Setting
Cycles per hour (maximum)
5
6
6
5
7
4
8
3.7
10
3
The recommended setting is 8 minutes. A higher setting may be
appropriate for buildings with low heat loss/gain.
The default setting is 8.
12 Heating minimum on/off time (minutes)
Same as Cooling minimum on/off time, for the heating system.
The default setting is 8.
13 Stage 2 Differential
This item specifies the temperature difference between stage 1 and
stage 2. The default setting of 2 (degrees F) is recommended for all
applications. In special cases a setting of 3 or 4 may be used when
precise control of temperature is not as important as highest energy
efficiency, however, the thermostat will not be able to maintain
temperature within 1 degree of its setting under severe weather
conditions. A setting of 1 or 0 is not recommended.
In this thermostat, the automatic anticipator will compensate for the
temperature "droop" caused by the stage 2 differential under cold
weather conditions.
The default setting is 2.
14 Clock adjust
If the clock on the thermostat is running faster or slower than the
actual time, you can have the thermostat automatically compensate up
to 29 seconds per day. The thermostat will add or subtract the
selected amount of time daily.
13