Service diagnosis
4
6
Domestic air conditioner
10.3.11 Loss of synchronism detection
Inverter side current detection is abnormal
Outdoor Display LED1 flash 18 times
LED1 flash 19 times
Method of The position of the compressor rotor can not detected normally
Malfunction
Detection
Malfunction when the wiring of compressor is wrong or the connection is poor;
Decision or the compressor is damaged
Conditions
Supposed
■
Faulty The wiring of compressor
Causes
■
Faulty compressor
■
Faulty PCB
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or parts
damage may be occurred.
Within 3 minutes after the machine is
supplied with power and turned on with
the remote controller, check whether
the compressor can start up
1. The wiring of compressor is incorrect
or the connection is poor;
2. The compressor is damaged
At first, the compressor start up ,soon the
compressor stopped with the LED1 on the
outdoor PCB blinks
(
1Hz
)
19/18 times
IPM Module is damaged and needs
replacing.
the Malfunctions exist also, the
compressor is damaged replace a
new one
YES
NO
YES
Malfunction unsolved
Maybe there is some disturbance
Summary of Contents for 1U18TR4ERA
Page 11: ...Pinping diagrams Domestic air conditioner 4 Piping diagrams 9 EEV EEV ...
Page 12: ...Operation range Domestic air conditioner 5 Operation range 10 ...
Page 63: ...Domestic air conditioner Removal of procedure 1 Removal of Outdoor panel 1 ...
Page 65: ...Domestic air conditioner Loosen the screws and pull the panel Removal of procedure 3 ...
Page 66: ...Domestic air conditioner 2 Removal of Electrical Box Removal of procedure 4 ...
Page 67: ...Domestic air conditioner 3 Removal of Fan and Fan Motor Removal of procedure 5 ...
Page 69: ...Domestic air conditioner 4 Removal of Fan Motor Bracket and Partition Removal of procedure 7 ...
Page 70: ...Domestic air conditioner and remove the reactor Loosen the screw Removal of procedure 8 ...