5
Rack requirements
Table 1 Switch dimensions and rack requirements
Model
Switch dimensions
Rack requirements
S12516X-AF
•
Height
—931 mm (36.65 in) (21 RU)
•
Width
—440 mm (17.32 in)
•
Total depth
—977 mm (38.46 in)
{
857 mm (33.74 in) for the chassis
{
102 mm (4.02 in) from the rear side of the
mounting bracket front ear to the
management bracket front end
{
30 mm (1.18 in) for the fan tray handle at
the rear of the chassis
•
A minimum of 1.1 m (3.61 ft) in
depth (recommended.)
•
A minimum of 130 mm (5.12 in)
from the front rack post to the
front door.
•
A minimum of 950 mm (37.40
in) from the front rack post to
the rear door.
S12512X-AF
•
Height
—753 mm (29.65 in) (17 RU)
•
Width
—440 mm (17.32 in)
•
Total depth
—977 mm (38.46 in)
{
857 mm (33.74 in) for the chassis
{
102 mm (4.02 in) from the rear side of the
mounting bracket front ear to the
management bracket front end
{
30 mm (1.18 in) for the fan tray handle at
the rear of the chassis
S12508X-AF
•
Height
—531 mm (20.91 in) (12 RU)
•
Width
—440 mm (17.32 in)
•
Total depth
—977 mm (38.46 in)
{
857 mm (33.74 in) for the chassis
{
102 mm (4.02 in) from the rear side of the
mounting bracket front ear to the
management bracket front end.
{
30 mm (1.18 in) for the fan tray handle at
the rear of the chassis
S12504X-AF
•
Height
—264 mm (10.39 in) (6 RU)
•
Width
—440 mm (17.32 in)
•
Depth
—977 mm (38.46 in) when the
LSXM104XFAN fan trays are installed
{
857 mm (33.74 in) for the chassis
{
102 mm (4.02 in) from the rear side of the
mounting bracket front ear to the
management bracket front end
{
30 mm (1.18 in) for the fan tray handle at
the rear of the chassis
•
Depth
—1016 mm (40 in) when the
LSXM104XFANH fan trays are installed
{
857 mm (33.74 in) for the chassis
{
102 mm (4.02 in) from the rear side of the
mounting bracket front ear to the
management bracket front end
{
69 mm (2.72 in) for the fan tray handle at
the rear of the chassis
NOTE:
As a best practice, use a rack that has a single door at the front.