Sensor signals
• Voltage signal
0-10 VDC, R
i
> 50 k
˖
(via internal voltage supply).
Tolerance: + 0 %/- 3 % at maximum voltage signal.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 1640 ft.
• Current signal
DC 0-20 mA/4-20 mA, R
i
= 175
˖
.
Tolerance: + 0 %/- 3 % at maximum current signal.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 1640 ft
Internal power supplies
• 10 V power supply for external potentiometer:
Max. load: 2.5 mA.
Short-circuit protected.
• 24 V power supply for sensors:
Max. load: 40 mA.
Short-circuit protected.
Signal relay output
Potential-free changeover contact.
Maximum contact load: 250 VAC, 2 A, cos
˳
0.3 - 1.
Minimum contact load: 5 VDC, 10 mA.
Screened cable: 0.5 - 2.5 mm
2
/ 28-12 AWG.
Maximum cable length: 1640 ft.
Bus input
Grundfos bus protocol, GENIbus protocol, RS-485.
Screened 3-core cable: 0.2 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 1640 ft
22. Technical data - three-phase pumps,
1 - 10 Hp
22.1 Supply voltage
3 x 380-480 V - 10 %/+ 10 %, 50/60 Hz - 2 %/+ 2 %, PE.
Cable: Max 10 mm
2
/ 8 AWG.
Use min. 158 °F (70 °C) copper conductors only.
Recommended fuse sizes
Motor sizes from 1 - 7.5 Hp: Max. 16 A.
Motor size 10 Hp: Max. 32 A.
Standard as well as quick-blow or slow-blow fuses may be used.
22.2 Overload protection
The overload protection of the E-motor has the same
characteristic as an ordinary motor protector. As an example, the
E-motor can stand an overload of 110 % of I
nom
for 1 min.
22.3 Leakage current
The leakage currents are measured in accordance with
EN 61800-5-1.
22.4 Inputs/output
Start/stop
External potential-free contact.
Voltage: 5 VDC.
Current: < 5 mA.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Digital
External potential-free contact.
Voltage: 5 VDC.
Current: < 5 mA.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Setpoint signals
• Potentiometer
0-10 VDC, 10 k
˖
(via internal voltage supply).
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 328 ft.
• Voltage signal
0-10 VDC, R
i
> 50 k
˖
.
Tolerance: + 0 %/- 3 % at maximum voltage signal.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 1640 ft.
• Current signal
DC 0-20 mA/4-20 mA, R
i
= 175
˖
.
Tolerance: + 0 %/- 3 % at maximum current signal.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 1640 ft.
Sensor signals
• Voltage signal
0-10 VDC, R
i
> 50 k
˖
(via internal voltage supply).
Tolerance: + 0 %/- 3 % at maximum voltage signal.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 1640 ft.
• Current signal
DC 0-20 mA/4-20 mA, R
i
= 175
˖
.
Tolerance: + 0 %/- 3 % at maximum current signal.
Screened cable: 0.5 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 1640 ft.
Internal power supplies
• 10 V power supply for external potentiometer:
Max. load: 2.5 mA.
Short-circuit protected.
• 24 V power supply for sensors:
Max. load: 40 mA.
Short-circuit protected.
Signal relay output
Potential-free changeover contact.
Maximum contact load: 250 VAC, 2 A, cos
˳
0.3 - 1.
Minimum contact load: 5 VDC, 10 mA.
Screened cable: 0.5 - 2.5 mm
2
/ 28-12 AWG.
Maximum cable length: 1640 ft.
Bus input
Grundfos bus protocol, GENIbus protocol, RS-485.
Screened 3-core cable: 0.2 - 1.5 mm
2
/ 28-16 AWG.
Maximum cable length: 1640 ft.
Motor size
[kW]
Leakage current
[mA]
1 - 3 Hp (supply voltage < 460 V)
1 - 3 Hp (supply voltage > 460 V)
< 3.5
< 5
5 to 7.5 Hp
< 5
10 Hp
< 10
DBP-1 - GRUNDFOS PUMP CRE - 99392005