9
3 Installation
3. 1 Unpacking Inspection
1. Open the packing box of UPS and take it out, visually examine the unit
for transit damage.
2. Check against the accessory lists that the accessories of the UPS are
present. (Refer to Table 9-1).
3. Make sure the model is what you wanted from the nameplate on the rear
panel
4. If the UPS arrives damaged, or there is any missing accessory or other
question above, please contact the distributor immediately.
3. 2 Installation Notes
1. When locating the UPS, make sure there is no hazardous objects such as
water, inflammable gas, corrosive agents and so on around the UPS, and
that the installation environment meets the specifications.
2. The UPS should not be placed on a side. The air inlet port at the front
panel and the outlet port on the rear panel and two side panels should not
be blocked so as to ensure good ventilation.
3. In case if the UPS is unpacked, installed and used at very low
temperatures, condensations of water drops may appear. It is necessary
to wait until the UPS fully dried inside out before proceeding to
installation and use. Otherwise, they may be a risk of electric shock.
4. Place the UPS near the utility power source outlet which supplies power
to the UPS. In any emergency, switch off the main input socket, cut off
the battery voltage input. All power sockets must be connected with
ground protection.
10
3. 3 Cable Connection
3.3.1 Connecting Input and Output Cables
1. Input cable connection
If the UPS is connected via the power cable, please use a proper socket
with over current protection, and pay attention to the capacity of the
socket: over 10A for ZS110-1K(-KS), over 16A for ZS110-2K(-KS) and
ZS110-3K(-KS). A side of input wiring has been fixed with the UPS, and
the other side is just need to plug into the input socket. The wiring
configuration is shown in the following diagram.
Figure 3-1 Connection Method of Input
2. Output cable connection
The output of ZS110-1K(-KS)/ ZS110-2K(-KS)/ ZS110-3K(-KS) all
available to uses sockets. The total output power shall not exceed
1kVA/0.8kW, 2kVA/1.6 kW
,
3kVA/2.4 kW. Simply plug the load power
cable to the output sockets of UPS to complete connection as shown in
the following diagram.