11. Standard control panel
This control panel is fitted as standard on TPE2, TPE2 D pumps.
Fig. 26
Standard control panel
11.1 Setpoint setting
Set the desired setpoint of the pump by pressing
or
. The
light fields on the control panel will indicate the setpoint set.
11.1.1 Pump in differential-pressure control mode
The following example applies to a pump in an application where
a pressure sensor gives a feedback to the pump. If you retrofit the
sensor to the pump, set it up manually as the pump does not
automatically register a connected sensor.
Figure
shows that the light fields 5 and 6 are activated,
indicating a desired setpoint of 3 metres with a sensor measuring
range from 0 to 6 metres. The setting range is equal to the sensor
measuring range.
Fig. 27
Setpoint set to 3 metres, differential-pressure control
TM
05
48
48
35
12
Pos.
Symbol Description
1
Grundfos Eye
Shows the operating status of the pump.
For further information, see section
.
2
-
Light fields for indication of setpoint.
3
Changes the setpoint.
Resets warnings and alarms when you
press one of the buttons briefly.
4
Enables radio communication with
Grundfos GO and other products of the
same type.
When you try to establish radio
communication between the pump and
Grundfos GO or another pump, the green
indicator light in Grundfos Eye will flash
continuously. Press
on the pump control
panel to enable radio communication with
Grundfos GO and other products of the
same type.
5
Makes the pump ready for operation or
starts/stops the pump.
Start:
If you press the button when the pump is
stopped, the pump will only start if you have
not enabled another function with higher
priority. See section
.
Stop:
If you press the button when the pump is
running, the pump will always stop. Then
the "Stop" text next to the button will
illuminate.
1
2
3
4
5
Stop
T
M
05
48
94
35
1
2
0
6
3
m