NS3000 Series User Manual    rev.01 

8.2 Environmental Characteristics ...................................................................................................................... 46

 

Table 8-2 ........................................................................................................................................................... 46

 

8.3 Mechanical Characteristics ........................................................................................................................... 46

 

8.4 Electrical Characteristics (Input Rectifier)..................................................................................................... 47

 

8.5 Electrical Characteristics (Intermediate DC Link).......................................................................................... 47

 

8.6 Electrical Characteristics (Inverter Output).................................................................................................... 48

 

8.7 Electrical Characteristics(Bypass Mains Input).............................................................................................. 49

 

8.8 Efficiency .................................................................................................................................................... 49

 

-

8

NS3000 Series User Manual    rev.01 

Chapter 1 Quick Start 

1.1 Introduction 

This

 

chapter introduces the basic principles for UPS installation and debugging, so that personal service can install 

and debug UPS quickly. 

1.2 Initial Checking 

Perform the following checking operations prior to the UPS installation. 

1. 

Visually examine if there is any damp, water, or damage inside and outside the UPS packing, products and battery 

equipments due to the transportation. Report any such damage to the shipper immediately. 

2. 

Verify the product label and confirm the correctness of the equipment. The equipment label is attached on the panel 

behind front door. The UPS model, capacity and main parameters are marked on the label. 

3. 

Verify correctness of the accessories. If there is any mistake for accessories, contact with shipper or provider. 

1.3 Environment Checking 

        Before installing UPS, please check these items as below: 

1.  Is the UPS operation environment temperature above 25°C? If so, please add cooling equipments. 

Note: Environment temperature above 20°C, battery life will reduce to half when environment    temperature 

rise each 10°C. 

2.  Is the UPS operation environment temperature below 0°C? If so, please add heaters. 

3.  Is  the  UPS  operation  environment  humidity  is  above  90%  Is  there  any  condensing?  If  so,  please  add  additional 

protection. 

4.  In the UPS operation environment, is there any sunshine shining in directly or life-form coming in? If so, please add 

additional protection. 

5.  In  the  UPS  operation  environment,  is  there  any  dust,  combustible  or  explosive  gas?  If  so,  please  add  additional 

protection. 

1.4 Installation Checking 

After finishing installation, please check these items as below: 

1.  Is UPS installed on the flame-retardant materials? 

2.  Are all cables connected exactly? 

3.  Are all grounded system connected according to the manual? 

4.  Is there enough operation space around UPS? 

5.  Please confirm all UPS external terminals are fastened, the moment should meet requirements. 

6.  Please confirm that there are no screws, cables and other conductor left in the UPS. If there is, please take out. 

Summary of Contents for NS3000 10 kVA

Page 1: ...1 NS3000 Series User Manual Rev 01 UPS NS3000 10 20 30kVA USER Manual 2 NS3000 Series User Manual Rev 01...

Page 2: ...te the static switch if excessive voltage is present at the bypass input when the bypass source is deenergized If this function is not installed and enabled there must be a warning label on the extern...

Page 3: ...al rev 01 3 2 3 Auto Restart Mode 29 3 2 4 Bypass Mode 29 3 2 5 Maintenance Mode 29 3 2 6 ECO Mode 29 3 2 7 Frequency Converters Mode 29 3 2 8 Parallel connection redundancy mode 30 3 3 Battery Manage...

Page 4: ...s any mistake for accessories contact with shipper or provider 1 3 Environment Checking Before installing UPS please check these items as below 1 Is the UPS operation environment temperature above 25...

Page 5: ...sary a system of extractor fans should be installed to aid cooling air flow An air filter should be used when the UPS is to operate in a dirty environment and should be regularly cleaned to maintain a...

Page 6: ...l Against ambient corrosive gases l Against excessive humidity and heat sources l Against dust l With the current fire prevention requirements l The operating environment temperature is within 20 25...

Page 7: ...supply the installed device should l Sensitive to DC Class B or class A in the network l Insensitive to transient current pulses l Have an average sensitivity that is adjustable between 0 3A 1A 14 NS3...

Page 8: ...epartment After the equipment has been finally positioned and secured connect the power cables as described in the following procedures 1 Verify that all the external input distribution switches of th...

Page 9: ...2 5 A Pay attention all cable are marked and have different color 6 Connect the battery according fig 2 5 A don t connect A and B cable in the shelf 1 7 In shelf 1 on the left connect the cable mark...

Page 10: ...d be double insulated with a typical 0 5 to 1 5 mm 2 cross section area for a maximum connection length between 25 and 50 meters 2 6 1 Dry Contact Interface of Battery and Environmental Temperature De...

Page 11: ...Note 1 The emergency stop action within the UPS will shut down the rectifier inverter and static bypass However it does not internally disconnect the mains input and batterypower supply To disconnect...

Page 12: ...neral warning dry contact interface diagram Table 2 7 Position Name Purpose J9 1 ALARM_NC Integrated warning relay normally closed will be open during warning J9 2 ALARM_NO Integrated warning relay no...

Page 13: ...25 NS3000 Series User Manual rev 01 2 7 Installation Diagram 26 NS3000 Series User Manual rev 01 a 10KVA 30KVA terminal block NS3030 NS3010 NS3020...

Page 14: ...ss module can be removed for maintenance Fig 3 1 System principle framework 28 NS3000 Series User Manual rev 01 3 1 2 Bypass During normal system operation the load is connected to the inverter but in...

Page 15: ...e output frequency The range of output frequency is 40Hz 70Hz Under this mode static bypass is unavailable but battery can be selected according to the actual requirements of battery mode Frequency Co...

Page 16: ...4 1 Typical 1 N parallel operation system Note when the load exceeds the capacity of the single device we recommended an external manual Bypass The cables for the parallel operation provide double in...

Page 17: ...Warning Please confirm that UPS output rotating switch point to UPS with anti misoperation stop plate for rotating switch is fixed well 1 Close UPS bypass input switch and input switch in turns The LC...

Page 18: ...aution Before making this operation read messages on display to be sure that bypass supply is regular and the inverter is synchronous with it so as not to risk a short interruption in powering the loa...

Page 19: ...chapter introduces the functions and operation instructions of the parts on UPS operator control and display panel in detail and provides LCD display information including LCD display types detailed...

Page 20: ...tus indicator Steady red Failure 6 1 2 Audible Alarm buzzer There are two different types of audible alarm during UPS operation as shown in table 6 3 Table 6 3 Description of audible alarm Alarm Purpo...

Page 21: ...rface you can select each function and press ENTER press ENTER again it will display Confirm interface 6 2 5 State Display The alarm page as below press left and right arrow to select STA in homepage...

Page 22: ...inverted power supply status Bypass power supply The system is in bypass power supply status No power supply System no output Battery equalized charging Battery is in boost charging Battery float char...

Page 23: ...hows the power is normally supply by the bypass 8 Open maintenance bypass switch and close mains input switch the inverter automatically starts and UPS operates in the normal mode after 60 seconds 9 C...

Page 24: ...harge V cell 2 4V cell selectable from 2 3V cell 2 45V cell Constant current and constant voltage charge mode Battery Charging Power Max Current kW 10 UPS capacity selectable from 0 20 UPS capacity NS...

Page 25: ...eutral cable A 1 7 In Frequency2 Hz 50 60 Switch time between bypass and inverter ms Synchronized switch 1ms Bypass voltage tolerance Vac Upper limit 10 15 or 20 default 20 Lower limit 10 20 30 or 40...

Reviews: