Lightning protection 

To protect the gateway from the lightning, make sure the following requirements are met: 

 

The grounding cable for the chassis is correctly grounded. 

 

The grounding terminal of the AC power receptacle is correctly grounded. 

 

If an AC power cord is routed from outdoors for connecting to the device, connect the power 
cord first to a power lightning arrester before connecting it to the power receptacle on the 
device. 

 

If a network cable is routed from outdoors for connecting to the device, connect the network 
cable first to a network port lightning arrester before connecting it to the port. 

 

 

IMPORTANT: 

  No network port lightning arrester or AC power lightning arrester is provided with the device. 

Purchase them as required. 

  For the technical specifications and installation instructions for the lightning arresters, see the 

documents shipped with them. 

 

Temperature 

 

CAUTION: 

If condensation appears on the chassis when you move it to a high-temperature environment, dry 
the chassis before powering it on to avoid short circuits. 

 

If the temperature in the equipment room is too high, too low, or changes dramatically, the device 
reliability is reduced and its service lifetime is shortened. 

High temperature can accelerate the aging of insulation materials and significantly lower the 
reliability and lifespan of the gateway. 

To ensure the correct  operation of the gateway,  make sure  the room temperature meets the 
requirements in 

Table

 2. 

Table 2 Temperature requirements 

Temperature 

Range 

Operating temperature 

0°C to 45°C (32°F to 113°F) 

Storage temperature 

–40°C to +70°C (–40°F to +158°F) 

 

Humidity 

Maintain appropriate humidity in your equipment room, as described i

Table

 3. 

 

Lasting high relative humidity tends to cause poor insulation, electricity leakage, mechanical 
property change of materials, and corrosion of metal parts.  

 

Lasting low relative humidity is likely to result in loose screws due to washer contraction, and 
even electrostatic discharge (ESD), which causes the circuits to fail. 

Table 3 Humidity requirements 

Humidity 

Range 

Operating humidity 

5% RH to 95% RH, noncondensing 

Summary of Contents for SecPath M9000-AI-E8

Page 1: ...tions 1 Electricity safety 1 Handling safety 1 ESD prevention 1 Laser safety 2 Examining the installation site 2 Weight support 2 Space 2 Cooling 3 Power 4 Lightning protection 5 Temperature 5 Humidit...

Page 2: ...ngrounded power extension cables missing safety grounds and wet floors Locate the emergency power off switch in the room before installation so you can quickly shut power off when an electrical accide...

Page 3: ...sure the floor can support the total weight of the rack chassis and accessories Additionally the floor loading plan must also consider system expansion such as adding more modules For more information...

Page 4: ...e screw of the fan tray at the chassis rear Figure 1 Rack dimensions Cooling The gateway uses front to rear airflow for heat dissipation Plan the installation site for the gateway based on its airflow...

Page 5: ...t voltage is stable and within the acceptable range allowed by the gateway Enough batteries are available to ensure uninterrupted device operation in the event of a power failure For the power supply...

Page 6: ...to a high temperature environment dry the chassis before powering it on to avoid short circuits If the temperature in the equipment room is too high too low or changes dramatically the device reliabi...

Page 7: ...ents as shown in Table 5 Table 5 Harmful gas limits in an equipment room Gas Max mg m 3 SO2 1 0 H2S 0 5 NH3 3 0 Cl2 0 3 NO2 1 0 EMI Electromagnetic interference EMI might be coupled from the source to...

Page 8: ...ies Pre installation checklist Table 6 Pre installation checklist Item Requirements Result Installation site Load bearing The floor or ground at the installation site can support the sum of the weight...

Page 9: ...rotective earthing systems of the communication power supplies use the same earthing conductor set with the protective earthing system of the communication devices Temperature 0 C to 45 C 32 F to 113...