2-1
2
Installing the device in a rack
Device dimensions
Figure 2-1 Device dimensions
(1) Power supply handle
(2) Mounting bracket
(3) Cable management bracket
Rack requirements
Table 2-1 Rack requirements
Device dimensions
Rack requirements
•
Height
—133 mm (5.24 in) (3 RU).
•
Width
—440 mm (17.32 in).
•
Chassis depth
—895 mm (35.24 in)
•
Total depth
—1013 mm (39.88 in)
104 mm (4.09 in) from the rack-facing
surface of the mounting brackets to the
front ends of the cable management
brackets
909 mm (35.79 in) from the rack-facing
surface of the mounting brackets to the
power supply handles at the chassis rear
•
A minimum of 1.1 m (3.61 ft) in depth
(recommended)
•
A minimum of 130 mm (5.12 in) from the front
rack post to the front door
•
A minimum of 950 mm (37.40 in) from the front
rack post to the rear door
NOTE:
As a best practice, use a rack that has a single door at the front.
133 mm
(5.24 in)
28 mm
(1.1 in)
909 mm
(35.79 in)
104 mm
(4.09 in)
2
3
1
14 mm
(0.55 in)