Control Menu: FLOODING
To configure the
FLOODING
controls, access the
FLOODING
menu.
•
From the
CONTROL Menu
, highlight
FLOODING
option and then press the
✓
key in order
to gain access to it, the following will be displayed:
Enter Level 3 Access Code
•
Use the keypad to enter code 3333:
o
Press
✓
key
o
Use the Up/Down arrow keys to increase/decrease the number value of the first digit
in the 4-digit sequence.
o
Use the Left/Right arrow keys to move to the next digit in the 4-digit sequence
o
When all 4 digits have been set to the code 3333 press
✓
key once again.
•
The
FLOODING
menu will be presented, as follows:
FLOODING
AREA ONE:
AREA TWO
STOP
STOP
STATE:
STATE:
FLOODING / OFF
FLOODING / OFF
•
Use Left/Right arrow keys to move between Flood Zone Areas (dual flood zone panels only).
•
Press the
✓
key to stop flooding time count (jumps to end of Flooding time count, when
stopped).
•
The indicated
STATE
on the screen will change from
FLOODING
to
OFF
.
•
Press return
key to return to
CONTROL Menu
, further pressing return
key to return
to Logo screen.
Control Menu: DELAYS
To configure the system
DELAYS
, access the
DELAYS
menu:
•
From the
CONTROL Menu
, highlight
DELAYS
option and then press the
✓
key in order to
gain access to it.
•
For Enabling of any set Zone Delays:
o
Use Left/Right arrow keys to move indicator between
OFF
and
ON
.
•
Press return
key to accept and return to
CONTROL Menu
, further pressing return
key to return to Logo screen.