(1 = - 29 to 59 = + 29 - Seconds per day - 30 = No change)
The default setting is 30.
Note: If an HAI automation system is being used, the controller
system time is sent to the thermostat every minute. This adjustment
will have no effect.
15 Filter reminder
The thermostat logs the amount of time the system fan has been
running. When this setting reaches 0, the thermostat will display a
reminder to replace the filter. The setting is the amount of days (24
hours of system operation) before this reminder is displayed.
Days - Counting down from 10 - 0
16 System runtime (This week)
This item logs the amount of time (hours) that the heating and
cooling system was in operation this week.
17 System runtime (Last week)
This item logs the amount of time (hours) that the heating and
cooling system was in operation last week.
ANTICIPATION
Anticipation is performed electronically and is independent of the
type and load of the components in the heating and cooling
equipment. This thermostat has electronic control based on
proportional, integral and derivative components and maintains
temperature to within 1 degree F of the setting. Anticipation is not
adjustable.
OWNER'S MANUAL
Following Installer Setup, check the option boxes ( ) in the Owner's
Manual according to the configuration of the thermostat.
14