20
HST-M2 Ident.-No.: 12188
HST-M3 Ident.-No.: 12288
Position 1:
Switch key S1 locked by locking mechanism. Switch S2 is not pressed. Switch position ON
Position 0:
Switch key is unlocked and removed from S1. S2 button pressed. Switch position OFF
Attention:
Before starting up the following points
must be observed:
Check connections to all terminals for tight
connection! Tightening torque: min 0.6 Nm
/ max. 0.8 Nm
Installation housing or installation front
panel grounded at the central grounding
point about the existing blade terminal
connections.
No liability is accepted in the event of improper installation!
terminal block X1
terminal block X2
terminal block X3
==============
==============
==============
rated operating voltage: max. 500 V
terminals 21 / 22:
terminals 23 / 24:
rated operating current: max 20 A
+125 V / 0 V DC
AC max. 230 V / 1.5 A
rated surge voltage:
max 6 kV
DC max. 60 V / 0.5 A
or 24 V / 2 A