Functional test, inspection, maintenance and care
44
Technical changes reserved
7
Functional test, inspection, maintenance and care
-
The fire safety housings must be serviced at least twice a year and checked
to ensure they are functioning properly. We recommend that you carry out a
functional test (visual inspection) once a month. Only a qualified technician
can carry out the safety inspection with the necessary care as this requires
adequate experience and a comprehensive level of knowledge.
-
Check the silicone seam twice a year for cracking.
-
Common and mild household cleaning agents can be used to clean the
outside of the fire safety housing.
-
The doors’ closing mechanism must be oiled twice a year.
-
The fire safety housing must be protected against water, moisture penetration
and splashing water.
-
If any safety relevant damage is identified, the fire safety housing must be
serviced with original parts before continued use.
-
Check the fan unit and smoke detector twice a year.
-
Check the air filter regularly (depending on ambient conditions) for dirt and
clean. Replace if necessary.
Air filter as replacement item
Panel width
Item no.
1
FZ399N
2
FZ400N
3
FZ401N
4
FZ402N
8
Disposal information
Environmental protection:
Electrical waste products should not be disposed of with
household waste. Please recycle electrical components in
a designated location. You can get advice from your local
authority on professional recycling.