics of all the operators inside the room must be powered off.

  

One dry powder or carbon dioxide extinguisher shall be equipped inside the maintenance area, and the extinguisher must

be under available state.

  

The maintenance site shall be provided with favorable ventilation and must be flat. Arrangement of the maintenance site

inside the basement is not allowed.

  

Welding zone and non-welding zone shall be divided at the maintenance site, and shall be clearly marked. A certain safety

distance must be guaranteed between the two zones.

  

Ventilators shall be installed at the maintenance site, and exhaust fans, fans, ceiling fans, floor fans and dedicated exhaust

duct can be arranged, to meet the requirements of ventilation volume and uniform exhaust, and to avoid accumulation of

refrigerant gas.

  

Leak detection equipment for flammable refrigerant shall be equipped, with relevant management system being established.

Whether the leak detection equipment is under available state shall be confirmed before maintenance.

  

Sufficient dedicated vacuum pumps of flammable refrigerant and refrigerant charging equipment shall be equipped, with

relevant management system for maintenance equipment being established. It shall be guaranteed that the maintenance

equipment can only be used for vacuumizing and charging of one type of flammable refrigerant, and mixed usage is not

allowed.

  

The master power switch shall be arranged outside the maintenance site, with protective (anti-explosive) device being

equipped.

  

Nitrogen cylinders, acetylene cylinders and oxygen cylinders shall be placed separately. The distance between the gas

cylinders above and the working area involved in open fire shall be at least 6m. The anti-backfire valve shall be installed for

the acetylene cylinders. The color of the acetylene cylinders and oxygen cylinders installed shall meet the international

requirements.

  

The warning sign of " No Fire" ,"No Smoking", or"Anti static"shall be arranged inside the maintenance area.

  

Fire control device suitable for electric appliance such as the dry powder extinguisher or carbon dioxide extinguisher shall

be equipped, and shall always be under the available state.

  

The ventilator and other electrical equipment at the maintenance site shall be relatively fixed, with standardized pipe

routing. Temporary wires and sockets at the maintenance site are not allowed.

  

The environment in which the refrigerant leakage is checked shall be free from potential ignition source. Leak detection with

halogen probes (or any other detector with open fire) shall be avoided.

  

For the system containing flammable refrigerant, leak detection may be realized with electronic leak detection equipment.

During leak detection, the environment in which the leak detection equipment is calibrated shall be free from refrigerant. It

shall be guaranteed that the leak detection equipment will not become potential ignition source, and is applicable to the

refrigerant to be detected. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be

calibrated to the refrigerant employed, and the appropriate percentage of gas (25 % maximum) is confirmed.

  

The fluid used for leak detection shall be applicable to most of the refrigerant. The use of chlorine-containing solvent shall

be avoided, to avoid chemical reaction between chlorine and refrigerant and corrosion to copper pipelines.

  

In case leakage is suspected, the open fire at the site shall be evacuated or be put out.

  

In case welding is required at the leakage position, all the refrigerants shall be recovered, or be isolated at a position far

from the leak point with a stop valve. Before and during welding, the whole system shall be purified with OFN.

The power supply should be cut off before the maintenance

.

  

During product maintenance, favorable ventilation shall be guaranteed at the maintenance site, and the close of all the

doors/windows is not allowed.

  

Operation with open fire is not allowed, including welding and smoking. The use of phones is also not allowed. The user

shall be informed that cooking with open fire is not allowed.

  

During maintenance in a dry season, when the relative humidity is less than 40%, anti-static measures shall be taken,

including the wearing of cotton clothes and cotton gloves.

  

In case the leakage of flammable refrigerant is identified during maintenance, forced ventilation measures shall be taken

immediately, and the source of leak shall be plugged.

  

In case the product damaged must be maintained by disassembling the refrigeration system, the product must be delivered

to the maintenance point. Welding of refrigerant pipelines at the user's site is not allowed.

  

During maintenance, in case re-treatment is required due to lack of fittings, the air conditioner shall be reset.

  

The refrigeration system must be safely earthed in the whole course of maintenance.

  

For the door-to-door service with refrigerant cylinders, the refrigerant charged inside the cylinder cannot exceed the specified

value. The cylinder placed in vehicles or at the installation/maintenance site shall be fixed perpendicularly and be kept away

from heat sources, ignition source, source of radiation and electric appliance.

Summary of Contents for 3U55S2PR1FA

Page 1: ...TIONER 3U55S2PR1FA 4U71S2PR1FA 4U80S2PR1FA 5U125S2PN1FA 0150558811 Move and scrap the air conditioning Contents Safety Precautions Read Before Installation Accessories Procedure for Selecting the location Installation drawings of indoor and outdoor units Precautions on Installation Limitations on the installation Refrigerant piping work Pump Down Operation Wiring work Dred function Test running Tr...

Page 2: ...y refrigerant charge of the product see unit name plate C additional refrigerant amount charged in the field D total refrigerant charge E outdoor unit F refrigerant cylinder and manifold for charging Air conditioner working temperature cooling 10 46 degree heating 15 24 degree The single indoor unit will reduce in heating efficiency if the ambient temperature is under 0 degree WARNING IMPORTANT IN...

Page 3: ...ware that refrigerants may not contain an odour The appliance must be installed operated and stored in a room with a floor area larger than the Minimum Room Area specified in the table on the following pages The room should be well ventilated Comply with national gas regulations This appliance can be used by children aged 8 years and above and persons with reduced physical sensory or mental capabi...

Page 4: ... do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock fire or explosion If any refrigerant has leaked out during the installation work ventilate the room The refrigerant produces a toxic gas if exposed to flames may cause explosion After all installation is complete check to make sure t...

Page 5: ...all be used for maintenance and exposed transporting of refrigerant cylinders and the products to be maintained is not allowed 4 The rain cover or similar shielding material of transporting vehicles shall be provided with certain flame retardancy 5 Leakage warning device of flammable refrigerant shall be installed inside the closed type compartment 6 Anti static device shall be equipped inside the...

Page 6: ...hecked cannot be less than the area specified on the warning sign of the indoor unit 2 Inspection on the surrounding environment of place of installation the outdoor unit of flammable refrigerants air conditioner cannot be installed inside an enclosed room reserved 3 Power supply switches or other high temperature articles such as the fire source and oil heater shall be avoided below the indoor un...

Page 7: ...r of the indoor unit is connected to the connector pipe after welding nitrogen more than 4 0MPa shall be charged inside the evaporator and the piping connected to evaporator with a nitrogen cylinder adjusted by a reducing valve Afterwards the valve of the nitrogen cylinder shall be closed for leak detection with soapy water or leak detecting solution The pressure shall be maintained for more than ...

Page 8: ...with the conical surface of corresponding valve connector The nut of connecting pipes shall be installed at a proper position and then be tightened with a spanner Excessive tightening torque shall be avoided or otherwise the nut may be damaged A digital vacuum gauge shall be connected for vacuumizing The duration of vacuumizing shall be at least 15 minutes and the pressure of the vacuum gauge shal...

Page 9: ...dging of the refrigeration system requiring no disassembly of refrigeration elements and no welding In case replacement of gas liquid pipes is required during maintenance the joint of evaporator gas liquid pipes of the indoor unit shall be cut off with a cutting knife Connection is only allowed after re flaring the same to the outdoor unit Note in case relocation is required the joint of evaporato...

Page 10: ...e maintenance site shall be relatively fixed with standardized pipe routing Temporary wires and sockets at the maintenance site are not allowed The environment in which the refrigerant leakage is checked shall be free from potential ignition source Leak detection with halogen probes or any other detector with open fire shall be avoided For the system containing flammable refrigerant leak detection...

Page 11: ...ied out to ensure no leakage and reliable earthing In case the allowable voltage and current limit may be surpassed during the service of the air conditioner any inductance or capacitance cannot be added in the circuit Only the elements appointed by the air conditioner manufacturer can be used as the parts and components replaced or otherwise a fire or explosion may be triggered in case of refrige...

Page 12: ...linder and equipment must be evacuated rapidly and all the stop valves on the equipment must be closed 11 Before purification and tests the refrigerant recovered cannot be charged into another refrigeration system Note The air conditioner shall be marked with dates and signature after being scrapped and the refrigerant is discharged It shall be guaranteed that the sign on the air conditioner can r...

Page 13: ...k without circuit breaker Call the dealer to take measures to prevent the refrigerant from leaking If conditioner is installed in a small room be sure to take every measure in order to prevent suffocation and explosion accident even in case of refrigerant leakage When conditioner is installed or reinstalled the dealer should be responsible for them Incorrect installation may cause water leaking el...

Page 14: ... If installed improperly dust and or water may enter the unit and present a risk of electric shock smoke fire or explosion Only use refrigerant R32 as indicated on the unit when installing or relocating the unit The use of any other refrigerant or an introduction of air into the unit circuit may cause the unit to run an abnormal cycle and abnormal cycle and cause the unit to burst In the event of ...

Page 15: ...nections Use liquid refrigerant to charge the system Charge the unit with gas refrigerant will cause the refrigerant in the cylinder to change its composition and will lead to a drop in performance Do not use a charging cylinder The use of charging cylinder will change the composition of the refrigerant and lead to power loss Exercise special care when handling the tools An introduction of foreign...

Page 16: ...itioners in water Water on the unit presents a risk of electric shock Periodically check the platform on which is placed for damage to prevent the unit from falling If the unit is left on a damaged plarform it may topple over causing injury Things such as nails may be included in the package Dispose of them properly to prevent injury Plastic bags present a choking hazard to children Tear up the pl...

Page 17: ...rging Meter Refrigerant charging Vacuum Gauze Checking vacuum degree Tools Materials Use Notes Charging Cylinder Refrigerant Charging Must not be used with R32 type units CAUTION Items to Be Checked 1 Verify the type of refrigerant used by the unit to be serviced Refrigerant Type R32 2 Check the symptom exhibited by the unit to be serviced Look in this service handbook for symptoms relating to the...

Page 18: ...ack into the refrigerant circuit when the vacuum pump power is turned off power failure It is also possible to attach a check valve to the actual vacuum pump afterwards Standard degree of vacuum for the vacuum pump Use a pump which reaches 65Pa or below after 5 minutes of operation In addition be sure to use a vacuum pump that has been properly maintained and oiled using the specified oil If the v...

Page 19: ...ther places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moisture 10 On a flat surface that does not collect rain water 11 Away from strong wind 12 Away from direct exposure to rain or snow 13 Away from sea breeze 14 Away from inflammable mater...

Page 20: ...nity on the heat exchanger and applying a rust inhibitor more frequently than once a year ODU ODU ODU ODU Sea breeze Sea breeze Sea breeze Sea Sea Sea Protection walls ODU 7 Set the unit on mounting brackets or pad To avoid the adverse effects of snow ice and defrosting issues install the unit on heat pump risers to ensure a sufficient height from the ground In all cases refer to local code for co...

Page 21: ...pe with the finishing tape from bottom to top Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left in the insulation pipe s cut line more than 10cm more than 10cm more than 60cm more than 25cm 20 Installation figure please refers to the following Do not connected the embedded branch piping and the outdoor unit when only carrying out piping work...

Page 22: ...g and the maximum allowable height difference between the outdoor and indoor units are listed below The shorter the refrigerant piping the better the performance Connect so that the piping is as short as possible Shortest allowable length per room is 3m 1 Precautions on installation Check the strength and level of the installation ground so that unit will not cause any operating vibration or noise...

Page 23: ...eight under the outdoor unit s feet 3 In cold areas do not use a drain hose with the outdoor unit Otherwise drain water may freeze impairing heating performance Indoor Unit Outdoor Unit Level difference 15m max Level difference 7 5m max If the outdoor unit is positioned higher than all indoor units Outdoor Unit Indoor Unit Level difference 15m max Level difference 7 5m max If the outdoor unit is p...

Page 24: ...g all the connection and loosening then retightening thenuts reqeat steps 2 4 Remove covers from liquid stop valve and gas stop valve Turn the liquid stop valve s rod 90 degrees counterclockwise with a hexagonal wrench to open valve Close it after 5 seconds and check for gas leakage Using soapy water check for gas leakage from indoor unit s flare and outdoor unit s flare and valve rods After the c...

Page 25: ...ecommend 1 Before filling check whether the cylinder has a siphon attached or not It should have something like liquid filling siphon attached displayed on it recommend 2 Be sure to use the R32 tools to ensure pressure and to prevent foreign objects entering 1 This system must use refrigerant R32 2 Add refrigerant 20g per meter when the total piping length exceeds the standard value but make sure ...

Page 26: ... never install a drier to this R32 unit in order to guarantee its lifetime The drying material may dissolve and damage the system 5 Incompete flaring may cause refrigerant gas leakage Cut exactly at right angles Remove burrs Flare s inner surface must be flaw free The pipe end must be evenly flared in a perfect circle Make sure that the flare nut is fitted Check A Flare tooling die Pipe diameter S...

Page 27: ...nits for 5U outdoor and the rest outdoors follow the same logic Reinstall the clamp and cover of terminal box according to the Installation Manual after the connection above mentioned done 2 Wiring method Wiring Method for Ring Terminal Block Connect the wire with same diameter to the two sides of the terminal Do not connect the wire with same diameter to the same side Do not connect the wire with...

Page 28: ...e heat generation Do not connect the power line with different dimensions to the same grounding wire end Improper contact will affect protection Do not connect the power line to the connecting end of communication wire Incorrect connection will cause damage to the connected unit The wiring should ensure that the ground line is the last one to be broken off by force 4 Wiring method of indoor unit 5...

Page 29: ... bag b Separate DRED module to 3 parts as shown c Continue to separate the DRED module to 7 parts as shown 1 2 3 4 3 2 1 3 a Fix Pin 1 for contractor supplied line through nut 1 seal ring 2 tapered cup nut 3 insert to stud 4 b Repeat step 1 for fixed DRM line c Tighten the screw position on both sides a b c a b c 4 a Tighten the DRED module to right side plate b Tighten the screw Insert the DRED t...

Page 30: ...r example a flashing means No 15 failure that is indoor and outdoor communication error Wiring Error Check This product is capable of automatic checking of wiring error ON 4 3 2 1 CN2 CN3 CN1 CN4 SW1 4 3 2 1 5 During this operation the digital number will alternately show the compressor working frequency e g 50 stands for the current running frequency and letter CH means checking After this operat...

Page 31: ...unction of module temp sensor Momentary power failure detection 38 3A 5 8 Malfunction of condensing temp sensor 39 3B 5 9 Malfunction of liquid pipe temp sensor for indoor unit E 40 3C 6 0 System high pressure switch off 42 3E 6 2 System low pressure switch off 43 3F 6 3 44 40 6 4 45 41 6 5 Timer lamp flash time Running lamp flash time Communication failure between Module and ECU Module low or hig...

Page 32: ...Address Haier Industrial Park Qianwangang Road Eco Tech Development Zone Qingdao 266555 Shandong P R C Contacts TEL 86 532 88936943 FAX 86 532 8893 6999 Website www haier com ...

Reviews: