operAtion
14
ADICOS GTL-3
430-2410-102 EN11
7 Operation
7.1 Testing fire gas detector GSME
1
Press the GTL-3 test device with the gas funnel
against the front of the detector until an alarm is
indicated.
In order to receive detailed information about the
sensor status the total dest duration is two min
-
utes per detector..
2
Remove gas funnel from detector
3
After the last test,
it is essential to extinguish the
GTL-3 smouldering sticks
and switch off the fan (–›
Chap. 7.2, Set fan unit out of operation).
7.2 Set fan unit out of operation
►
Slide the operating switch in direction ‘OFF’.
NOTICE!
The GTL-3 smouldering rod can cause fires if left unattended.
• Always extinguish GTL-3 smouldering sticks after the last test!
Delete GTL-3 smouldering sticks
1
Open the device
2
Loosen knurled nut
3
Remove glowing GTL-3 smouldering sticks carefully and extinguish with water
Alternatively:
Break off the glowing end of the GTL-3 smouldering rod generously and extinguish with
water