6.
On the
Controller organizer
tab, select
Tasks
>
Main Task
>
MainProgram
>
Parameter and
local tags
. Select
Edit tags
, then add the name of the data structure on the
Data type
field.
7.
On the
Controller organizer
tab, select
Tasks
>
Main Task
>
MainProgram
>
MainRoutine
.
Add a COP module with the data structure.
8.
Section 6 PROFINET Telegram composition
The format of the PROFINET tags can be integer (2 bytes), unsigned integer (2 bytes) or float
(4 bytes).
The data transmission between the SC4500 controller and the PLC can have a maximum of 7 slots,
where each slot has a quantity of bytes used in the Telegram.
The size of data sent from the SC4500 controller to PLC is calculated with the input modules. The
size of data sent from PLC to SC4500 is calculated with the output modules.
The algorithm in the PROFINET module uses the rules that follow:
• The minimal number of slots are used.
• The byte modules are used from higher to lower without repetition. The modules available are
128 bytes, 64 bytes, 32 bytes, 16 bytes, 8 bytes, 4 bytes and 2 bytes.
• Because the module cannot be higher than 128 bytes and it cannot be repeated, there is one
module of 128 bytes for each slot.
• The maximum capacity of the Telegram is 768 bytes for input data and 128 bytes for output data.
38
English
Summary of Contents for SC4500
Page 1: ...DOC343 52 90752 PROFINET and EtherNet IP modules 11 2021 Edition 2 User manual...
Page 2: ......
Page 4: ...Table of Contents 2...
Page 6: ...Figure 1 Chain topology Figure 2 Star topology Figure 3 Ring topology 4 English...
Page 26: ...16 Select the option Go Online 17 Select Download 24 English...
Page 46: ...44 English...
Page 47: ......