Service diagnosis
4
4
Domestic air conditioner
10.3.10 The communication fault between indoor and outdoor
Indoor display E7
outdoor display LED1 flash 15 times
Method of Communication is detected by checking the indoor PCB and the outdoor PCB.
Malfunction
Detection
Malfunction
■
The outdoor PCB broken leads to communication fault.
Decision
■
The indoor PCB broken leads to communication fault.
Conditions
Supposed
■
Communication wiring disconnected.
Causes
■
The indoor PCB is broken.
■
The outdoor PCB is broken.
■
The Module PCB is broken.
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or else
parts damage may be occurred.
NO
(
A
)
Yes
NO
Yes
No
YES
Restart the a/c and it
becomes normally.
If starting up normally, but
malfunction occurs again after a
while
Check whether the linking cable
between the indoor and outdoor is well
connected or whether its core wires are
well insulated.
The outdoor mainboard needs
dehumidification.
The outdoor mainboard needs
dedust.
1. Reconnect the linking cable;
2. Replace the linking cable with new
one.
Summary of Contents for 1U18TR4ERA
Page 11: ...Pinping diagrams Domestic air conditioner 4 Piping diagrams 9 EEV EEV ...
Page 12: ...Operation range Domestic air conditioner 5 Operation range 10 ...
Page 63: ...Domestic air conditioner Removal of procedure 1 Removal of Outdoor panel 1 ...
Page 65: ...Domestic air conditioner Loosen the screws and pull the panel Removal of procedure 3 ...
Page 66: ...Domestic air conditioner 2 Removal of Electrical Box Removal of procedure 4 ...
Page 67: ...Domestic air conditioner 3 Removal of Fan and Fan Motor Removal of procedure 5 ...
Page 69: ...Domestic air conditioner 4 Removal of Fan Motor Bracket and Partition Removal of procedure 7 ...
Page 70: ...Domestic air conditioner and remove the reactor Loosen the screw Removal of procedure 8 ...