C
Low Voltage Cable Specifications
Using the correct cables when installing your system ensures maximum performance.
The following requirements apply to the following low voltage devices unless otherwise stated:
• Sensor cables
• Potentiometer cables
• Communication cables
• All other low voltage devices
Table C-1
Low voltage cable specifications
Item
Description
Cable type
Twisted and shielded
Minimum gauge
1 mm
2
(18 AWG)
Maximum sensor cable length (including any
cable extension)
150 m (500 feet)
When extending a cable (see figure below):
• solder all joints (2)
• use heat shrink tubing
• do not connect ground wire, cut it (1)
Figure C-1
Soldering the joints when extending a cable
0 0 0
0
0
0
0
0
0
0
0
1
2
1
895–00677
Agri Alert 128 Touch
101
Summary of Contents for Agri-Alert 128 Touch
Page 14: ...NOTES 14 895 00677 Agri Alert 128 Touch...
Page 20: ...NOTES 20 895 00677 Agri Alert 128 Touch...
Page 30: ...NOTES 30 895 00677 Agri Alert 128 Touch...
Page 38: ...NOTES 38 895 00677 Agri Alert 128 Touch...
Page 44: ...NOTES 44 895 00677 Agri Alert 128 Touch...
Page 64: ...Chapter 9 Configuring a 0 5 Volt Zone Type 64 895 00677 Agri Alert 128 Touch...
Page 66: ...NOTES 66 895 00677 Agri Alert 128 Touch...
Page 82: ...NOTES 82 895 00677 Agri Alert 128 Touch...
Page 88: ...NOTES 88 895 00677 Agri Alert 128 Touch...
Page 92: ...NOTES 92 895 00677 Agri Alert 128 Touch...
Page 96: ...NOTES 96 895 00677 Agri Alert 128 Touch...
Page 100: ...NOTES 100 895 00677 Agri Alert 128 Touch...
Page 102: ...NOTES 102 895 00677 Agri Alert 128 Touch...
Page 106: ...NOTES 106 895 00677 Agri Alert 128 Touch...
Page 107: ...F Wiring Diagram with Terminals 895 00677 Agri Alert 128 Touch 107...
Page 110: ...NOTES 110 895 00677 Agri Alert 128 Touch...
Page 118: ......