102
Expert Power Control 8041/8045
© 2022 GUDE Systems GmbH
Specifications
0
16-bit
Number of Ports (Relay)
1
16-bit
Number of Ports (Outlets) with
Energy Measurement
2
16-bit
Number of Banks
3
16-bit
Number of Line-In
4
16-bit
Phases per line
5
16-bit
Number of Inputs
Sensor Type Description
Address
Width
Information
0x080 to 0x083
16-bit (signed
CPU Sensor values
0x100 to 0x1ff
16-bit (signed)
external Sensors
0x400 to 0x39ff
32-bit (signed)
Line Energy Sensors
0x3a00 to 0x81ff
32-bit (signed)
Port Energy Sensors
0x8200 to 0x823f
16-bit (signed)
Bank Energy Sensors
0x8240 to 0x827f
16-bit (signed)
Power Source Energy Sensors
0x8280 to 0x82cf
16-bit (signed)
Residual Current Monitor
CPU Sensor Values
Offset
Sensor Field
Unit
0
Vsystem
0.01 V
1
Vaux
0.01 V
2
Vmain
0.01 V
3
CPU Temperature
0.1 °C
External Sensors:
The measured value of the external sensors are coded as fixed point arithmetic. For a
factor of e.g. 0.1 in the unit the value must be divided by 10 in order to reach the real
measured value. A value of 0x8000 means that no sensor is plugged into the corres-
ponding port, or the corresponding field in the sensor is not available. The formula for the
address is (the port numbers start at zero):
0x100 + Port * 8 + Offset
In the Expert Sensor Box 7213 / 7214 the internal sensor corresponds to the value
Port = 0, and is coded Port = 1 for Sensor 2 and Port = 2 for Sensor 3.
Offset
Sensor Field
Unit
0
Temperature
0.1 °C
1
Humidity
0.1 %
2
Digital Input
bool
3
Air Pressure
1 hPa (millibar)
4
Dew Point
0.1 °C
5
Dew Point Difference
0.1 °C
For example, the humidity of the second port has the address: 0x100 + 1 * 8 + 1 =
0x109