background image

-

15

NS3000 Series User Manual    rev.01 

2.4.3 Battery 

A battery string is composed of 40 batteries connected in series, maximum is possible install 2 strings 40batteries (B1-B2 

in  this document). The  positive,  the negative  and  middle point (the joint  part between the  20th and 21st battery) cable 

must push through a DC circuit breaker before connecting to corresponding UPS . For detailed wiring please refers to fig 

2-4 below: 

 

 

 

Fig 2-4 Diagram of batteries connected in series 

2.4.3 UPS Output 

A main output switch has been installed in UPS; the user shall install the overcurrent protective device on the bypass 

and on each output of the external distribution cabinet. 

2.5 Power Cables 

Design  the  cables  according  to  the  descriptions  in  this  section  and  local  regulatory  wiring  standards,  and  the 

environmental conditions should be taken into consideration. Refer to IEC60950-1 table 3B.

 

  Warning 

Prior cabling the UPS, confirm the status and positions of the switches of the UPS rectifier input 

power supply / bypass power supply and mains power distribution board. 

Ensure that these switches are opened and attached with WARNING label so as to prevent 

unauthorized operation to these switches.

 

2.5.1 Maximum stable state current and configuration of minimum cable system 

Table 2-1   

Model Name 

 

NS3010 

NS3020 

NS3030 

 

UPS Power 

10KVA 

20KVA 

30KVA 

Rated current A 

15A 

30A 

45A 

Main Input 

Cable mm2 

10 

Rated current A 

15A 

30A 

45A 

Output 

Cable mm2 

10 

Rated current A 

18A 

36A 

53A 

Battery 

Cable mm2 

10 

16 

PE 

Cable mm2 

10 

10 

 

Forty batteries in series connection in total 

Batt + 

Batt-

Batt - N 

Batt + 

Batt - 

B1 + series

 

B1 - series

 

-

16

NS3000 Series User Manual    rev.01 

  Warning 

FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES CAN RESULT IN EMI, ELECTRIC 

SHOCK HAZARD OR RISK OF FIRE, SHOULD AN EARTH FAULT OCCUR.

 

2.5.2 Cable Connection 

Important   

The operations described in this section must be performed by authorized electricians or qualified 

technical personnel.. If you have any difficulties, do not hesitate to contact our Customer Service & 

Support department .

 

After the equipment has been finally positioned and secured, connect the power cables as described in the following 

procedures: 

1. 

Verify that all the external input distribution switches of the UPS are completely opened (off position) and the UPS 

internal  maintenance  bypass  switch  is  opened.  Attach  necessary  warning  signs  to  these  switches  to  prevent 

unauthorized operation. 

2. 

Open the door of the cabinet, remove the left bottom cover and then the input and output terminal, battery terminal 

and earth terminal are visible. 

3. 

Connect the input earth wire to input earth terminal. Please note: the earth wire shall be connected in accordance 

with related local or state regulation 

4. 

If in UPS, same electric supply input is used for the by-pass and main input AC input cables should be connected 

with the input terminal of UPS (Main input    L1ma – L2mb – L3mc 

and the output load cables are connected 

with the output terminal of UPS 

(Output L1oa - L2oA - L3oC). If in UPS, two electric supply inputs are used for 

the rectifier and by-pass, the AC input cables should be respectively connected with the main input terminal of UPS 

(Main input L1ma - L2mb – L3mc 

and the input terminal of the bypass,L1ba,L2bb,L3bc and the short circuit 

copper bars between the main circuit and the bypass have to be removed; fastening moment of force is 

30kg(M5), 50kg(M6), 180kg(M8). Attention is given to phase sequence and the short circuit at a joint between cable 

terminals. If the phase sequence is wrong UPS show an alarm 

5. 

Connect the battery cables between the UPS battery terminals and battery switch. 

ENSURE CORRECT Polarity.

 

 

  Warning-Hazardous battery terminal voltage 

400Vdc 

The operations described in this section must be performed by authorized electricians or qualified 

technical personnel. 

Ensure the correct polarity connection between the battery terminals and the UPS terminals: Positive 

terminal to positive terminal, negative terminal to negative terminal, The middle poin of the batteies is 

Neutral point in the UPS. 

Disconnect in the tray 1 and tray 5 the cable marked A and B. Do not connect the cables and close 

the battery circuit breakers before getting the approval from the commissioning engineer. 

6. 

Re-install all the protective covers. 

Summary of Contents for NS3000 10 kVA

Page 1: ...1 NS3000 Series User Manual Rev 01 UPS NS3000 10 20 30kVA USER Manual 2 NS3000 Series User Manual Rev 01...

Page 2: ...te the static switch if excessive voltage is present at the bypass input when the bypass source is deenergized If this function is not installed and enabled there must be a warning label on the extern...

Page 3: ...al rev 01 3 2 3 Auto Restart Mode 29 3 2 4 Bypass Mode 29 3 2 5 Maintenance Mode 29 3 2 6 ECO Mode 29 3 2 7 Frequency Converters Mode 29 3 2 8 Parallel connection redundancy mode 30 3 3 Battery Manage...

Page 4: ...s any mistake for accessories contact with shipper or provider 1 3 Environment Checking Before installing UPS please check these items as below 1 Is the UPS operation environment temperature above 25...

Page 5: ...sary a system of extractor fans should be installed to aid cooling air flow An air filter should be used when the UPS is to operate in a dirty environment and should be regularly cleaned to maintain a...

Page 6: ...l Against ambient corrosive gases l Against excessive humidity and heat sources l Against dust l With the current fire prevention requirements l The operating environment temperature is within 20 25...

Page 7: ...supply the installed device should l Sensitive to DC Class B or class A in the network l Insensitive to transient current pulses l Have an average sensitivity that is adjustable between 0 3A 1A 14 NS3...

Page 8: ...epartment After the equipment has been finally positioned and secured connect the power cables as described in the following procedures 1 Verify that all the external input distribution switches of th...

Page 9: ...2 5 A Pay attention all cable are marked and have different color 6 Connect the battery according fig 2 5 A don t connect A and B cable in the shelf 1 7 In shelf 1 on the left connect the cable mark...

Page 10: ...d be double insulated with a typical 0 5 to 1 5 mm 2 cross section area for a maximum connection length between 25 and 50 meters 2 6 1 Dry Contact Interface of Battery and Environmental Temperature De...

Page 11: ...Note 1 The emergency stop action within the UPS will shut down the rectifier inverter and static bypass However it does not internally disconnect the mains input and batterypower supply To disconnect...

Page 12: ...neral warning dry contact interface diagram Table 2 7 Position Name Purpose J9 1 ALARM_NC Integrated warning relay normally closed will be open during warning J9 2 ALARM_NO Integrated warning relay no...

Page 13: ...25 NS3000 Series User Manual rev 01 2 7 Installation Diagram 26 NS3000 Series User Manual rev 01 a 10KVA 30KVA terminal block NS3030 NS3010 NS3020...

Page 14: ...ss module can be removed for maintenance Fig 3 1 System principle framework 28 NS3000 Series User Manual rev 01 3 1 2 Bypass During normal system operation the load is connected to the inverter but in...

Page 15: ...e output frequency The range of output frequency is 40Hz 70Hz Under this mode static bypass is unavailable but battery can be selected according to the actual requirements of battery mode Frequency Co...

Page 16: ...4 1 Typical 1 N parallel operation system Note when the load exceeds the capacity of the single device we recommended an external manual Bypass The cables for the parallel operation provide double in...

Page 17: ...Warning Please confirm that UPS output rotating switch point to UPS with anti misoperation stop plate for rotating switch is fixed well 1 Close UPS bypass input switch and input switch in turns The LC...

Page 18: ...aution Before making this operation read messages on display to be sure that bypass supply is regular and the inverter is synchronous with it so as not to risk a short interruption in powering the loa...

Page 19: ...chapter introduces the functions and operation instructions of the parts on UPS operator control and display panel in detail and provides LCD display information including LCD display types detailed...

Page 20: ...tus indicator Steady red Failure 6 1 2 Audible Alarm buzzer There are two different types of audible alarm during UPS operation as shown in table 6 3 Table 6 3 Description of audible alarm Alarm Purpo...

Page 21: ...rface you can select each function and press ENTER press ENTER again it will display Confirm interface 6 2 5 State Display The alarm page as below press left and right arrow to select STA in homepage...

Page 22: ...inverted power supply status Bypass power supply The system is in bypass power supply status No power supply System no output Battery equalized charging Battery is in boost charging Battery float char...

Page 23: ...hows the power is normally supply by the bypass 8 Open maintenance bypass switch and close mains input switch the inverter automatically starts and UPS operates in the normal mode after 60 seconds 9 C...

Page 24: ...harge V cell 2 4V cell selectable from 2 3V cell 2 45V cell Constant current and constant voltage charge mode Battery Charging Power Max Current kW 10 UPS capacity selectable from 0 20 UPS capacity NS...

Page 25: ...eutral cable A 1 7 In Frequency2 Hz 50 60 Switch time between bypass and inverter ms Synchronized switch 1ms Bypass voltage tolerance Vac Upper limit 10 15 or 20 default 20 Lower limit 10 20 30 or 40...

Reviews: