5.2.2 Install the EtherNet/IP EDS file
An example of installation in Studio 5000 Logix Designer software from Rockwell Automation
Technologies Inc. follows:
Note: Steps that follow is an example. Steps and commands may change based on the installed PLC solution.
1.
Select
Tools
>
EDS hardware Installation Tool
.
2.
Follow the wizard instructions.
3.
In the wizard, select the option
Register and EDS file(s)
. Then, select
Register a single file
and
browse the downloaded ESD file.
4.
Complete the Wizard instructions.
When the file is installed, the SC4500 module is available in the
Controller organizer
view.