ECOTRONIC tech
Cod. 3540V010 - 07/2010 (Rev. 00)
106
EN
Service menu
The regulator Service Menu is accessed by pressing the Info button for 10 seconds. Press the
/
buttons to
select “tS”, “In”, “Hi” or “rE”. "tS" means Transparent Parameters Menu, "In" Information Menu, "Hi" History Menu,
and "rE" History Menu Reset. After selecting the Menu, press the Info button to access it.
"tS" - Transparent Parameters Menu
The regulator has 26 editable transparent parameters:
Card
Description of Transparent Parameters
Range
Default
P01
System setting
(0=Basic System, 1=System 1, 2=System 2, 3=System 3, 4=System 4)
0–4
0
P02
Activation temperature differential (°C)
1–20°C
6°C
P03
Deactivation temperature differential (°C)
1–20°C
4°C
P04
Tank max. temperature (°C)
20–95°C
60°C
P05
Collector limit temperature (°C)
110-160°C
140°C
P06
System cooling parameter (0=Off, 1=On)
0-1
1=On
P07
System cooling function activation collector temperature (°C)
100–150°C 120°C
P08
Collector min. limitation parameter (0=Off, 1=On)
0–1
0=Off
P09
Collector min. temperature (°C)
10–90°C
10°C
P10
Antifreeze protection function parameter (0=Off, 1=On)
0–1
0=Off
P11
Antifreeze temperature (°C)
0–10°C
4°C
P12
Tank cooling parameter (0=Off, 1=On)
0–1
0=Off
P13
Thermostat activation temperature (°C)
0–95°C
40°C
P14
Thermostat deactivation temperature (°C)
0–95°C
45°C
P15
Thermal Quantity Balance parameter (0=Off, 1=On)
0–1
0=Off
P16
Solar circuit max.
fl
ow rate (l/min)
0–20
6 l/min
P17
Not implemented
0
0
P18
Antifreeze liquid protection rating (%)
0-50%
25%
P19
Solar Circulating Pump output operation mode
(0=OFF continuous, 1=auto and 2=ON continuous)
0-2
1=Auto
P20
FREE CONTACT relay operation mode
(0=OFF continuous, 1=auto, 2=ON continuous, 3=Boiler activation/deactivation)
0-3
1=Auto
P21
Minimum - Solar Circulating Pump modulation temperature differential
(°C)
5-20°C
10°C
P22
Solar Circulating Pump modulation temperature differential (°C)
2-20°C
5°C
P23
Solar Circulating Pump operation (0=On/Off, 1=Modulating)
0-1
0
P24
Hot water tank limit temperature (°C)
70-95°C
80°C
P25
Flowmeter type selection (0=Operation without
fl
owmeter, 1=DN8,
2=DN10, 3=DN15, 4=DN20, 5=DN25)
0-5
0
P26
Operation type selection (DO NOT MODIFY)
0-1
1
Press the Up/Down buttons to scroll the list of parameters, in increasing or decreasing order respectively. To
change the value of a parameter just press the Enter button in relation to the parameter and then modify the
parameter with the Up/Down buttons: the change will be automatically saved.
Press the Enter button to return to the list of parameters.
Press the Info button to return to the Service Menu. Press the Info button for 10 seconds to exit the Service Menu
or exiting is automatic after 15 minutes.
Summary of Contents for ECOTRONIC tech
Page 6: ...ECOTRONIC tech IT Cod 3540V010 07 2010 Rev 00 6 Dimensioni ...
Page 43: ...ECOTRONIC tech 43 Cod 3540V010 07 2010 Rev 00 ES Medidas ...
Page 81: ...ECOTRONIC tech 81 Cod 3540V010 07 2010 Rev 00 EN Dimensions ...
Page 118: ...ECOTRONIC tech Cod 3540V010 07 2010 Rev 00 118 Dimensions FR ...
Page 155: ...ECOTRONIC tech 155 Cod 3540V010 07 2010 Rev 00 NL Afmetingen ...
Page 192: ......