ESPRIT Gas Extinguishing User Manual 

 

CONFIGURING THE PANEL 

 

 
 

 

45 

Approved Document Ref: UI-ESG-01 Issue 2.0 

 

When  the  required  changes  are  completed,  press  return 

  button  to  return  to 

DEVICES

 

Menu.  A  short  sequence  of  buzzer  beeps  will  indicate  that  changes  have  been  stored  in 
memory. 

 

To go back to the main logo screen, press the return 

 button and the 

 

button as required. 

 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for ESG-2001

Page 1: ...NSTALLATION COMMISSIONING OPERATING MANUAL This manual covers the installation programming and commissioning of the Esprit Extinguishing Fire Alarm Control Panels for One and Two Flood Zones www acorn...

Page 2: ...d EN12094 1 2003 Requirements and test methods for electrical automatic control and delay devices Haes Technologies Ltd declare that the products identified below conform to the essential requirements...

Page 3: ...4 26 Triggering Signals to Equipment outside the System 4 27 Emergency Abort Device 4 30 Activation of Alarm Devices with Different Signals EN54 2 1997 A1 Control and indicating equipment for fire de...

Page 4: ...e Standby Current Alarm Current ESG 1002 Esprit Ext Control Panel Single Flood Zone 3 4A PSU 205mA 300mA ESG 1003 Esprit Ext Control Panel Dual Flood Zone 3 4A PSU Large Cabinet 207mA 365mA ESG 1004 E...

Page 5: ...nnections 19 Connecting the Batteries 19 Battery Charging Voltage Checks 20 Detection Zone Inputs 20 Sounders Monitored Output Circuits 22 Relay Outputs 23 Inputs Class Change and Pulse 24 Monitored I...

Page 6: ...GAS CARD 57 CONFIG Menu DEVICES 58 CONFIG Menu P BUS 61 CONFIG Menu PSU 61 CONFIG Menu sub menu Breakdown 62 CONTROL Menu 68 Control Menu EXTRACT 68 Control Menu FLOODING 69 Control Menu DELAYS 69 CON...

Page 7: ...e client s employees and assets are protected to the highest degree with the minimum risk The panels are available in One Flood Zone three Conventional Detection Circuits and Two Flood Zones six conve...

Page 8: ...IT Gas Extinguishing User Manual PRODUCT OVERVIEW 8 Approved Document Ref UI ESG 01 Issue 2 0 Cabinet for Single Flood Zone Cabinet for Two Flood Zones www acornfiresecurity com www acornfiresecurity...

Page 9: ...nguishing User Manual PRODUCT OVERVIEW 9 Approved Document Ref UI ESG 01 Issue 2 0 Circuit Boards 2827 206 DISPLAY CARD 2972 206 EXTENSION LEDs CARD 2nd Flood Zone www acornfiresecurity com www acornf...

Page 10: ...ESPRIT Gas Extinguishing User Manual PRODUCT OVERVIEW 10 Approved Document Ref UI ESG 01 Issue 2 0 2879 206 PSU CARD 2883 206 GAS CARD www acornfiresecurity com www acornfiresecurity com...

Page 11: ...sounders outputs to pulse PBUS Note Stage sounders will not be affected unless programmed to do so see program details PBUS Input for RS 485 Peripheral BUS PBUS circuit for remote control call points...

Page 12: ...W SW Flow switch monitored input Current limit Max 50mA 6K8 EOL PRESS SW Pressure switch monitored input Current limit Max 50mA 6K8 EOL MAN REL Manual release monitored input Current limit Max 50mA 6K...

Page 13: ...s supply 230VAC 10 15 50Hz max current 0 74Amp 35W for Single flood zone 230VAC 10 15 50Hz max current 2 1 Amp 100W for Dual flood zone Mains supply fuse 2 Amp T2A 250V 35W unit 4 Amp T4A 250V 100W un...

Page 14: ...oltage 27 3VDC nominal at 20 C for single and dual flood zones Temperature compensated Battery charging output current 700mA Both sizes Current limited Charging supressed During Alarm Condition Batter...

Page 15: ...e 3v6 Zener diode SOUNDERS 1 2 28VDC polarity reversal monitored sounder outputs to fire alarm devices 6K8 Ohm 5 0 25W EOL resistor Monitoring current limit 28mA fused at 500mA Typical max load 22 dev...

Page 16: ...ning 21 30VDC 2A continuous rated for solenoids 3A at 450mS available for Metron actuators Monitored inputs 6 FLOW SW PRESS SW MAN REL HOLD ABORT AUTO MAN End of line resistor 6K8 Thresholds 8K to 1K2...

Page 17: ...e protective earth will render the equipment unsafe Warnings Warning Sign Before installation refer to the ratings shown on the label inside the product and to the Specifications Chart in this documen...

Page 18: ...ubject to shock or vibration Environments where there is damp salt air water ingress or extremes of temperature must be avoided The temperature should be in the range of 5 C to 40 C and the relative h...

Page 19: ...ains supply is restored the batteries will be automatically reconnected Note If the mains are connected before the batteries the panel will show a Power Supply fault for up to 1 minute until the monit...

Page 20: ...tch should be set to ON which will override the temperature compensation controls Carefully adjust the voltage to 29 0VDC 0 2V When completed switch off Access Level 3 DIL switch and re connect the ba...

Page 21: ...the return key or Enter key as the calibration changes made will be lost and the calibration procedure will need to be repeated Detection Zone Inputs A maximum of 32 detectors per zone only can be fit...

Page 22: ...e output circuits are provided for single flood zone and six conventional 24VDC programmable and monitored sounder style output circuits are provided for dual flood zone 6K8 End of Line Resistor The s...

Page 23: ...fter the flooding time has elapsed without a reset This allows a flooded area to be vented of extinguishing medium Local Fire Relay operates on activation of a fire condition in a Flood Zone Stage 1 R...

Page 24: ...do so see program details Pulse Switch ve inputs which cause the common sounder and detection zone stage sounder s outputs to pulse Note Stage sounders will not be affected unless programmed to do so...

Page 25: ...ust have a 6k8 resistor fitted at the panel terminals Extinguishing Actuator Output Wiring The circuit is monitored for both open and circuit conditions No EOL resistor needed The output can supply a...

Page 26: ...on the actuator circuit should be calculated to ensure that the voltage at the end of the circuit exceeds the minimum required by the solenoid typically 18V when the actuator circuit has minimum outpu...

Page 27: ...d mini RSU require a 4 wire connection 2 wires for 28Vpower 2 wires for RS485 data from the control panel Each RSU has a PCB mounted DIL switch and must be allocated a unique address between 1 and 16...

Page 28: ...PERATING INSTRUCTIONS Panel Control and Indicators Control Panel The Control Panel contains LCD Display Screen Control Keypads Manual Extinguisher Release Status LED Indicators Activate Controls Key O...

Page 29: ...uring a fi re or fault condition This function is operational without the need to activate controls Also has the numeric value 3 for code entry Return Press to exit current menu or command as indicate...

Page 30: ...sounder circuits have been disabled or are in test mode Indicates a fault on one or more sounder circuits Power Supply Fault N A Indicates a power supply fault on mains power input or battery Delay S...

Page 31: ...in test mode A Fault exists which may prevent the release of extinguishant Manual Only Indicates that extinguishant can only be released by means of a manual release button Briefly indicates during a...

Page 32: ...de has not been entered Available Functions The functions that can be performed in Access Level 1 are Manually activate the extinguisher release Mute the internal sounder View active faults Change fro...

Page 33: ...Menu will become available for operation Once the four digit code is entered or the Activate Controls key is turned to On the LCD unit will display the Main Menu Use the Scroll Control keypad up down...

Page 34: ...3333 is the factory default The access code may be changed from the CONFIG menu PANEL sub menu Available Functions The functions that can be performed at Access level 3 are Set the panel to automatica...

Page 35: ...ss key o Use the Up Down arrow keys to increase decrease the number value of the first digit in the 4 digit sequence o Use the Left Right arrow keys to move to the next digit in the 4 digit sequence o...

Page 36: ...isplay shows UNAFFECTED Activated Released Condition The extinguishant Activated Released condition is established for a Flood Zone when Two or more detectors in a single Detection Zone or one or more...

Page 37: ...ue to be activated to warn that extinguishant has been released Flooding Stage 2 During this phase the now released extinguishant spreads out and settles in the flood zone Gas Released LED continues t...

Page 38: ...e of extinguishant Flow switch would need a trigger 470 After trigger extinguishant release is started and Gas Released LED illuminated steady Gas Released sounder 2nd Stage Sounder is activated The d...

Page 39: ...minent countdown is reset to the beginning and restarts Abort Condition If an Extinguishant Abort button is activated in a Flood Zone that is in a Fire Alarm condition the Release Imminent countdown f...

Page 40: ...fline fault o Fault relay is activated Extension LED board Gas Area 2 LEDs o System Fault LED illuminated continuous o General Fault LED illuminated pulsing o The extension LED Board is halted o Fault...

Page 41: ...utput options etc Extinguishant release CONTROL Menu Set configurable options for extinguishant release including for FLOOD and EXTRACT Accessing the Menu Structure Power on the panel and wait for it...

Page 42: ...use Left Right arrow keys to move cursor to CONFIG menu icon Press key to select CONFIG menu The digital display will show the following message Enter Level 3 Access Code Use the keypad to enter code...

Page 43: ...list containing all 16 RSUs and show if they are connected or not using the P BUS indicated by PRESENT or NOT PRESENT P BUS 1 1st RSU PRESENT NOT PRESENT 2 2nd RSU PRESENT NOT PRESENT 3 3rd RSU PRESE...

Page 44: ...nter Level 3 Access Code Use the keypad to enter code 3333 o Press key o Use the Up Down arrow keys to increase decrease the number value o Use the Left Right arrow keys to move to the next digit in t...

Page 45: ...n the required changes are completed press return button to return to DEVICES Menu A short sequence of buzzer beeps will indicate that changes have been stored in memory To go back to the main logo sc...

Page 46: ...ts are set to the code 1111 press button o The Main Menu will become available for operation Note Access level 2 Menu will deactivate after 30 sec if not used User Menu AUTO MANUAL MODE Menu Used to s...

Page 47: ...1 SOUNDERS ENABLED DISABLED 2 FIRE Relay ENABLED DISABLED 3 FARE OUTPUT ENABLED DISABLED 4 FAULT Relay ENABLED DISABLED 5 FFRE OUTPUT ENABLED DISABLED GAS AREA ONE 6 Zone ONE ENABLED DISABLED 7 Zone T...

Page 48: ...turn key to return to User menu User Menu Time Date The Time Date and Set DST sub menus are used to set the system clock and the local Daylight Savings Time Time Date Menu Time Date To set the system...

Page 49: ...u User Menu LAMP TEST To test the panel LCD display and warning LEDs On the Main Menu use Left Right arrow keys to move cursor box to User menu Press key to select the User menu Under User menu highli...

Page 50: ...t Right arrow keys to move cursor box to User menu Press key to select the User menu Under User Menu highlight the BUZZER option and then press key to select it Under BUZZER Menu the following option...

Page 51: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 51 Approved Document Ref UI ESG 01 Issue 2 0 User Menu Breakdown www acornfiresecurity com www acornfiresecurity com...

Page 52: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 52 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Page 53: ...Left Right arrow keys to move to the next digit in the 4 digit sequence o When all 4 digits have been set to the code 1111 press the key again o The Main Menu will become available for operation Note...

Page 54: ...following information will be displayed in turn each accompanied by a progress bar o LEARNING INTERNAL CARDS o LEARNING EXTINGUISHANT o LEARNING P BUS On completion of the learning routine the LEARN P...

Page 55: ...tem Fault status LEDs will be illuminated pulsing with an accompanying fault tone from the internal buzzer Additionally on return to the Title screen a FAULT display will list the applicable faults Th...

Page 56: ...lue has been selected then the system will return to CONFIG PANEL Menu and all the current settings will be maintained If YES is selected then all current settings will be overwritten and the system w...

Page 57: ...2 Zone FOUR YES NO 13 Zone FIVE YES NO 14 Zone SIX YES NO 15 CONTRIBUTORY COUNT ONE TWO THREE FOUR Configure the various options for the Gas Card s as follows o Use Left Right arrow keys to toggle bet...

Page 58: ...LARM YES NO 3 INTRINS SAFE YES NO 4 PRIORITY ALARM ENABLED DISABLED 5 HEAD REMOVAL ENABLED DISABLED 6 Sounder DELAY OFF 10 SEC 20 SEC 30 SEC 1 MIN 90 SEC 2 10 MIN Use Up Down arrow keys to select betw...

Page 59: ...er HOLD OUTPUT YES NO Note Single Flood Zone Panels will have 4 Sounders 2 Common PSU Card Sounders and 2 Sounders for the Gas Card Dual Flood Zone Panels will have 6 Sounders 2 Common PSU Card Sounde...

Page 60: ...10 EVAC CONTINUOUS PULSING OFF 11 FAULT CONTINUOUS PULSING OFF 12 FAIL YES NO 13 EXTRACT AREA 1 YES NO 14 EXTRACT AREA 2 YES NO Note Single Flood Zone Panels will have 6 Relays 2 common Relays on the...

Page 61: ...return to CONFIG Devices menu A short acknowledgement sound will be present Note Any differences between detected devices and changes made by user will result in a General Fault condition The General...

Page 62: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 62 Approved Document Ref UI ESG 01 Issue 2 0 CONFIG Menu Breakdown www acornfiresecurity com www acornfiresecurity com...

Page 63: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 63 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Page 64: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 64 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Page 65: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 65 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Page 66: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 66 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Page 67: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 67 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Page 68: ...display will show the following message Enter Level 3 Access Code Use the keypad to enter code 3333 o Press key o Use the Up Down arrow keys to increase decrease the number value o Use the Left Right...

Page 69: ...ll be presented as follows FLOODING AREA ONE AREA TWO STOP STOP STATE STATE FLOODING OFF FLOODING OFF Use Left Right arrow keys to move between Flood Zone Areas dual flood zone panels only Press the k...

Page 70: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 70 Approved Document Ref UI ESG 01 Issue 2 0 CONTROL Menu Breakdown www acornfiresecurity com www acornfiresecurity com...

Page 71: ...to increase decrease the number value o Use Left Right arrow keys to move to the next digit in the 4 digit sequence o When all 4 digits have been set to the code 1111 press the key again The Main Menu...

Page 72: ...he return key or key to return to the Main Menu display Report Menu FAULT From the FAULT sub menu the number of FAULT events is displayed To get FAULT events information On the Main Menu use Left Righ...

Page 73: ...nu will become available for operation On the Main Menu use Left Right arrow keys to move cursor to Report menu icon and press key to select From the Report Menu use Left Right arrow keys to move curs...

Page 74: ...Left Right arrow keys to move curser to select OTHER sub menu Press key to select The number n of OTHER events will be displayed in the following manner OTHER A 00 F 00 D 00 O nn List of detected oth...

Page 75: ...ENT HISTORY will open e g nnnn PANEL RESET nnnn BATTERY MISSING nnnn MAINS FAIL Note Where nnnn represents an automatically assigned four digit sequential number allocated to each event Use the Up Dow...

Page 76: ...ress key to select the Report menu Under Report Menu select the COUNTER option and then press key to access it The ALARM COUNT sub menu will open and the following information will be available ALARM...

Page 77: ...SU Card To get status information for the panel s PSU card On the Main Menu use Left Right arrow keys to move cursor box to Report menu Press key to select the Report menu Under Report Menu select the...

Page 78: ...Manual CONFIGURING THE PANEL 78 Approved Document Ref UI ESG 01 Issue 2 0 Next press return key or key to return to the Report Menu A short acknowledgement sound will be present www acornfiresecurity...

Page 79: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 79 Approved Document Ref UI ESG 01 Issue 2 0 Report Menu Breakdown www acornfiresecurity com www acornfiresecurity com...

Page 80: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 80 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Page 81: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 81 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Page 82: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 82 Approved Document Ref UI ESG 01 Issue 2 0 www acornfiresecurity com www acornfiresecurity com...

Page 83: ...in the zone s in test detectors call points etc can be activated and the panel will automatically reset enabling the system to be tested by one person Under the Test MODE sub menu the following sub m...

Page 84: ...NERAL 1 SOUNDERS EXCLUDED TESTING GAS AREA ONE 2 Zone ONE EXCLUDED TESTING 3 Zone TWO EXCLUDED TESTING 4 Zone THREE EXCLUDED TESTING GAS AREA TWO for twin Flood Zone panels 5 Zone FOUR EXCLUDED TESTIN...

Page 85: ...to move curser to select MISC sub menu Press key to select The MISC OPTIONS menu will now be displayed as follows 1 REMOVE ALL Disablement Highlight the REMOVE ALL Disablement option and press key to...

Page 86: ...ESPRIT Gas Extinguishing User Manual CONFIGURING THE PANEL 86 Approved Document Ref UI ESG 01 Issue 2 0 ENG Menu Breakdown www acornfiresecurity com www acornfiresecurity com...

Page 87: ...indicating venting aperiodic load test with the Mains supply disabled to ensure adequate battery capacity Both batteries should be renewed if there is any doubt about their integrity The memory log sh...

Page 88: ...www haes Tech com www acornfiresecurity com www acornfiresecurity com...

Reviews: