English (GB)
40
14.17.1 Setpoint influence
The table below gives an overview of the types of setpoint
influence and the availability depending on pump type.
You can select these functions:
• Not active
When set to "Not active", the setpoint will not be influenced
from any external function.
•
Linear function
The setpoint is influenced linearly from 0 to 100 %. See fig.
Fig. 61
Linear function
• "Linear with Stop" and "Linear with Min."
– Linear with Stop
In the input signal range from 20 to 100 %, the setpoint is
influenced linearly.
If the input signal is below 10 %, the pump will change to
operating mode "Stop".
If the input signal is above 15 %, the operating mode will be
changed back to "Normal". See fig.
– Linear with Min.
In the input signal range from 20 to 100 %, the setpoint is
influenced linearly.
If the input signal is below 10 %, the pump will change to
operating mode "Min.".
If the input signal is increased above 15 %, the operating
mode will be changed back to "Normal". See fig.
Fig. 62
"Linear with Stop" and "Linear with Min."
• Linear with Min.
The setpoint is influenced inversely from 0 to 100 %.
See fig.
.
Fig. 63
Linear with Min.
Setpoint influence
Pump type
TPE3
TPE3 D
TPE2
TPE2 D
Not active
●
●
Linear function
●
●
Linear with Stop
-
●
Linear with Min.
●
●
Inverse function
-
●
Inverse with Stop
-
●
Inverse with Min.
-
●
Influence table
-
●
Influence table with Stop at Min.
-
●
Influence table with Stop at Max.
-
●
TM
06 41
66 161
5
100
0
100 %
0
3.5 V
0.5
5 V
0
10 V
0
20 mA
0
20 mA
4
-50
204 C
Setpoint influence [%]
External input
TM
06
41
67
16
15
T
M
06
41
68
16
15
100
0
20
100 %
0
3.5 V
0.5
5 V
0
10 V
0
20 mA
0
20 mA
4
-50
204 C
Setpoint influence [%]
External
input
Normal
Min. or
Stop
100
0
100 %
0
3.5 V
0.5
5 V
0
10 V
0
20 mA
0
20 mA
4
-50
204 C
Setpoint influence [%]
External input