background image

English (GB)

12

6. Startup

1. Turn on the water supply. Allow the system to fill.
2. Immediately inspect for any leaks.

Fig. 25

Inspect for leaks before operation

3. With the pump not running, allow maximum water flow, for 

example remove handset from shower hose.

4. Operate maximum hot and cold flows for at least two minutes 

to flush out all debris. See fig. 26.

Fig. 26

Operating hot- and cold-water taps

5. Switch on the power supply, run the pump for a few minutes, 

switch off, drain down and clean the inlet strainers. See fig. 
27.

Fig. 27

Cleaning the inlet strainer

For SSN, SSP, STN and STP pumps, remove the inlet hose from 
the pump, and the strainer basket can be removed by hand or 
with long-nosed pliers.
6. Replace the inlet strainers and reconnect the hoses.
7. Turn on the water supply. With the power supply off, allow 

maximum water flow, for example remove handset from 
shower hose.

8. Operate maximum hot and cold flows for at least five minutes 

each to ensure air is thoroughly purged from the system.

9. Replace handset on shower hose.
10. Switch on the power supply. 
11. Operate the pump in both full hot and cold modes for at least 

two minutes each while inspecting for leaks.

Fig. 28

Inspect for leaks after operation

12. Check that all hot-water connections are tight and not leaking, 

when the hot water has been run for several minutes. See fig. 
28.

Fig. 29

Re-tighten connections after operation

The first few times the pump is used, the insulating varnish used 
on the pump motor may give off an odour. This is perfectly normal 
and will diminish with use.

6.1 Shaft seal run-in

The seal faces are lubricated by the pumped liquid, meaning that 
there may be a certain amount of leakage from the shaft seal.
When the pump is started up for the first time, or when a new 
shaft seal is installed, a certain run-in period is required before 
the leakage is reduced to an acceptable level. The time required 
for this depends on the operating conditions, i.e. every time the 
operating conditions change, a new run-in period will be started.
Under normal conditions, the leaking liquid will evaporate. As a 
result, no leakage will be detected.

Do not start the pump until it has been filled with 
liquid.

Before startup, flush the system with clean water and 
drain to remove possible impurities.

T

M

05

 73

0

8

 09

1

3

TM

05

 73

07 

09

13

TM

05

 73

17

 10

13

0/OFF

2 min.

0/OFF

I

/ON

10 min.

T

M

05

 73

09

 09

13

T

M

05

 73

11

 0

9

1

3

Run the pump for five minutes or more at least once 
every four weeks in order to prevent the pump from 
seizing up. Scale buildup can cause the pump parts 
to stick.

I

/ON

I

/ON

2 min.

Summary of Contents for SSN

Page 1: ...Shower pumps SSR2 SSR2 CN STR2 STR2 CN SSP STP SSN and STN Installation and operating instructions GRUNDFOS INSTRUCTIONS...

Page 2: ...2...

Page 3: ...Table of contents 3 Shower pumps English GB Functional profile and user manual 4 T rk e TR Functional profile and user manual 18 Appendix 32 Declaration of conformity 34...

Page 4: ...ding 15 9 1 Positive head pumps STP SSP STR2 SSR2 15 9 2 Universal head pumps STN SSN STR2 CN and SSR2 CN 16 10 How it works 17 10 1 Universal head pumps 17 11 Engineer check list 17 12 Maintenance an...

Page 5: ...ath or serious personal injury The unit must be connected to a switched spur fused at 5 A 10 A on models STP 4 0 B and STN 4 0 B with a minimum contact gap of 3 mm in all poles Metal pipes must be ear...

Page 6: ...e tank Example S T P 2 0 B S Shower pump T S Twin impeller Single impeller P N L C R Positive head Universal negative head Low voltage Centrifugal Regenerative Maximum head bar Material B C CN Brass C...

Page 7: ...um height difference Install the pump in accordance with the Water Supply Water Fittings regulations 1999 Position the pump at the base of the hot water cylinder See fig 7 Fig 7 Positioning the pump i...

Page 8: ...hot and cold water Avoid blanked off pipes Avoid restrictions in the flexible hoses Secure down all pipes to minimise noise and vibration Fig 11 Fixing the pipes Fig 12 Pipe installation examples 4 2...

Page 9: ...ing of isolating valves Strainers Fit the strainers supplied with the STR2 and SSR2 on the inlet connections See fig 16 1 Fit the strainer washer to the inlet connection 2 Fit the plain hose washer to...

Page 10: ...6700 2006 to eliminate the risk of lime scale and cavitation 4 7 Installation options This section gives you an overview of your options during installation Positioning the pump Inlet head of at least...

Page 11: ...s been switched off and that it cannot be accidentally switched on DANGER Electric shock Death or serious personal injury The unit must be connected to a switched spur fused at 5 A 10 A on models STP...

Page 12: ...nspect for leaks after operation 12 Check that all hot water connections are tight and not leaking when the hot water has been run for several minutes See fig 28 Fig 29 Re tighten connections after op...

Page 13: ...ater to supply the pump can be found on the nameplate Maximum static head of 8 metres i e the highest point of the system must be less than 8 metres above the pump See fig 33 Fig 33 Maximum static hea...

Page 14: ...current See pump nameplate Insulation class 155 F Miscellaneous data Sound power level The sound power level of the pump is lower than 70 dB A Enclosure class IPx2 STP SSP STR2 SSR 2 STR2 CN SSR2 CN...

Page 15: ...dset and allowing the hose to hang into the shower tray or bath Operate maximum hot and cold flow for at least five minutes each For fixed head showers remove the shower rose and connect a length of h...

Page 16: ...h For fixed head showers remove the shower rose and connect a length of hose hanging into the shower tray or bath 4 The pump runs continuously a A flow demand still exists Check the installation for l...

Page 17: ...t point of pipes must be at least 250 mm below the base of the cold water storage tank not applicable for universal head pumps Hot water temperature must not exceed 60 C cylinder must have thermostat...

Page 18: ...r STP SSP STR2 SSR2 29 9 2 niversal kafa pompalar STN SSN STR2 CN ve SSR2 CN 30 10 Nas l al r 31 10 1 niversal kafa pompalar 31 11 M hendis kontrol listesi 31 12 Bak m ve servis 31 13 Hurdaya karma 31...

Page 19: ...kla a lamayaca ndan emin olun TEHL KE Elektrik arpmas l m veya ciddi yaralanma nite t m kutuplarda minimum 3 mm ba lant bo lu u ile 5 A sigorta ayar na sahip bir anahtarl d meye ba l olmal d r STP 4...

Page 20: ...ebeke kayna ba lant s rnek S T P 2 0 B S Du Pompas T S ift arkl Tek arkl P N L C R Pozitif bas n Evrensel negatif bas n D k gerilim Santrif j Rejeneratif Maksimum basma y ksekli i bar Malzeme B C CN...

Page 21: ...z ekil 6 ekil 6 Minimum y kseklik fark Pompay 1999 su temini su te hizatlar y netmeli ine uygun olarak monte edin Pompay s cak su silindirinin taban na yerle tirin Bkz ekil 7 ekil 7 Pompan n s cak su...

Page 22: ...ve so uk su i in ayr ebeke kayna kullan n Contal borulardan ka n n Esnek hortumlarda olu acak k s tlama ve zorlamalar nleyin G r lt ve titre imi minimize etmek i in t m borular sabitleyin ekil 11 Boru...

Page 23: ...tak lmas Filtreler STR2 ve SSR2 ile birlikte temin edilen filtreleri giri ba lant lar na tak n Bkz ekil 16 1 Filtre rondelas n giri ba lant s na tak n 2 D z hortum rondelas n tahliye ba lant s na tak...

Page 24: ...nca 60 C yi ge memelidir 4 7 Kurulum se enekleri Bu b l mde kurulum se enekleri verilmektedir Pompan n yerle tirilmesi SSP STP SSN STN ve STR pompalar i in en az 1 m giri basma y ksekli i gerekmektedi...

Page 25: ...dan ve yanl l kla a lamayaca ndan emin olunuz TEHL KE Elektrik arpmas l m veya ciddi yaralanma nite t m kutuplarda minimum 3 mm ba lant bo lu u ile 5 A sigorta ayar na sahip bir anahtarl d meye ba l o...

Page 26: ...l 28 al t rd ktan sonra s z nt kontrol yap n 12 S cak su birka dakika boyunca ak t ld ktan sonra t m s cak su ba lant lar n n s k oldu undan ve su s zd rmad ndan emin olun Bkz ekil 28 ekil 29 al t rd...

Page 27: ...sim levhas nda yer al r Maksimum statik bas n 8 metredir yani sistemin en y ksek noktas pompan n en fazla 8 metre zerinde olmal d r Bkz ekil 33 ekil 33 Maksimum statik bas n Pompan n b y k geni leme t...

Page 28: ...i Nominal ak m Pompa etiketine bak n z zolasyon s n f 155 F e itli veriler Ses g c seviyesi Pompan n ses seviyesi 70 dB A den azd r Koruma s n f IPx2 STP SSP STR2 SSR 2 STR2 CN SSR2 CN STN SSN Maksimu...

Page 29: ...erin Maksimum s cak ve so uk ayarlar n her birinde be dakika boyunca suyu ak t n Duvar du tak ml du larda du ba l n kar p hortuma ba layarak du teknesine veya k vete do ru salland r n c Ak anahtar ama...

Page 30: ...sine veya k vete do ru salland r n 4 Pompa s rekli olarak al r a Debi gereksinimi h l mevcut S z nt lar i in tesisat kontrol edin b Bas n alteri ar zal Ayarlama ve de i tirme bilgileri i in yetkili se...

Page 31: ...250 mm alt nda olmal d r niversal kafa pompalar i in ge erli de ildir S cak suyun s s 60 C yi ge memelidir silindirde termostat bulunmal d r Yukar daki i lemler ba ar l bir sonu vermezse ngiltere i in...

Page 32: ...of installation for positive head pumps and installation heights required TM05 8352 2413 The highest point of pipework must be at least 250 mm below the cold water storage tank See pump nameplate for...

Page 33: ...3 Fig 2 Example of installation of universal head pumps and installation heights required TM05 8351 2413 Maximum 8 m See pump nameplate for minimum and maximum inlet heads from water level to pump suc...

Page 34: ...yla ilgili durumun a a daki Konsey Direktifleriyle uyumlu oldu unu ve bununla ilgili olarak t m sorumlulu un bize ait oldu unu beyan ederiz Low Voltage Directive 2014 35 EU Standards used EN60335 1 20...

Page 35: ...8 5005 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznes...

Page 36: ...7019 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding...

Reviews: