PID control function
Option
Description
Error mode
Sets the controller to not change the analog output value (Hold) or show the transfer value
on the analog output when an internal error occurs. Options: Hold or Transfer
Mode
Sets the output condition when the process value is out of the controlled band. Options:
Direct control or Reverse
Mode
Automatic—The output works as a PID controller.
Manual—The output has got an on/off ratio as set in Manual output.
Manual output
Additionally the on/off ratio can be set (condition: Mode is set to Manual). Note that this ratio
cannot exceed a value beyond the values set in the Minimum and Maximum menus.
Minimum
Sets the lower limit for the output current. Default: 0.1 mA
Maximum
Sets an upper limit for the possible output current value. Default: 20.0 mA
Relay setpoint
Sets the process value which is controlled by the PID controller.
Dead zone
The dead zone is a band around the setpoint. In this band the PID controller does not
change the PWM on/off ratio output signal. This band is determined as se/- dead
zone. The dead zone stabilizes the PID controlled system which have a tendency to
oscillate.
Proportional
Sets the proportional part of the PID controller. Refer to
Configure the high voltage relays
on page 31.
Integral
Sets the integration part of the PID controller.
Derivative
Sets the derivative part of the PID controller.
Snap shot
Shows the snap shot value.
5.
Push OK to apply the changes.
6.
Push the main menu icon, then select Outputs > mA outputs > Test/Maintenance.
The Test/Maintenance menu lets the user do a test of the internal plug in the expansion cards.
7.
Select an option.
Option
Description
Function test
Does a test on the outputs on the selected module.
Output status
Shows the condition of the outputs on the selected module.
6.5.3 Configure the telegram
The industrial communication protocols usually operates with a cyclic transmission of data between
main (master) and secondary (slave) devices on a network. The controller uses Telegram for data
transmission. The content of the Modbus TCP telegram is the same as the Profibus telegram, the
PROFINET telegram and the EtherNet/IP telegram. Configure the telegram settings as follows:
1.
Push the main menu icon, then select Outputs > [output source] > Telegram.
2.
Select Add device. A list of available devices show.
3.
Select the devices to add to the telegram list and push OK.
4.
On the Telegram menu, select one device.
5.
Select Add tag. A list of available tags for the selected device shows.
6.
Select the tags to add to the device and push OK.
7.
Push SAVE.
8.
To remove a device from the telegram list, do the steps that follow:
a.
Go to Outputs > [output source] > Telegram
b.
Select - Delete device. A list of available devices shows.
38