Show the sample history
The sample history shows each sample that was collected, the time the sample was collected and if
the sample collection was completed or not. The reasons for the missed samples shows. The sample
history is automatically erased when the sampling program starts from the beginning.
1.
Push
MENU
.
2.
Select Review Data>Sample History.
3.
Select an option.
Option
Description
All
Samples
Shows the sample collection time, the sample number, the bottle number(s) and the sample
volume for each sample.
Missed
Samples
Shows the sample collection time, the sample number and the reason the sample was not
collected. The reasons that are given follow:
• Bottle Full—The sample was missed because a full bottle was detected.
• Rinse Error—The sample was missed because an error occurred during the rinse cycle.
• User Abort—The sample was missed because a user pushed the STOP key to end the
sample cycle.
• Arm Faulty—The sample was missed because the distributor arm did not move correctly.
• Pump Fault—The sample was missed because a fault occurred when the pump was
operating.
• Purge Fail—The sample was missed because an error occurred during the purge cycle.
• Sample Timeout—The sample was missed because liquid was not detected within the
timeout period.
• Pump Low Volt—The sample was missed because the power supply was not sufficient to
operate the pump.
• Low Flow—The sample was missed due to insufficient flow.
Show the measurement data
Show the measurement data to see the measurements recorded to the data log.
Note: Measurement data is recorded to the data log in accordance with the selected logging interval. Refer to
Configure data logging
on page 11.
1.
Push
MENU
and select Review Data>Measurement Data>[Select Instrument]>[Select
Measurement]. The selected measurements show in table format or graph format.
2.
To change the view, push
Options
, then select an option.
Option
Description
View Type
Changes the view to table format or graph format.
Zoom
Changes the view to one week, one day or one hour of measurements in graph view.
Note: This option is only available when the View Type setting is set to Graph.
Jump to newest
Shows the last measurement.
Jump to oldest
Shows the first measurement.
Jump to Date & Time
Shows the measurement recorded at the entered date and time.
3.
To erase the data log, push
MENU
and select General Settings>Clear Data. Select Data Log,
then push
Yes
.
Show the event log
Show the event log to see the events that occurred.
1.
Push
MENU
.
2.
Select Diagnostics>Event Log.
26
English
Summary of Contents for AS950 AWRS
Page 1: ...DOC346 53 80493 AS950 Controller 06 2016 Edition 8 Operations...
Page 2: ......
Page 35: ......