10.3.12 Operating range
How to set the operating range:
• Set the min. curve within the range from max. curve to 12 % of
maximum performance. The pump is factory-set to 24 % of
maximum performance.
• Set the max. curve within the range from maximum
performance (100 %) to min. curve.
The area between the min. and max. curves is the operating
range.
Fig. 35
Setting of the min. and max. curves in % of maximum
performance
10.3.13 Motor bearing monitoring (only three-phase pumps)
The motor bearing monitoring function can be set to these values:
•
Active
•
Not active.
When the function is set to
Active
, a counter in the controller will
start counting the mileage of the bearings. See section
10.2.7 Lubrication status of motor bearings (only 15 - 30 Hp)
on
page 18.
10.3.14 Confirming relubrication/replacement of motor
bearings (only three-phase pumps)
This function can be set to these values:
•
Relubricated
(only 15 - 30 Hp)
•
Replaced
•
Nothing done
.
When the bearing monitoring function is
Active,
the controller will
give a warning indication when the motor bearings are due to be
relubricated or replaced. See section
10.1.3 Fault indications
on
page 16.
When the motor bearings have been relubricated or replaced,
confirm this action in the above display by pressing "OK".
10.3.15 Standstill heating (only three-phase pumps)
The standstill heating function can be set to these values:
•
Active
•
Not active.
When the function is set to
Active
, an AC voltage will be applied
to the motor windings. The applied voltage will ensure that
sufficient heat is generated to avoid condensation in the motor.
TM
05
32
39
10
12
T
M
00
77
47
18
9
6
6: GND (frame)
5: +10 V
4 Setpoint input
3: GND (frame)
2: Start/stop
Group 1
Group 2
Group
3
1: Digital input 2
9: GND (frame)
8: +24 V
7: Sensor input
B: RS-485B
Y: Screen
A: RS-485A
Q
H
100 %
Max. curve
12 %
Min. curve
Oper
ating
rang
e
1
1RWH
1
1RWH
The counter will continue counting even if the
function is switched to Not active, but a warning
will not be given when it is time for relubrication.
When the function is switched to Active again,
the accumulated mileage will again be used to
calculate the relubrication time.
1
1RWH
1
1RWH
Relubricated cannot be selected for a period of
time after confirming relubrication.
DBP-1 - GRUNDFOS PUMP CRE - 99392005