background image

English (GB)

13

7. Universal-head pumps 

7.1 General description

Automatic universal-head shower pumps are designed to operate 
automatically in installations where the shower outlets are above 
the level of the cold-water storage tank.
Shower pumps, types STN, SSN, STR2 CN and SSR2 CN, 
feature independent pressure and flow controls, with built-in non-
return valves and stainless-steel expansion tanks in each pump 
end. This system ensures complete hot- and cold-water system 
isolation with stable control over a very wide flow range.

Fig. 30

Definition of universal-head pumps

7.2 Dry-running protection

STN, SSN, STR2 CN and SSR2 CN universal-head pumps 
feature dry-running protection to avoid damage to seals caused 
by water starvation. This condition is possible if the water supply 
fails, for instance if the water storage is insufficient or the pump 
strainers are blocked.
If the pump runs for 60 seconds with an insufficient water supply, 
the pump will stop and "lock out".

Fig. 31

Dry-running protection

Resetting the "lock out"

To reset the pump, switch off the power supply for ten seconds. 

Fig. 32

Resetting dry-running protection

When the power supply is switched on again, the pump will run 
for a few seconds to recharge the tanks. If it continues to run and 
there is no demand, this would indicate that one of the following 
situations is still present:
• No water in the system.
• Blocked strainer.
• Air which has not yet cleared.

7.3 Connecting the pump

• Follow general instructions in section 

4. Installation

.

• Minimum head of water to supply the pump can be found on 

the nameplate.

• Maximum static head of 8 metres, i.e. the highest point of the 

system must be less than 8 metres above the pump. See fig. 
33.

Fig. 33

Maximum static head

• Connect the pump side with the larger expansion tank to cold 

water and the pump side with the smaller expansion tank to 
hot water.

Fig. 34

Expansion tanks

7.4 Operating instructions

Taps and valves used on the "pressure system" must be fully 
turned off when not in use to avoid that the pump runs 
reciprocating on and off.

7.5 Installation options

Lavatory cisterns

If the pump is to supply a lavatory cistern, take the precautions 
below to avoid frequent starting and stopping of the pump due to 
low flow rates.
If possible, best practice is to supply the cistern from the mains 
water supply. If this is not possible, we recommend a "Torbeck" or 
equilibrium valve. If either of these are not possible, the following 
instructions should be followed:
• A: The pump is supplied with two expansion or pressure tanks. 

They have capacities of 500 ml and 300 ml. 
The larger tank must be used on the cold side of the pump.

• B: The cistern-filling pipe must be as free-flowing as possible 

with all flow restrictors removed.
It is possible to change the tanks from one side of the pump to 
the other. When doing so, take care to ensure that none of the 
fibre washers are lost.

Washer dryers

• Only brass pumps must be used for these applications.

T

M

05

 73

1

3

 46

1

4

TM

05 731

4 091

3

T

M

05

 73

15

 09

13

Continued dry running will lead to overheating of the 
shaft seals and eventually to a water leak.

> 227 litres 

(50 gallons) 

60 sec.

ON

OFF

I

/ON

0/OFF

10 sec.

RESET

=

TM

05

 73

10

 09

13

TM

0

5

 7

314

 0

913

Max. 8 m

Hot-water 
expansion tank

Cold-water

expansion tank

Summary of Contents for SSN

Page 1: ...Shower pumps SSR2 SSR2 CN STR2 STR2 CN SSP STP SSN and STN Installation and operating instructions GRUNDFOS INSTRUCTIONS...

Page 2: ...2...

Page 3: ...Table of contents 3 Shower pumps English GB Functional profile and user manual 4 T rk e TR Functional profile and user manual 18 Appendix 32 Declaration of conformity 34...

Page 4: ...ding 15 9 1 Positive head pumps STP SSP STR2 SSR2 15 9 2 Universal head pumps STN SSN STR2 CN and SSR2 CN 16 10 How it works 17 10 1 Universal head pumps 17 11 Engineer check list 17 12 Maintenance an...

Page 5: ...ath or serious personal injury The unit must be connected to a switched spur fused at 5 A 10 A on models STP 4 0 B and STN 4 0 B with a minimum contact gap of 3 mm in all poles Metal pipes must be ear...

Page 6: ...e tank Example S T P 2 0 B S Shower pump T S Twin impeller Single impeller P N L C R Positive head Universal negative head Low voltage Centrifugal Regenerative Maximum head bar Material B C CN Brass C...

Page 7: ...um height difference Install the pump in accordance with the Water Supply Water Fittings regulations 1999 Position the pump at the base of the hot water cylinder See fig 7 Fig 7 Positioning the pump i...

Page 8: ...hot and cold water Avoid blanked off pipes Avoid restrictions in the flexible hoses Secure down all pipes to minimise noise and vibration Fig 11 Fixing the pipes Fig 12 Pipe installation examples 4 2...

Page 9: ...ing of isolating valves Strainers Fit the strainers supplied with the STR2 and SSR2 on the inlet connections See fig 16 1 Fit the strainer washer to the inlet connection 2 Fit the plain hose washer to...

Page 10: ...6700 2006 to eliminate the risk of lime scale and cavitation 4 7 Installation options This section gives you an overview of your options during installation Positioning the pump Inlet head of at least...

Page 11: ...s been switched off and that it cannot be accidentally switched on DANGER Electric shock Death or serious personal injury The unit must be connected to a switched spur fused at 5 A 10 A on models STP...

Page 12: ...nspect for leaks after operation 12 Check that all hot water connections are tight and not leaking when the hot water has been run for several minutes See fig 28 Fig 29 Re tighten connections after op...

Page 13: ...ater to supply the pump can be found on the nameplate Maximum static head of 8 metres i e the highest point of the system must be less than 8 metres above the pump See fig 33 Fig 33 Maximum static hea...

Page 14: ...current See pump nameplate Insulation class 155 F Miscellaneous data Sound power level The sound power level of the pump is lower than 70 dB A Enclosure class IPx2 STP SSP STR2 SSR 2 STR2 CN SSR2 CN...

Page 15: ...dset and allowing the hose to hang into the shower tray or bath Operate maximum hot and cold flow for at least five minutes each For fixed head showers remove the shower rose and connect a length of h...

Page 16: ...h For fixed head showers remove the shower rose and connect a length of hose hanging into the shower tray or bath 4 The pump runs continuously a A flow demand still exists Check the installation for l...

Page 17: ...t point of pipes must be at least 250 mm below the base of the cold water storage tank not applicable for universal head pumps Hot water temperature must not exceed 60 C cylinder must have thermostat...

Page 18: ...r STP SSP STR2 SSR2 29 9 2 niversal kafa pompalar STN SSN STR2 CN ve SSR2 CN 30 10 Nas l al r 31 10 1 niversal kafa pompalar 31 11 M hendis kontrol listesi 31 12 Bak m ve servis 31 13 Hurdaya karma 31...

Page 19: ...kla a lamayaca ndan emin olun TEHL KE Elektrik arpmas l m veya ciddi yaralanma nite t m kutuplarda minimum 3 mm ba lant bo lu u ile 5 A sigorta ayar na sahip bir anahtarl d meye ba l olmal d r STP 4...

Page 20: ...ebeke kayna ba lant s rnek S T P 2 0 B S Du Pompas T S ift arkl Tek arkl P N L C R Pozitif bas n Evrensel negatif bas n D k gerilim Santrif j Rejeneratif Maksimum basma y ksekli i bar Malzeme B C CN...

Page 21: ...z ekil 6 ekil 6 Minimum y kseklik fark Pompay 1999 su temini su te hizatlar y netmeli ine uygun olarak monte edin Pompay s cak su silindirinin taban na yerle tirin Bkz ekil 7 ekil 7 Pompan n s cak su...

Page 22: ...ve so uk su i in ayr ebeke kayna kullan n Contal borulardan ka n n Esnek hortumlarda olu acak k s tlama ve zorlamalar nleyin G r lt ve titre imi minimize etmek i in t m borular sabitleyin ekil 11 Boru...

Page 23: ...tak lmas Filtreler STR2 ve SSR2 ile birlikte temin edilen filtreleri giri ba lant lar na tak n Bkz ekil 16 1 Filtre rondelas n giri ba lant s na tak n 2 D z hortum rondelas n tahliye ba lant s na tak...

Page 24: ...nca 60 C yi ge memelidir 4 7 Kurulum se enekleri Bu b l mde kurulum se enekleri verilmektedir Pompan n yerle tirilmesi SSP STP SSN STN ve STR pompalar i in en az 1 m giri basma y ksekli i gerekmektedi...

Page 25: ...dan ve yanl l kla a lamayaca ndan emin olunuz TEHL KE Elektrik arpmas l m veya ciddi yaralanma nite t m kutuplarda minimum 3 mm ba lant bo lu u ile 5 A sigorta ayar na sahip bir anahtarl d meye ba l o...

Page 26: ...l 28 al t rd ktan sonra s z nt kontrol yap n 12 S cak su birka dakika boyunca ak t ld ktan sonra t m s cak su ba lant lar n n s k oldu undan ve su s zd rmad ndan emin olun Bkz ekil 28 ekil 29 al t rd...

Page 27: ...sim levhas nda yer al r Maksimum statik bas n 8 metredir yani sistemin en y ksek noktas pompan n en fazla 8 metre zerinde olmal d r Bkz ekil 33 ekil 33 Maksimum statik bas n Pompan n b y k geni leme t...

Page 28: ...i Nominal ak m Pompa etiketine bak n z zolasyon s n f 155 F e itli veriler Ses g c seviyesi Pompan n ses seviyesi 70 dB A den azd r Koruma s n f IPx2 STP SSP STR2 SSR 2 STR2 CN SSR2 CN STN SSN Maksimu...

Page 29: ...erin Maksimum s cak ve so uk ayarlar n her birinde be dakika boyunca suyu ak t n Duvar du tak ml du larda du ba l n kar p hortuma ba layarak du teknesine veya k vete do ru salland r n c Ak anahtar ama...

Page 30: ...sine veya k vete do ru salland r n 4 Pompa s rekli olarak al r a Debi gereksinimi h l mevcut S z nt lar i in tesisat kontrol edin b Bas n alteri ar zal Ayarlama ve de i tirme bilgileri i in yetkili se...

Page 31: ...250 mm alt nda olmal d r niversal kafa pompalar i in ge erli de ildir S cak suyun s s 60 C yi ge memelidir silindirde termostat bulunmal d r Yukar daki i lemler ba ar l bir sonu vermezse ngiltere i in...

Page 32: ...of installation for positive head pumps and installation heights required TM05 8352 2413 The highest point of pipework must be at least 250 mm below the cold water storage tank See pump nameplate for...

Page 33: ...3 Fig 2 Example of installation of universal head pumps and installation heights required TM05 8351 2413 Maximum 8 m See pump nameplate for minimum and maximum inlet heads from water level to pump suc...

Page 34: ...yla ilgili durumun a a daki Konsey Direktifleriyle uyumlu oldu unu ve bununla ilgili olarak t m sorumlulu un bize ait oldu unu beyan ederiz Low Voltage Directive 2014 35 EU Standards used EN60335 1 20...

Page 35: ...8 5005 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznes...

Page 36: ...7019 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding...

Reviews: