5.2.2 Install the EtherNet/IP EDS file

An example of installation in Studio 5000 Logix Designer software from Rockwell Automation
Technologies Inc. follows:

Note: Steps that follow is an example. Steps and commands may change based on the installed PLC solution.

1.

Select 

Tools

 > 

EDS hardware Installation Tool

.

2.

Follow the wizard instructions.

3.

In the wizard, select the option 

Register and EDS file(s)

. Then, select 

Register a single file

 and

browse the downloaded ESD file.

4.

Complete the Wizard instructions.

When the file is installed, the SC4500 module is available in the 

Controller organizer

 view.

10

   

English

Summary of Contents for SC4500

Page 1: ...DOC343 52 90752 PROFINET and EtherNet IP modules 11 2021 Edition 2 User manual...

Page 2: ......

Page 3: ...9 5 2 1 Install the PROFINET GSDML file 9 5 2 2 Install the EtherNet IP EDS file 10 5 3 Configure the PLC environment 11 5 3 1 Configure the PROFINET environment 11 5 3 2 Configure the EtherNet IP env...

Page 4: ...Table of Contents 2...

Page 5: ...Use of hazard information D A N G E R Indicates a potentially or imminently hazardous situation which if not avoided will result in death or serious injury W A R N I N G Indicates a potentially or imm...

Page 6: ...Figure 1 Chain topology Figure 2 Star topology Figure 3 Ring topology 4 English...

Page 7: ...ure the module on page 27 PROFINET or EtherNet IP on the controller Section 3 Installation D A N G E R Multiple hazards Only qualified personnel must conduct the tasks described in this section of the...

Page 8: ...Ethernet ports based on the network configuration For star topologies configure the controllers with 1 Ethernet port Refer to Figure 5 For chain or ring topologies configure the controller with 2 Ethe...

Page 9: ...connection The cable is a 4 wire shielded green colored cable that gives 100 Mbps Fast Ethernet minimum at 100 meters maximum The cables used in industrial networks are CAT 5 5E CAT 6 6A or CAT 7 cat...

Page 10: ...the options that follow based on the wiring configuration of the controller Option Description IEP only The two Ethernet ports are configured for PROFINET or EtherNet IP Port 2 in the module is enable...

Page 11: ...ed Automation portal from SIEMENS PLC software follows Note Steps that follow is an example Steps and commands may change based on the installed PLC solution 1 Select Options Manage general station de...

Page 12: ...commands may change based on the installed PLC solution 1 Select Tools EDS hardware Installation Tool 2 Follow the wizard instructions 3 In the wizard select the option Register and EDS file s Then s...

Page 13: ...g devices In the example the PLC industrial switch and SC4500 controller 2 Select Catalog Other field devices PROFINET IO I O Hach Lange Hach SC4500 controller The PROFINET catalog shows two SC4500 co...

Page 14: ...4 Assign the SC4500 controller to the PLC on the Network overview 5 On the Online and Diagnostic view select Assign IP address to set the IP address of the SC4500 controller 12 English...

Page 15: ...es information about the data sent through Telegram 7 On the PLC menu select Accessible devices view Then select Flash LED to identify the SC4500 controller with the installed module The controller di...

Page 16: ...lues to the PLC The controller continuously sends a simulation value in a loop from Minimum to Maximum during the set Period When the value gets the Maximum set value it decreases to the minimum and t...

Page 17: ...ned to see the information that the controller sends in simulation mode 13 Select Telegram composition to see Telegram information on the type of data integer or float and their relative address in th...

Page 18: ...ngs as in the Industrial Ethernet web page Refer to the table below Tags Type Size Slot Slot size Input address Address 1 Simulation_value Float Real 4 bytes Slot 1 8 bytes 68 75 ID68 2 Simulation_Tem...

Page 19: ...ure the EtherNet IP environment Configure the EtherNet IP Studio 5000 Logix Designer environment as follows 1 On the SC4500 controller go to the main menu Then select OUTPUTS EtherNet IP Adressing mod...

Page 20: ...et Period When the value gets the Maximum set value it decreases to the minimum and then again to maximum Error and Status values set on the controller are also sent to the PLC 4 Open or create a new...

Page 21: ...ct the HACH SC4500 Controllers then select Create The New module window shows 7 In the General section add a Name in the example the controller serial number and Description optional to identify the c...

Page 22: ...Connection section and configure the settings that follow Requested Packet Interval RPI Sets the PLC update rate in milliseconds Range 1 0 to 3200 0 Default 10 0 Very low values can flood the network...

Page 23: ...11 In a web browser type the IP address to access the Industrial Ethernet Interface web page 12 Select Modules assigned to see the information that the controller sends in simulation mode English 21...

Page 24: ...e of data integer or float and the Input Tag suffix 14 In the Studio 5000 Logix Designer environment on the Controller organizer tab select Tasks Main Task MainProgram Parameter and local tags Add the...

Page 25: ...le below Source Add the controller name then the I Data based on the bytes size Dest Add the parameter Tag Length Add the bit size of the Tag Tags Type Size I Data 1 Simulation_value Float Real 4 byte...

Page 26: ...16 Select the option Go Online 17 Select Download 24 English...

Page 27: ...18 Select Download 19 On the SC4500 controller go to the main menu Select OUTPUTS EtherNet IP Status to examine the connection condition English 25...

Page 28: ...b Monitor tags If the connection is successful the simulation data from the SC4500 controller shows 21 When the simulation is successful stop the simulation in the controller In the main menu of the c...

Page 29: ...am data in the controller to send sensor or device data to the PLC Refer to PROFINET Telegram composition on page 38 Configure the PROFINET settings as follows 1 Push the main menu icon then select Ou...

Page 30: ...cted Classified Error Classified Status 1 Dissolved oxygen mg L Heartbeat and Temperature C 4 Push OK then Save 5 In the PROFINET menu select Modules assigned The controller shows the slots informatio...

Page 31: ...dules assigned to see the information that the sensor sends 8 Select Telegram composition to see Telegram information on the type of data integer or float and their relative address in the PLC memory...

Page 32: ...he sensor values Add the same settings as in the Industrial Ethernet web page Refer to the table below Tags Type Size Slot Slot size Input address Address 1 LDO_Error Integer Uint 2 bytes Slot 1 8 byt...

Page 33: ...ss of the data structure 11 Select the option Monitor all in the popup menu in the Default table screen If the connection is successful the data from the SC4500 controller shows 5 4 2 Configure the Et...

Page 34: ...le devices Push OK 3 On the Telegram menu select the device Select Add tags For this example the tags that follow are selected Classified Error Classified Status 1 Dissolved oxygen mg L Heartbeat and...

Page 35: ...lect Module definition The controller shows the bytes data based on the selected Telegram tags 6 Go to the Industrial Ethernet Interface Home Page 7 Select Modules assigned to see the information that...

Page 36: ...he Input Tag suffix 9 In the Studio 5000 Logix Designer environment on the Controller organizer tab select Tasks Main Task MainProgram Parameter and local tags Add the tags based on the Telegram compo...

Page 37: ...sed on the bytes size Dest Add the parameter Tag Initial element to be overwritten by the source Lenght Number of destination elements to copy Tags Type Size I Data 1 LDO_Error Integer INT 2 bytes 0 2...

Page 38: ...der in the controller based on the variable type all float values first and then all of the integer values To configure the EtherNet IP module with a data structure do the steps that follow 1 Do steps...

Page 39: ...he data type is mixed in the Telegram composition the data structure will show an error in the PLC 5 In the Studio 5000 Logix Designer environment on the Controller organizer tab select Data Types Use...

Page 40: ...mum of 7 slots where each slot has a quantity of bytes used in the Telegram The size of data sent from the SC4500 controller to PLC is calculated with the input modules The size of data sent from PLC...

Page 41: ...le Input 4 bytes Tags assigned to this module tag 3 2 bytes and tag 4 2 bytes Slot 3 Module Input 2 bytes Tags assigned to this module tag 4 2 bytes Note Use the drag and drop function to change the e...

Page 42: ...data size is calculated based on the tags configured in the controller The output data size is the data sent from the PLC to the SC4500 The output data size is 0 bytes if there are no inputs selected...

Page 43: ...to Figure 9 on page 40 Figure 11 Industrial Ethernet Interface web page Section 8 LED status diagnostic and messages On the PLC put the system in Online mode and examine the status of the network On t...

Page 44: ...nt Comments Off Off The module has no power Off On Pending Waiting Ethernet Link Waiting Ethernet Link No ethernet cable connected to module Ethernet cable plugged on Port 2 in Mix IEP option On On Ru...

Page 45: ...accessories W A R N I N G Personal injury hazard Use of non approved parts may cause personal injury damage to the instrument or equipment malfunction The replacement parts in this section are approve...

Page 46: ...44 English...

Page 47: ......

Page 48: ...0 669 2932 orders hach com www hach com HACH LANGE GMBH Willst tterstra e 11 D 40549 D sseldorf Germany Tel 49 0 2 11 52 88 320 Fax 49 0 2 11 52 88 210 info de hach com www de hach com HACH LANGE S rl...

Reviews: