10.
On the
Controller organizer
tab, select
Tasks
>
Main Task
>
MainProgram
>
MainRoutine
.
For each Tag add a COP module with the data that follow (refer to the table bellow):
• Source—Add the controller name followed with the I.Data based on the bytes size.
• Dest—Add the parameter Tag. Initial element to be overwritten by the source.
• Lenght—Number of destination elements to copy.
Tags
Type
Size
I.Data
1 - LDO_Error
Integer (INT)
2 bytes
0
2 - LDO_Status
Integer
2 bytes
2
3 - LDO_Measurement_mgL
Float (Real)
4 bytes
4
4 - LDO_Heartbeat
Integer
2 bytes
8
5 - LDO_Temperature
Float
4 bytes
10
11.
Select the option
Go Online
.
12.
Select
Download
.
13.
Select
Download
.
English
35