105
Expert Power Control 8041/8045
© 2022 GUDE Systems GmbH
Specifications
Device Resource
Start
End
Function
Bank Power Source
0x000
0x00f
Sets Power Source for Bank
Fan Mode
0x010
0x01f
0 = Automatic / 1 = Maximum
Device Identification
Returns manufacturer name and device identification:
Request Code
1 Byte
0x2b
MEI Type
1 Byte
0x0e
Read Dev ID code
1 Byte
0x01
Object Id
1 Byte
0x00
Response Code
1 Byte
0x2b
MEI Type
1 Byte
0x0e
Read Dev ID code
1 Byte
0x01
Conformity Level
1 Byte
0x01
More Follows
1 Byte
0x00
NextObjectID
1 Byte
0x00
Number of Objects
1 Byte
0x03
Object ID
1 Byte
0x00
Object Length
1 Byte
n1
Object Value
n1 Bytes
"Company Id"
Object ID
1 Byte
0x00
Object Length
1 Byte
n2
Object Value
n2 Bytes
"Product Id"
Object ID
1 Byte
0x00
Object Length
1 Byte
n3
Object Value
n3 Bytes
"Product Version"
4.9.1
Sensor Tables
Important
: All calculations in this chapter are based on addresses starting at "0".
With some Modbus TCP utilities the addresses start at 1. In this case a 1 must be ad-
ded to the addresses in this chapter. Please try both possibilities for tests!
External sensors addresses (Input Register)
Sensor field
Port 1
Port 2
Temperature
0x100
0x108
Humidity
0x101
0x109
Digital input
0x102
0x10a
Air Pressure
0x103
0x10b
Dew Point
0x104
0x10c
Dew Point Difference
0x105
0x10d